AN
Id
Parameter
Parameter
Description
Range
Default
Customised
value
t0
Central heating set
point minimum
temperature
Defines the minimum flow temperature.
20
÷
50 °C
25
t1
Central heating set
point maximum
temperature
Defines the maximum flow temperature.
(t0
+
5)
÷
85 °C
85
t2
DHW thermostat
Establishes the boiler ignition and switch-off mode in DHW mode.
0 - Ignition occurs when the water contained in the storage tank drops by 3 °C
with respect to the temperature set and switches off when the temperature
is at the value set (solar deactivated)
1 - Ignition occurs when the water contained in the storage tank drops by 2 °C
with respect to the temperature set and switches off when the temperature
is at
+
1 °C with respect to the value set (solar deactivated)
2 - Ignition occurs when the water contained in the storage tank drops by
10 °C with respect to the temperature set and switches off when the
temperature is at the value set (Solar activated)
3 - Ignition occurs when the water contained in the storage tank drops by 5 °C
with respect to the temperature set and switches off when the temperature
is at the value set (Solar activated)
0
On = -3 °C
Off =
+
0 °C
1
On = -2 °C
Off =
+
1 °C
2
On = -10
Off =
+
0
3
On = -5 °C
Off =
+
0 °C
2
t3
-
Not used on this boiler model
-
-
t4
-
Not used on this boiler model
-
-
t5
Central heating
ignitions timer
The boiler has electronic timing, which prevents the burner from igniting
too often in central heating mode
0 - 600
seconds
(step 10 sec)
18
t6
Central heating
ramp timer
In the heating stage, the boiler performs an ignition ramp in order to reach
the maximum output set
0 - 840
seconds
(step 10 sec)
18
t7
CH ignition de-
lay from TA and
CR request
The boiler is set to switch-on immediately after a request. In the event of
particular systems (e.g. area systems with motorised thermostatic valves
etc.) it may be necessary to delay ignition
0 - 600
seconds
(step 10 sec)
0
t8
Display lighting
Establishes the display lighting mode.
0 Automatic:
the display lights up during use and dims after 15 seconds of
inactivity. In the event of an anomaly the display flashes.
1 Low:
the display is always lit with low intensity
2 High:
the display is always lit with high intensity.
0 - 2
0
t9
Display
Establishes what the indicator displays 14 (Fig. 2-1).
"Summer" mode:
0: the indicator is always off
1: circulator active, it displays the flow temperature
pump off the indicator is off
"Winter" mode:
0: it always displays the value set on the central heating selector
1: circulator active, it displays the flow temperature
pump off always displays the value set on the CH selector
0 - 1
1