9. TROUBLESHOOTING
Fault
Possible Causes
Remedial measures
Water not heating
Electrical supply fault
Check electrical supply. Verify the operation of Audax and
Inoxstor controls.
Legionalla control not
working (temperature
does not reach 60°C)
Thermostat fault
Check immersion high limit thermostat operation, replace if
necessary
Anti-Legionella Timer incorrectly set
Check settings and operation of anti-legionella timer. Replace
if necessary.
Discharge of water
from Pressure Relief
Valve (continuously)
Excessive supply water pressure
Check Pressure Reducing Valve is fitted and operational. Re
-
place Safety Group if necessary.
Faliure of Pressure Relief Valve
Check valve is seating properly. Replace Safety Group if nec-
essary.
Discharge of water
from Pressure Relief
Valve (intermittently)
Inadequate expansion in system
Check expansion vessel size and pre-charge pressure.
Water supply pressure exceeds 3.5 bar
Check Pressure Reducing Valve is operational. Replace Safety
Group if necessary.
Water or steam from
Pressure Relief Valve
Thermostat fault
Check operation of high limit thermostat. Replace if neces-
sary.
No water flow
Inlet valves incorrectly fitted
Check all valves are correctly installed in accordance with flow
direction arrows
Supply water not turned on
Check water supply is on
Blockage in water supply
Check for obstructions. If a pressure reducing valve is fitted
check strainer is not blocked.
Milky water
Oxygenated water
Water from a pressurised system releases oxygen bubbles
when flowing. The milkiness will disappear after a short time.