28
STV50 ed 09/08
VICTRIX 50 Rev. 002
Breakage of the flow probe (B5) prevents boiler operation.
Triggering is indicated by error code “E32” or “E37” displayed on the boiler panel monitor.
A manual reset, performed by pressing the relative button, is required to restore operation.
NTC return probe breakage
(B5)
If a fan speed outside the minimum safety limit is detected (900 rpm) the burner is switched off.
Triggering is indicated by error code “E65” on the display of the boiler panel monitor.
A manual reset, performed by pressing the relative button, is required to restore operation.
Fan speed safety device
Breakage of the d.h.w. probe (B2) prevents boiler operation in the d.h.w. phase.
Triggering is indicated by error code “b33” or “b38” on the display of the boiler panel monitor.
Domestic hot water
NTC probe breakage
(B2)
(optional)
If there is no fan signal the burner is switched off.
Triggering is indicated by error code “E28” or “E29” on the display of the boiler panel monitor.
A manual reset, performed by pressing the relative button, is required to restore operation.
Fan safety device
Technical Documentation
Technical Documentation