34
STV50 ed 09/08
VICTRIX 50 Rev. 002
Indications and malfunctions (display board, 4-digit display).
(from the serial number 3918687)
Indications and malfunctions with manual rearming.
The board features a display that shows malfunctions or ope-
rating shutdowns by means of error codes.
The error codes preceded by the letter “E” are permanent
shutdowns.
Code "E"
Description
Remedy
00
Flame presence inhibited
Check detection electrode
Check electronic board
02
Ignition block
Check the gas valve
Check the electronic board
Check the electrode position
Check the flame signal at minimum higher
than 6Micro AµA
03
Gas valve supply error
Check the gas valve / electronic board
Change the electronic board
05, 11, 15,
16, 17, 44,
60
Internal block
(electronic)
Check the electronic board
Change the electronic board
04
Non-volatile block
(inhibit condition with no electric power)
Check the cause of the lock
06
Failure found at the electronic board input
Change the electronic board
Check the electronic board
07
Gas valve relay error
Check the gas valve / electronic board
Change the electronic board
12
Activation of overtemperature safety thermostat or activation of
flue thermostat
Check the water overtemperature ther-
mostat
Check the flue overtemperature thermo-
stat
13
Failure found at the electronic board output
Check the electronic board
Change the electronic board
14
Block in the flow probe control circuit
Check the flow probe / electronicboard
Change the electronic board
18
System flow temperature is too high
(over 95 °C)
Check the circulation of water in the
system
To eliminate the lock simply press the RESET button on the
boiler panel monitor.
Technical Documentation