3.4 INFORMATION MENU.
Pressing the buttons (3 and 4) for 5 seconds, the
“Information menu” is activated, which allows
to display some boiler functioning parameters.
To scroll through the various parameters, press
(3 and 4), to exit from the menu press buttons
(3 and 4) again for 5 seconds or press button (2)
for 5 seconds or wait for 60 seconds.
List of parameters.
Parameter
N°
Description
d1
Displays the flame signal (uA)
d2
Displays the primary exchanger
output instant heating flow
temperature
d3
Displays the instant output
temperature from the DHW
exchanger
d4
Displays the temperature set for
the central heating set (if remote
control is present)
d5
Displays the temperature set for
the DHW set (if remote control
is present)
d6
Displays the external environ-
ment temperature (if external
probe is present). If the tempera-
ture is below zero, the value is
displayed flashing.
3.5 PROGRAMMING THE P.C.B.
The boiler is prepared for possible programming
of several operation parameters. By modifying
these parameters as described below, the boiler
can be adapted according to specific needs.
To access the programming phase, proceed as
follows:
- press buttons (1) and (2) at the same time for
approximately 8 seconds;
- Using buttons (3) and (4), select the parameter
to be changed indicated in the following table:
List of
parameters
Description
P1
Boiler mode
(DO NOT USE)
P2
Display lighting
P3
DHW thermostat
P4
Minimum CH output
P5
Maximum CH output
P6
Central heating ignitions
timer
P7
Central heating ramp timer
P8
Heating switch-on delay
request from room thermostat
and remote control
P9
Solar mode
- adjust the corresponding value consulting the
table using buttons (5) and (6);
- confirm the set value pressing the Reset button
(1) for approximately 3 seconds; by pressing
keys (3) + and (4) - at the same time exit the
function without memorising the modifica-
tions made.
N.B.:
after a period of time, without touching
any keys, the operation cancels automatically.
Boiler mode.
It establishes whether the boiler
functions in instant or storage mode.
Boiler mode (P1)
Range of values which can
be set
Standard
setting
0 - instant boiler
1 - Boiler with storage tank
0
Display lighting.
Establishes the display light-
ing mode.
Display lighting (P2)
Range of values which can
be set
Standard
setting
0 - Off
1 - Auto
2 - On
1
- Off:
the display is always lit with low intensity
- Auto:
the display lights up during use and
lowers after 5 seconds of inactivity. In the case
of anomaly the display flashes.
- On:
the display is always lit with high intensity.
DHW thermostat.
With the “correlated” ther-
mostat setting, boiler switch-off takes place on
the basis of the temperature set. While with
the setting of the “fixed” DHW thermostat the
switch-off temperature is fixed at the maximum
value independently from the value set on the
control panel.
DHW thermostat (P3)
Range of values which can
be set
Standard
setting
0 - Fixed
1 - Correlated
1
Heating output.
The boiler also has electronic
modulation that adapts the boiler potentiality to
the effective heating demand of the house. Then
the boiler works normally in a variable gas pres-
sure field between the minimum heating power
and the maximum heating power depending on
the system’s heating load.
N.B.:
the boiler is produced and calibrated in
the central heating phase at nominal output.
Approximately 10 minutes are needed to reach
the nominal heat output, which can be changed
using the parameter (P5).
N.B.:
the selection of the “Minimum heating
power” and “Maximum heating power” param-
eters, in the presence of a heating request, allows
switch-on of the boiler and power supply of the
modulator with current equal to the value of the
respective set value.
Minimum central heating output (P4)
Range of values which can
be set
Standard
setting
0 - 63%
Set ac-
cording
to factory
inspection
Maximum heating output (P5)
Range of values which can
be set
Standard
setting
0 - 99%
99
Central heating ignitions timer.
The boiler has
electronic timing, which prevents the burner
from igniting too often in central heating mode.
Central heating ignitions timer (P6)
Range of values which can
be set
Standard
setting
0 - 20 (0 - 10 minutes)
(01 equals 30 seconds)
6
(3’)
Central heating ramp timing.
In the ignition
phase, the boiler performs an ignition ramp in
order to arrive at the maximum power set.
Central heating ramp timer (P7)
Range of values which can
be set
Parametro
0 - 28 (0 - 14 minutes)
(01 equals 30 seconds)
28
(14’)