Error
Code
Anomaly signalled
Cause
Solution
38
Loss of flame signal
This occurs when the boiler is ignited correctly and the burner
flame switches off unexpectedly; a new ignition attempt is
performed and if normal conditions are restored, the boiler does
not have to be reset (this anomaly can be checked in the list of
errors “P19” in the “M1” menu).
If normal conditions are restored the boiler
restarts without having to be reset (1) (2).
45
High ΔT
If the board detects a sudden and unexpected rise in ΔT between
the system flow probe and return probe, the boiler limits the burner
output to prevent damaging the condensation module; when the
correct ΔT has been restored, the boiler resumes normal operation.
If normal conditions are restored the boiler
restarts without having to be reset (1) (2).
48
System probe anomaly
The board detects an anomaly on the system flow NTC probe.
(1) (3)
49
High temperature
block on return probe
This occurs when the heat exchanger return circuit reaches a
temperature that is too high.
Make sure that water circulates properly in
the boiler and that the three-way valve works
properly. Press the Reset button (1) (2).
50
External probe
missing or faulty
In the event the external probe is not connected or is faulty, the
anomaly is indicated.
Check the external probe connection (1)
(3).
58
Heat pump anomaly
In the event of a heat pump anomaly, room heating is ensured by
the boiler. All heat pump functions (room heating and cooling) are
inhibited.
Check the type of anomaly directly
on the heat pump display (see relative
instructions manual).
Attention:
in presence of cold temperatures
the heat pump can be activated in defrosting
mode, indicated on the heat pump with code
O21. This operation is not an anomaly.
In the event the heat pump does not
feature any anomaly, check that the
domestic hot water inlet probe is working
properly (1) (3).
(1) If the block or anomaly persists, contact an authorised company (e.g. Immergas Technical After-Sales Service).
(2) The boiler does not start, the heat pump stays active to satisfy the room heating and cooling requests.
(3) The heat pump does not start, the boiler stays active to satisfy the room heating and domestic hot water production requests.