40 cm
40 cm
40 cm
13
Installation
POSITIONING AND LIMITATIONS
For all information and any further clarifications, refer to the
local national regulations in force.
The minimum volume of the room where to install the appli-
ance is indicated by the manufacturer and, however, it is greater
than 15 m
3
.
Check that the room floor is suitable to withstand the weight
of the boiler.
In the event of simultaneous installation with other central heat-
ing appliances, provide for suitable air inlets for each of them
(according to the instructions of each product).
It is not permitted to install the product:
•
in areas that have appliances supplied with
liquid fuel with continuous or discontinuous
operation that take combustion air from the
room in which they are installed, or;
•
in areas where type B gas appliances are in-
stalled to heat the rooms, with or without pro-
duction of domestic hot water, and in adjacent
or communicating rooms, or;
•
in areas in which the measured operating nega-
tive pressure between the external and internal
technical room exceeds 4 Pa.
It is forbidden to position the product in bedrooms, bath-
rooms, garages and, in general, in places with a fire risk.
BOILER ROOM
Check that the room meets the requirements and characteristics
of regulations in force. Also, the room must at least provide as
much airflow as required for regular combustion. Therefore, it
is required to provide openings on the walls in the room that
meet the following requirements:
• Have a minimum free section of 6 cm
2
for every 1 kW (859.64
kcal/h). The minimum section of the opening must not be
less than 100 cm
2
. The section can be calculated by using the
following:
S = K * Q ≥ 100 cm
2
Where “S” is expressed in cm
2
, “Q” in kW, “K” = 6 cm
2
/kW
• The opening must be situated in the bottom part of an exter-
nal wall, preferably on the opposite side of the combustion
gas exhaust.
40 cm
Min.
100 cm
2
Distance from objects
The boiler must be installed in such a way that it can be inspected
from all sides. Therefore, you must respect a minimum distance
of 40 cm at the back and sides. It is also recommended to keep
the pellets and flammable materials at a safe distance.