9
1-6
1-7
INS
TALLER
US
ER
MAINTEN
AN
CE TECHNI
CI
AN
1.7 IMMERGAS FLUE SYSTEMS.
Immergas supplies various solutions separately
from the boiler regarding the installation of air
intake terminals and flue extraction, which are
fundamental for boiler operation.
Important: The boiler must only be installed
together with an original Immergas air intake
and flue gas exhaust system. This system can be
identified by an identification mark and special
distinctive marking bearing the note: “not for
condensing boilers”.
The flue exhaust pipes must not be in contact with
or be near to flammable materials. Moreover,
they must not pass through buildings or walls
made of flammable material.
See following paragraphs for the detailed descrip-
tion of the kits available
Positioning of double lip seals.
For correct
positioning of lip seals on elbows and exten-
sions, follow the direction of assembly given in
figure (Fig. 1-6).
• Resistance factors and equivalent lengths. Each
flue extraction system component has a
Resist-
ance Factor
based on experimental tests and
specified in the table below. The resistance fac-
tor for individual components is independent
from the type of boiler on which it is installed
or the actual dimensions. It is, however, condi-
tioned by the temperature of the fluids that pass
through the pipe and therefore varies according
to applications for air intake or flue exhaust.
Each single component has a resistance cor-
responding to a certain length in metres of pipe
of the same diameter; the so-called
equivalent
length
, obtained from the ration between the
relative Resistance Factors.
All boilers have an
experimentally obtainable maximum Resistance
Factor equal to 100
. The maximum Resistance
Factor allowed corresponds to the resistance
encountered with the maximum allowed pipe
length for each type of Terminal Kit. This
information enables calculations to be made
in order to verify the possibility of various
configurations of flue extraction systems.
1.8 OUTDOOR INSTALLATION IN
PARTIALLY PROTECTED AREA.
N.B.:
a partially protected area is one in which the
appliance is not exposed to the direct action of the
weather (rain, snow, hail, etc..).
.
• Configuration type B, open chamber and fan
assisted.
The relevant terminal must be used for this
configuration (present in the intake kit for the
installation in question), which must be placed
on the central hole of the boiler (Fig. 1-8). Air
intake takes place directly from the environment
in which the boiler is installed and flue exhaust
in individual flue or to the outside.
In this configuration the boiler is classified as
type B
22
.
With this configuration:
- air intake takes place directly from the environ-
ment in which the boiler is installed and only
functions in permanently ventilated rooms;
- the flue exhaust must be connected to its own
individual flue or channelled directly into the
external atmosphere.
The technical regulations in force must be
respected.
• Fitting the cover kit.
To assemble and confi-
gure the cover kit correctly, please refer to the
relative instructions sheet.
Max. length of exhaust duct.
The flue pipe
(vertical or horizontal) can be
extended to a
max. length of 12 m straight route, using insulated
pipes
(Fig. 1-27). To prevent problems of fume
condensate in the exhaust pipe Ø 80, due to fume
cooling through the wall,
the length of the pipe
(not insulated) must be limited to just 5 m.
Example of installation with direct vertical
terminal in partially protected location.
When
the vertical terminal for direct discharge of com-
bustion fumes is used, a minimum gap of 300
mm must be left between the terminal and the
balcony above. The height X+Y+Z+W evaluated
with respect to the balcony above, must be equal
to or more than 2000 mm. (Fig. 1-9). The term W
must only be considered if the balcony above has
closed balustrade (W=0 if the balustrade is open).
• Configuration without cover kit (boiler
type C).
By leaving the side plugs fitted, it is possible
to install the appliance externally, in partially
covered places, without the cover kit. Installa-
tion takes place using the Ø60/100 and Ø80/125
concentric horizontal intake/ exhaust kits. Refer
to the paragraph relative to indoor installation.
In this configuration the top cover kit guarantees
additional protection for the boiler. It is recom-
mended but not compulsory.
Diaphragm installation.
For correct functioning
of the boiler it is necessary to install a diaphragm
on the outlet of the sealed chamber and before the
intake and exhaust pipe (Fig. 1-10). The choice
of suitable diaphragm takes place on the basis
of the type of pipe and its maximum extension:
this calculation can be carried out using the
following tables:
N.B.:
the diaphragms are supplied together with
the boiler.
Intake diaphragm installation.
For correct
boiler functioning with Ø 80 separator kits and
drain measuring > 1 m a diaphragm Ø 47 must
be installed on the sealed chamber intake hole
and before the intake pipe (Fig. 1-11). The choice
of suitable diaphragm takes place on the basis
of the type of pipe and its maximum extension:
this calculation can be carried out using the
following tables:
Summary of Contents for MINI EOLO 28 3E
Page 1: ...MINI EOLO 28 3E Instruction and warning booklet IE 1 038767ENG ...
Page 2: ......
Page 28: ...28 3 5 4 4 5 6 6 d d c INSTALLER USER MAINTENANCE TECHNICIAN ...
Page 32: ...32 ...
Page 33: ...33 ...
Page 34: ...34 ...
Page 35: ...35 ...