35
3-14
INS
T
ALLER
US
ER
MAINTEN
AN
CE TECHNI
CI
AN
Victrix Maior 35 X TT 1 ErP
CO
2
at nominal
output
(99 %)
CO
2
at intermediate
output
(41 %)
CO
2
at minimum
output
(0 %)
G 20
9.50
±
0.80
9.00
±
0.80
9.00
±
0.80
G 31
10.50
±
1.00
10.00
±
1.00
10.00
±
1.00
N.B.:
measurements and calibration must be carried out by using regularly-
calibrated instruments.
3.20 YEARLY APPLIANCE CHECK AND
MAINTENANCE.
The following checks and maintenance should
be performed at least once a year.
- Check that the system's water PH is between
6.5 and 8.5.
- Visually check for water leaks or oxidation
from/on fittings and traces of condensate
residues inside the sealed chamber.
- Check contents of the condensate drain trap.
- Check that there are no residues of material
clogging the condensate passage; also check
that the entire condensate drainage circuit is
clear and efficient.
- Visually check that the water safety drain valve
is not clogged.
- Check that, after discharging system pressure
and bringing it to zero (read on boiler pressure
gauge), the expansion vessel pressure is at 1.0
bar.
- Check that the system static pressure (with
system cold and after refilling the system by
means of the filling valve) is between 1 and 1.2
bar.
- Visually check that the safety and control
devices have not been tampered with and/or
short-circuited.
- Check the condition and integrity of the electri-
cal system and in particular:
- supply voltage cables must be inside the
fairleads;
- there must be no traces of blackening or
burning.
- Check ignition and operation.
- Check correct calibration of the burner in
domestic hot water and central heating phases.
- Check the operation of the appliance control
and adjustment devices and in particular:
- system regulation probes intervention;
- the intervention of the DHW adjustment
thermostat
(when the boiler is connected to
an external storage tank unit)
.
- Check sealing efficiency of the gas circuit and
the internal system.
- Verify the intervention of the ionisation flame
control no gas device:
- Check the CO
2
by using the chimney sweep
function at the three reference heat outputs
and using the parameters in Fig. 3-14. Should
values out of the indicated tolerance range be
detected, check the integrity of the ignition /
detection electrode and, if required, change it,
also changing the relative gasket. At this point,
activate the “complete calibration” function.
- Carry out the flue test. Values below 40%
compared to the pressures detected upon first
check, suggest a clogged burner or module (flue
side).
Attention:
the burner does not need to be
opened for normal maintenance of the appli-
ance. However, should it be removed, you must
change the gasket.
IMPORTANT NOTE:
in addition to yearly
maintenance, you must also check the thermal
system and energy efficiency, with the frequency
and procedures that comply with the technical
regulations in force.
Summary of Contents for VICTRIX MAIOR 28 - 35 TT 1 ERP
Page 1: ...VICTRIX MAIOR 35 X TT 1 ERP IE Instruction and recommendation booklet 1 038660ENG...
Page 2: ......
Page 46: ...46...
Page 47: ...47...