background image

16

1.22 GAS SYSTEM START-UP.

To start up the system, refer to the technical 

standard in force: This divides the systems and 

therefore the start-up operations into three 

categories: new systems, modified systems, 

re-activated systems.

In particular, for new gas systems:

-

 

open windows and doors;

- avoid presence of sparks or open flames;
- bleed all air from the pipelines;
-  check the seal of the internal system by follow-

ing the instructions provided by the technical 

regulations in force (refer to the pertaining lo-

cal regulations for the "sealing test" on systems 

served by single or cascade generators with a 

nominal thermal capacity greater than 35 kW.

1.23 BOILER START UP (IGNITION).

In order to issue the Declaration of Conformity 

required by the regulations in force, one must 

fulfil the following requirements to commission 

the boiler (the operations listed below must only 

be performed by qualified personnel and in the 

presence of staff only):

-  check that the internal system is properly sealed 

according to the specifications set forth by 

regulations in force; Up to operating pressures 

of 40 mbar it is also possible to use the testing 

method adopted by the technical regulations 

in force for systems served by single appliances 

(or in cascade set-up), with nominal thermal 

capacities greater than 35 kW. For greater pres-

sure levels you will need to refer to legislation 

in force and/or other effectively tried and tested 

methods;

-  make sure that the type of gas used corresponds 

to boiler settings;

- check that there are external factors that may 

cause the formation of fuel pockets;

-  switch the boiler on and check correct ignition;
-  make sure the fan rpm matches the value pro-

vided in the book (Par. 3.24);

- ensure that the safety device intervenes in the 

event of gas supply failure and check the relative 
intervention time;

- check activation of the main switch located 

upstream from the boiler and in the boiler;

- check that the intake/exhaust concentric ter-

minal (if fitted) is not blocked.

The boiler must not be started up even if only 

one of the checks should be negative.

1.18 FLUE DUCT SYSTEMS FOR VOIDS 

AND CHIMNEYS.

Flue ducts may be installed in suitable voids or 

chimneys provided that the relevant building 

regulations permit this.  Flue ducting systems 

must be installed in strict accordance with the 

manufacturers instructions.

Immergas ducting system Ø 80 .

 The "Green 

Series" 80 Ø flexible ducting system must only be 

used with Immergas condensing boilers.

In any case, ducting operations must respect 

the provisions contained in the standard and in 

current technical regulations; in particular, the 

declaration of conformity must be compiled at 

the end of work and on commissioning of the 

ducted system. The instructions in the project 

or technical report must likewise be followed, in 

cases provided for by the standard and current 

technical regulations. The system or components 

of the system have a technical life complying with 

current standards, provided that:

- it is used in average atmospheric and envi-

ronmental conditions, according to current 

regulations (in particular, by the standards 

regarding: absence of combustion products, 

dusts or gases that can alter the normal ther-

mophysical or chemical conditions; existence 

of temperatures coming within the standard 

range of daily variation, etc.).

- Installation and maintenance must be per-

formed according to the indications supplied 

by the manufacturer and in compliance with 

the provisions in force.

- The max. possible length of the 80 Ø flexible 

ducting vertical section 

is equal to 11.0 m for 

Victrix Pro 35 2ErP and 15.0 m for Victrix Pro 

55 2ErP

. This length is obtained considering 

the complete exhaust terminal, 1m of 80 Ø 

pipe in exhaust, two 90° 80 Ø bends at the 

boiler outlet to connect to the ducting system 

and two direction changes of the flexible tube 

inside the flue/technical slot.

1.19 

FLUE EXHAUST WITH BOILERS IN 

CASCADE.

The boilers installed in cascade composed of 

any number between 2 and 5 boilers, can be 

manifolded to a unique flue exhaust pipe, which 

flows into a flue.

Immergas supplied an appropriate and original 

flue exhaust system separately to the boilers.

1.20 SYSTEM FILLING.

When the boiler has been connected, fill the sys-

tem. Filling is performed at low speed to ensure 

release of air bubbles in the water via the boiler 

and heating system vents.

The boiler incorporates two automatic vent 

valves fitted on the circulator pump and on the 

condensing module. Check if the cap is loose. 

Open the radiator vent valves. Close radiator 

vent valves when only water escapes from them. 

N.B.:

 during these operations start up the cir-

culation pump at intervals, acting on the main 

switch positioned on the control panel.

Attention:

 this boiler is 

not

 equipped with an 

expansion vessel on the system. It is mandatory 

to install a closed expansion vessel to guarantee 

correct boiler operation. The expansion vessel 

must comply with the European Standards in 

force. The dimensions of the expansion vessel 

depend on the data relative to the central heating 

system. Install a vessel whose capacity responds 

to the requisites of the Standards in force (''R'' 

collection).

1.21 CONDENSATE TRAP FILLING.

On first lighting of the boiler combustion prod-

ucts may come out the condensate drain; after a 

few minutes’ operation check that this no longer 

occurs. This means that the trap is filled with 

condensate to the correct level preventing the 

passage of combustion products.

B23

1-23

Exhaust

Exhaust

Summary of Contents for VICTRIX PRO 35 2ErP

Page 1: ...IE Instruction and warning book VICTRIX PRO 35 55 2 ErP 1 041662ENG...

Page 2: ......

Page 3: ...in the regulations in force and principles of good practice In compliance with legislation in force the systems must be designed by qualified professionals within the dimensional limits established b...

Page 4: ...9 Restoring central heating system pressure 26 2 10 System drainage 26 2 11Anti freeze protection 26 2 12Case cleaning 26 2 13Decommissioning 26 3 Boiler commissioning initial check 27 3 1 Hydraulic...

Page 5: ...ts or fixing template to fix the appliance to the wall they only ensure adequate support if inserted correctly according to technical standards in walls made of solid or semi hollow brick or block In...

Page 6: ...temperature 5 C The boiler comes standard with an anti freeze function that ac tivates the pump and burner when the system water temperature in the boiler falls below 5 C The anti freeze function is...

Page 7: ...igned to operate with combustible gas free of impurities otherwise it is advisable to fit special filters upstream of the appliance to restore the purity of the fuel Storage tanks in case of supply fr...

Page 8: ...nce is reached only when it is correctly connected to an efficient earthing system as specified by current safety standards Attention Immergas S p A declines any respon sibility for damage or physical...

Page 9: ...s Thermoregulation electrical connection Fig 1 4 Thermoregulation electrical connections must be carried out on the boiler terminal board eliminating jumper X40 Thermostat or On Off environment chrono...

Page 10: ...pe C configuration sealed chamber and fan assisted The boiler leaves the factory with B23 configuration to change the configuration of the boiler to type C sealed chamber and fan assisted disassemble...

Page 11: ...mplete with vertical exhaust 80 Exhaust m 3 DUCT TYPE Equivalent length in m of concentric pipe 80 125 Concentric pipe 80 125 m 1 1 0 m Concentric bend 90 80 125 1 9 m Concentric bend 45 80 125 1 4 m...

Page 12: ...in order to ensure sufficient space to carry out the tests required by law upon commissioning External grid The intake exhaust terminal if properly installed is pleasant to look at on the outside of...

Page 13: ...ng the previously disassembled sheet steel plate 3 Installation of the fake aluminium tile replace the tiles with the aluminium sheet 5 shaping it to ensure that rainwater runs off Position the fixed...

Page 14: ...with this configuration can be extended up to a max measurement of 24 0 m with Victrix Pro 35 2ErP and 30 0 m with Victrix Pro 55 2ErP including the terminal Using the 80 vertical terminal for direct...

Page 15: ...has been fitted This will ensure sealing and joining of the elements making up the kit Horizontal kit 80 with exhaust in flue Kit assembly Fig 1 21 install the 80 bend 1 with the male side smooth full...

Page 16: ...compiled at the end of work and on commissioning of the ducted system The instructions in the project or technical report must likewise be followed in cases provided for by the standard and current te...

Page 17: ...pump always runs at maximum speed Pump release If after a prolonged period of inactivity the circulation pump is blocked unscrew the front cap and turn the motor shaft using a screwdriver Take great...

Page 18: ...ter 13 Ignition electrode 14 Air pressure switch 15 Flue probe 16 Condensing module air vent valve 17 Fumes hood 18 Sample points air A flue gas F 19 Heat exchanger safety thermal fuse 20 Manual air v...

Page 19: ...aker switches andofthethermometer notsuppliedasstandard with the boiler must be set up as described in the installation instructions in compliance with theprovisionsofthe R collection Wheneverthe gene...

Page 20: ...1 13 Zone 2 central heating circuit pump CMI 2 14 Zone 3 direct circuit pump CD 15 Storage tank unit feeding pump 16 Zone 1 safety thermostat CMI 1 17 Zone 2 safety thermostat CMI 2 19 Fuel shut off...

Page 21: ...anti freeze is not used b shut off all electrical water and gas supplies N B in the case of maintenance interventions on the boiler that lead to the closure of one or both system cut off cocks the boi...

Page 22: ...25 Summer mode 2 5 USING THE BOILER Before ignition make sure that the system is full of water checking that the manometer 5 indicates a base value at which the system has been designed and calculate...

Page 23: ...us setting 2 4 2 5 Stand by mode by pressing buttons A and C at the same time it is possible to place the boiler in stand by In this mode the boiler is considered powered on but not active Accordingly...

Page 24: ...ure detection incorrect in stand by With the boiler in stand by the board detects an anomalous difference between the NTC probe flow and return temperatures The error may be caused by a failure in one...

Page 25: ...probe 2 1 0E46 FlueNTCprobeoutside theoperatingrange The board detects an open contact on the flue NTC probe 2 1 0E81 Flow and return NTC probe temperature detection incorrect in stand by With the boi...

Page 26: ...frequently filling must be carried out with suitably treated water to eliminate hardness that can cause lime scale 2 12 CASE CLEANING Use damp cloths and neutral detergent to clean the boiler casing N...

Page 27: ...ll adjustment devices seal the gas flow rate regulation devices if settings are modified check sealing efficiency of water circuits check ventilation and or aeration of the instal lation room where pr...

Page 28: ...iler configuration jumper Y1 Gas valve Configure the corresponding parameters when connecting in simple cascade or when con necting in system side flow probe or D H W pump 1 External reset optional 2...

Page 29: ...ectronic board A4 Display board B1 Flow probe B1 2 System side flow probe optional B2 Domestic hot water probe optional B4 External temperature probe optional B5 Return probe B10 Flue probe B25 System...

Page 30: ...r probe NTC optional B4 External probe optional M2 Plant CH pump optional M30 3 way valve optional Note probe B1 2 B2 B4 Connection cable diameter 3 7 mm Cable section 0 5 1 5 mm2 1 External relay opt...

Page 31: ...at the radiator valves are not closed and also the functionality of the pump In addition check that the exchanger safety thermostat has not intervened If it has check the integrity of the module and c...

Page 32: ...io It defines the boiler s modulation ratio Do not modify 0 100 10 P13 Boiler power Used to calculate the boiler power in the event of simple cascade 0 255 kW 35 kW 35 55 kW 50 P14 External probe curv...

Page 33: ...nes the unit of measure on the display whether metric or Imperial 0 127 C kW 128 256 F kBTu h 0 P32 Set Resc Min Limits the minimum value of the heating set The parameter takes priority in relation to...

Page 34: ...tor To increase the CO2 value turn the adjustment screw 3 in a clockwise direction and vice versa to decrease it Calibration of maximum CO2 When you finish the minimum CO2 adjustment turn the boiler o...

Page 35: ...d to terminals S1 and S2 and parameter P38 must be set up whereas the pump must be connected to termi nals C and D If there is a DHW circuit it can be connected via an external 3 way to be connected t...

Page 36: ...every two years regardless of their state of wear Check that the burner is intact that it has no deformations or cuts and that it is properly fixed to the combustion chamber lid otherwise it must be r...

Page 37: ...the central hooks and then slide it downwards take the two clamping screws out 4 from the control panel with their rings 5 press the two side hooks 7 and tilt the control panel 6 remove the lower grid...

Page 38: ...38 3 15 1 6 8 9 9 12 12 10 11 13 13 13 13 A A Rif A 7 7 Ref A...

Page 39: ...690 2 38 4510 29 0 24940 3 13 4570 2 30 4380 28 5 24469 3 07 4500 2 26 4310 27 0 23220 2 92 4320 2 14 4120 26 0 22360 2 81 4200 2 06 4000 25 0 21500 2 71 4070 1 99 3870 24 0 20640 2 60 3950 1 91 3750...

Page 40: ...0 10 CO with 0 O2 at Nom Min Q Nom Min ppm 157 1 184 1 NOX at 0 of O2 at Q Nom Min mg kWh 43 17 43 21 Flue temperature at nominal output C 52 53 Flue temperature at minimum output C 48 48 METHANE G20...

Page 41: ...4 4 4 4 Central heating circuit max operating temperature C 90 90 Adjustable central heating temperature C 20 85 20 85 Head available with 1000 l h flow rate kPa m H2 O 60 1 6 13 60 1 6 13 Weight of f...

Page 42: ...N Serial Number CHK Check Cod PIN PIN code Type applianceconfiguration ref CENTR1749 Qnw min Minimum DHW heat input Qn min CH minimum heat input Qnw max DHW maximum heat input Qn max CH maximum heat i...

Page 43: ...ns 60 C on return and 80 C on flow Low temperature mode for condensation Boilers means 30 C for low temperature boilers 37 C and for other appliances 50 C of return temper ature Model s Victrix Pro 55...

Page 44: ...easonal room heating yield s 91 Domestic hot water production yield wh Parameter value Yearly energy consumption for the heating function QHE 86 7 GJ Yearly electricity consumption for the domestic ho...

Page 45: ...r Supplementary heat pump From fiche of heat pump Solar contribution and Supplementary heat pump Select smaller value Boiler and supplementary heat pump installed with low temperature heat emitters at...

Page 46: ...che of heat pump The energy efficiency of the package of products provided far in this fiche may not correspond to its actual energy efficiency once installed in a building as the efficiency is influe...

Page 47: ...contribution From fiche of solar device 1 I 2 1 1 x I 10 x II III I Auxiliary electricity 3 G F E D C B A A A A 27 27 27 28 27 27 27 28 30 30 30 32 33 34 35 36 36 37 38 40 39 50 55 60 65 75 80 85 100...

Page 48: ...gy efficiency under colder and warmer climate conditions Colder 0 2 x Warmer 0 4 x Declared load profile Solar contribution From fiche of solar device 1 ___ 2 1 1 x ___ 10 x ___ ____ ____ Auxiliary el...

Page 49: ...49...

Page 50: ...50...

Page 51: ...51...

Page 52: ...mmergas S p A 42041 Brescello RE Italy Tel 0522 689011 Fax 0522 680617 Certified company ISO 9001 This instruction booklet is made of ecological paper Cod 1 041662ENG rev ST 003517 000 12 18 Inglese p...

Reviews: