1-1

INS

T

ALLER

US

ER

MAINTEN

AN

CE TECHNI

CI

AN

YES

NO

1

  BOILER  

INSTALLATION

1.1  INSTALLATION 

RECOMMENDATIONS.

The Victrix Maior 35 X TT 1 ErP boiler has been 
designed for wall mounted installation only, to 
heat and produce domestic hot water for domes-
tic use and similar purposes 

(when the boiler is 

connected to an external storage tank unit)

.

The  place  of  installation  of  the  appliance  and 
relative Immergas accessories must have suitable 
features (technical and structural) such to allow 
(always  in  safety,  efficiency  and  comfortable 
conditions):
-  installation (according to the provisions of the 

technical legislation and technical regulations);

-  maintenance operations (including scheduled, 

periodic, routine and special maintenance);

-  removal (to outdoors in the place for loading 

and  transporting  the  appliances  and  compo-
nents)  as  well  as  their  eventual  replacement 
with appliances and/or equivalent components.

The wall surface must be smooth, without any 
protrusions  or  recesses  enabling  access  to  the 
rear part. They are not designed to be installed 
on plinths or floors (Fig. 1-1).
By varying the type of installation the classifica-
tion of the boiler also varies, precisely:

Type  B

23

  or  B

53

  boiler  if  installed  using  the 

relevant terminal for air intake directly from 
the room in which the boiler has been installed.

Type  C  boiler

  if  installed  using  concentric 

pipes  or  other  types  of  pipes  envisioned  for 
sealed chamber boilers for air intake and expul-
sion of flue gas.

Note:

 appliance classification is provided in the 

depictions  of  the  various  installation  solutions 
shown on the following pages.

Only  professionally  enabled  companies  are 
authorised to install Immergas gas appliances.
Installation  must  be  carried  out  according  to 
regulation standards, current legislation and in 
compliance with local technical regulations and 
the required technical procedures.
Before installing the appliance, ensure that it is 
delivered in perfect condition; if in doubt, contact 
the supplier immediately. Packing materials (sta-
ples, nails, plastic bags, polystyrene foam, etc.) 
constitute a hazard and must be kept out of the 
reach of children. If the appliance is installed in-
side or between cabinets, ensure sufficient space 
for normal servicing; therefore it is advisable to 
leave clearance of at least 3 cm between the boiler 
casing and the vertical sides of the cabinet. Leave 
adequate space above the boiler for possible water 
and flue removal connections. Keep all flamma-
ble objects away from the appliance (paper, rags, 
plastic, polystyrene, etc.).

Do not place household appliances underneath 
the boiler as they could be damaged if the safety 
valve intervenes, if the drain trap is blocked, or 
if  there  are  leaks  from  the  hydraulic  connec-
tions;  otherwise,  the  manufacturer  cannot  be 
held responsible for any damage caused to the 
household appliances.
For the aforementioned reasons, we recommend 
not  placing  furnishings,  furniture,  etc.  under 
the boiler. 
In the event of malfunctions, faults or incorrect 
operation, turn the appliance off and contact an 
authorised company (e.g. the Authorised Tech-
nical  Assistance  centre,  which  has  specifically 
trained  staff  and  original  spare  parts).  Do  not 
attempt to modify or repair the appliance alone.
Failure to comply with the above implies personal 
responsibility and invalidates the warranty.

 Installation regulations: 

  -  this  boiler  can  be  installed  outdoors  in  a 

partially protected area. A partially protected 
area  is  one  in  which  the  appliance  is  not 
exposed to the direct action of the weather 
(rain, snow, hail, etc..).

   

This type of installation is only possible when 
permitted by the laws in force in the appliance's 
country of destination.

  -  Installation in places with a fire risk is pro-

hibited (for example: garages, closed parking 
stalls), gas appliances and relative flue ducts, 
flue exhaust pipes and combustion air intake 
pipes.

  -  Installation  is  prohibited  on  the  vertical 

projection of cooking hobs.

  -  Installation  is  also  prohibited  in  places/en-

vironments that constitute common parts of 
office condominiums such as stairs, cellars, 
entrance  halls,  attics,  lofts,  escape  routes, 
etc.  if  they  are  not  located  inside  technical 
compartments  under  the  responsibility  of 
each individual building and only accessible 
to the user (for the features of the technical 
compartments, see the technical standards in 
force).

Attention:

  wall  mounting  of  the  boiler  must 

guarantee  stable  and  efficient  support  for  the 
generator

The plugs (standard supply) are only to be used 
to fix the appliance to the wall;

 they only ensure 

adequate support if inserted correctly (according 
to technical standards) in walls made of solid or 
semi-hollow brick or block. In the case of walls 
made from hollow brick or block, partitions with 
limited  static  properties,  or  in  any  case  walls 
other than those indicated, a static test must be 
carried out to ensure adequate support.

These  boilers  are  used  to  heat  water  to  below 
boiling temperature in atmospheric pressure.
They  must  be  connected  to  a  central  heating 
system  and  hot  water  circuit  suited  to  their 
performance and capacity.

Attention: 

The  storage  tank  unit  must  also  be 

installed in an environment in which the tem-
perature cannot fall below 0°C.

Summary of Contents for VICTRIX MAIOR 28 - 35 TT 1 ERP

Page 1: ...VICTRIX MAIOR 35 X TT 1 ERP IE Instruction and recommendation booklet 1 038660ENG...

Page 2: ......

Page 3: ...ned by qualified professionals within the dimensional limits established by the Law Installation and maintenance must be performed in compliance with the regulations in force according to the manufact...

Page 4: ...2 General warnings 21 2 3 Control panel 21 2 4 Using the boiler 22 2 5 Troubleshooting 22 2 6 Information menu 25 2 7 Boiler shutdown 25 2 8 Restore central heating system pressure 25 2 9 System drain...

Page 5: ...ance paper rags plastic polystyrene etc Do not place household appliances underneath the boiler as they could be damaged if the safety valve intervenes if the drain trap is blocked or if there are lea...

Page 6: ...ary with respect to the minimum temperature at which the system must be kept An aqueous solution must be made with potential pollution class of water 2 EN 1717 2002 The materials used for the central...

Page 7: ...descaling products to remove any deposits that could compromise correct boiler operation A chemical treatment of the thermal system water is required in compliance with the tech nical standards in fo...

Page 8: ...hermostats are connected with 2 wires only Carefully read the user and assembly instructions contained in the acces sory kit On Off Immergas digital chrono thermostat The chrono thermostat allows set...

Page 9: ...s the max system flow temperature to be automatically decreased when the external temperature increases in order to adjust the heat supplied to the system according to the change in external temperatu...

Page 10: ...ds to the resistance encountered with the maximum allowed pipe length for each type of Terminal Kit This information allows calculations to be made to verify the possibility of setting up various flue...

Page 11: ...Intake and Exhaust 16 3 m 2 5 Intake m 18 7 Exhaust m 4 9 m 7 7 Exhaust m 13 6 Concentric vertical intake exhaust terminal 60 100 Intake and Exhaust 9 m 1 4 Intake m 10 3 Exhaust m 2 7 m 4 3 Exhaust m...

Page 12: ...side using the 2 previously removed screws Install the 80 outlet flange on the central hole of the boiler taking care to insert the gasket supplied with the kit and tighten by means of the screws prov...

Page 13: ...th the circular projections down wards in contact with the boiler flange and tighten using the screws present in the kit Fit the 60 100 3 concentric terminal pipe with the male side smooth to the fema...

Page 14: ...nge 2 up to the end stop making sure that the wall sealing plate has been fitted 3 this will ensure sealing and joining of the elements making up the kit NOTE when the boiler is installed in areas whe...

Page 15: ...the flat flange present in the lateral hole with respect to the central one ac cording to needs and replace it with the flange 3 positioningthegasket 2 alreadypresentin the boiler and tighten using t...

Page 16: ...ical data The dimensions of the shafts must ensure a minimum gap between the outer wall of the smoke duct and the inner wall of the shaft 30 mm for circular section shafts and 20 mm in the event of a...

Page 17: ...mber boilers must not be installed in places where commercial artisan or industrial activities take place which use products that may develop volatile vapours or substances e g acid vapours glues pain...

Page 18: ...of air bubbles in the water via the boiler and heating system vents The boiler has a built in automatic venting valve on the circulator Check if the cap is loose Open the radiator vent valves Close r...

Page 19: ...hut off valve kits with or without inspection filter on request The boiler is designed for installation of system interception cocks to be placed on flow and return pipes of the connection assembly Th...

Page 20: ...s mixer 7 Manual air vent valve 8 Delivery probe 9 Ignition detection electrode 10 Flue probe 11 Sample points air A flue gas F 12 Burner cover 13 Safety flow probe 14 Condensation module 15 Fan 16 Re...

Page 21: ...ler to direct vapours from a cooking surface Use of the boiler by unskilled persons or children is strictly prohibited For safety purposes check that the concentric air intake flue exhaust terminal if...

Page 22: ...he boiler selecting a value from 0 to 9 With external probe present the relative symbol 18 will appear on the display In the central heating phase if the temperature of the water contained in the syst...

Page 23: ...ner flame switches off unexpectedly a new attempt at ignition is performed and if normal conditions are restored the boiler does not have to be reset If normal conditions are restored the boiler resta...

Page 24: ...as valve has been detected The boiler does not start 1 88 Block gas valve control A malfunction of one of the components that controls the gas valve has been detected The boiler does not start 1 89 Co...

Page 25: ...ned frequently filling must be car ried out with suitably treated water to eliminate hardness that can cause lime scale 2 11 CASE CLEANING Use damp cloths and neutral detergent to clean the boiler cas...

Page 26: ...he intervention of the main switch lo cated upstream of the boiler and in the boiler check that the intake and or exhaust terminals are not blocked ensure activation of all adjustment devices check th...

Page 27: ...connector X5 is used for the connection to the relay board The connector X6 is for connection to a personal computer The connector X8 is used for software updating operations Key A19 Removable memory...

Page 28: ...values are within the set limits The factory set pressure values of the expansion vessel must be 1 0 bar the value of system pressure must be between 1 and 1 2 bar Noise due to air inside the condens...

Page 29: ...o clock position Fig 3 5 and press the Reset button for about 8 seconds until the chimney sweep function is activated then press the summer winter button within 3 seconds Nominalheatoutput with the f...

Page 30: ...ction is activated then press the info button within 3 seconds Once the function is active the boiler sequential ly carries out the procedures required to calibrate the appliance with the nominal inte...

Page 31: ...anomaly E62 will appear and complete calibration will be required Menu G This menu is reserved for the air gas control settings and it features two sub menus n and S relating to fan and gas valve con...

Page 32: ...Off 1 General alarm 2 CH phase active 3 External gas valve power supply 4 Secondary zone control from TA on relay P C B contact 5 Heat pump 6 Do not use on this boiler model 7 Do not use on this boile...

Page 33: ...f 0 3 On 5 C Off 0 C 2 t3 Not used on this boiler model t4 Not used on this boiler model t5 Central heating ignitions timer The boiler has electronic timing which prevents the burner from igniting too...

Page 34: ...so as to reduce the risk of the three way group becoming blocked due to prolonged inactivity 3 17 RADIATORS ANTI FREEZE FUNCTION If the system return water is below 4 C the boiler starts up until reac...

Page 35: ...ionandintegrityoftheelectri cal system and in particular supply voltage cables must be inside the fairleads there must be no traces of blackening or burning Check ignition and operation Check correct...

Page 36: ...o screws a 2 Press the hooks inwards which block the lower grid b 3 remove the grid b Front panel Fig 3 15b 4 Open the protection door e1 pulling it towards you 5 Remove the cover caps c and loosen sc...

Page 37: ...STALLER USER MAINTENANCE TECHNICIAN Ref X Control panel Fig 3 15d 9 Press the hooks on the side of the control panel i 10 Tilt the control panel i towards you Sides Fig 3 15e 11 Loosen screws k of sid...

Page 38: ...tput C 47 47 METHANE G20 PROPANE G31 THERMAL POWER THERMAL POWER MODULATION BURNER GAS FLOW RATE BURNER GAS FLOW RATE kW kcal h m3 h kg h 34 2 29412 99 3 70 2 71 33 5 28810 97 3 62 2 66 32 5 27950 94...

Page 39: ...30 Nom Min 106 0 107 6 Casing losses with burner On Off 80 60 C 0 35 0 10 Heat loss at flue with burner On Off 80 60 C 0 01 2 00 Central heating circuit max operating pressure bar 3 0 Maximum heating...

Page 40: ...N Serial Number CHK Check Cod PIN PIN code Type Type of installation ref CEN TR 1749 Qnw min Minimum DHW heat input Qn min CH minimum heat input Qnw max DHW maximum heat input Qn max CH maximum heat i...

Page 41: ...y 0 072 kW At partial load elmin 0 012 kW Ignition burner energy consumption Pign 0 000 kW In standby mode PSB 0 006 kW Emissions of nitrogen oxides NOX 23 mg kWh For mixed central heating appliances...

Page 42: ...I FLHQF RI ERLOHU 1 7HPSHUDWXUH FRQWURO URP FKH RI WHPSHUDWXUH FRQWURO 6XSSOHPHQWDU ERLOHU URP FKH RI ERLOHU 6XSSOHPHQWDU KHDW SXPS URP FKH RI KHDW SXPS 6RODU FRQWULEXWLRQ DQG 6XSSOHPHQWDU KHDW SXPS 6...

Page 43: ...PHQWDU KHDW SXPS LQVWDOOHG ZLWK ORZ WHPSHUDWXUH KHDW HPLWWHUV DW URP FKH RI KHDW SXPS 7KH HQHUJ HI FLHQF RI WKH SDFNDJH RI SURGXFWV SURYLGHG IDU LQ WKLV FKH PD QRW FRUUHVSRQG WR LWV DFWXDO HQHUJ HI FL...

Page 44: ...GHU DQG ZDUPHU FOLPDWH FRQGLWLRQV ROGHU DUPHU HFODUHG ORDG SUR OH 6RODU FRQWULEXWLRQ URP FKH RI VRODU GHYLFH 1 2 X LOLDU HOHFWULFLW 3 G F E D C B A A A A M L XL XXL 3 2 3 2 7KH HQHUJ HI FLHQF RI WKH S...

Page 45: ...DWLQJ HQHUJ HI FLHQF FODVV RI SDFNDJH XQGHU DYHUDJH FOLPDWH DWHU KHDWLQJ HQHUJ HI FLHQF XQGHU FROGHU DQG ZDUPHU FOLPDWH FRQGLWLRQV ROGHU DUPHU HFODUHG ORDG SUR OH 6RODU FRQWULEXWLRQ URP FKH RI VRODU G...

Page 46: ...46...

Page 47: ...47...

Page 48: ...mmergas com Immergas S p A 42041 Brescello RE Italy Tel 0522 689011 Fax 0522 680617 Certified company ISO 9001 This instruction booklet is made of ecological paper Cod 1 038660ENG rev ST 001863 000 06...

Reviews: