Mounting the vertical kit with aluminium tile
Ø 80/125 (Fig. 24)
To install the kit Ø 80/125 one must use the flanged
adapter kit in order to install the flue system Ø 80/125.
1. Install the concentric flange (2) on the central hole of the boi-
ler, positioning gasket (1) with the circular projections
downwards in contact with the boiler flange.
2. Tighten the concentric flange with the screws in the kit.
3. Replace the tiles with the aluminium sheet (4), shaping it to
ensure that rainwater runs off.
4. Position the fixed half-shell (5) on the aluminium tile;
5. Insert the intake-exhaust terminal (7);
6. Fit the Ø 80/125 concentric terminal pipe with the male side
(smooth) to the female side of the adapter (1) (with lip seals) up
to the end stop, making sure that the wall sealing plate (3) has
been fitted; this will ensure sealing and joining of the elements
making up the kit.
C32
1
2
3
4
5
6
7
24
The adapter kit includes (Fig. 24):
No.1 Gasket (1)
No.1 Adapter Ø 80/125 (2)
The Kit Ø 80/125 includes (Fig. 24):
No.1 Wall sealing plate (3)
No.1 Aluminium tile (4)
No.1 Fixed half-shell (5)
No.1 Mobile half-shell (6)
No.1 Concentric intake-exhaust terminal Ø 80/125 (7)
The remaining kit components must not be used
Extensions for Ø 80/125 vertical kit (Fig. 25)
The kit with this configuration can be extended to a max. straight
vertical length of 16 m, including the terminal.
If additional components are assembled, the length equivalent to
the maximum allowed must be subtracted.
In this case the special extensions must be requested.
C32
1
25
Key (Fig. C3225):
1 - Maximum length