43
3.29 TECHNICAL PARAMETERS FOR MIXED BOILERS (IN COMPLIANCE WITH REGULATION 813/2013).
The yields in the following tables refer to the higher heating value.
Model/s:
Victrix Pro 35 2ErP
Condensing Boilers:
YES
Low temperature boiler:
NO
Boiler type B1:
NO
Co-generation appliance for central heating:
NO
Fitted with supplementary heating system:
NO
Mixed heating appliance:
NO
Element
Symbol
Value
Unit
Element
Symbol
Value
Unit
Nominal heat output
P
n
34
kW
Seasonal energy efficiency of central
heating
η
s
91
%
For central heating only and mixed boilers: useful heat output
For central heating only and mixed boilers: useful efficiency
At nominal heat output in high tempera-
ture mode (*)
P
4
34.0
kW
At nominal heat output in high tempera-
ture mode (*)
η
4
86.8
%
At 30% of nominal heat output in a low
temperature mode (**)
P
1
11.1
kW
At 30% of nominal heat output in a low
temperature mode (**)
η
1
95.6
%
Auxiliary electricity consumption
Other items
At full load
el
max
0.039
kW
Heat loss in standby
P
stby
0.091
kW
At partial load
el
min
0.015
kW
Ignition burner energy consumption
P
ign
0.000
kW
In standby mode
P
SB
0.004
kW
Emissions of nitrogen oxides
NO
X
23
mg /
kWh
For mixed central heating appliances
Stated load profile
Domestic hot water production efficiency
η
WH
%
Daily electrical power consumption
Q
elec
kWh
Daily gas consumption
Q
fuel
kWh
Contact information
IMMERGAS S.p.A. VIA CISA LIGURE, 95 - 42041 BRESCELLO (RE) ITALY
(*) High temperature mode means 60°C on return and 80°C on flow.
(**) Low temperature mode for condensation Boilers means 30°C , for low temperature boilers 37°C and for other appliances 50°C of return temper-
ature.
Model/s:
Victrix Pro 55 2ErP
Condensing Boilers:
YES
Low temperature boiler:
NO
Boiler type B1:
NO
Co-generation appliance for central heating:
NO
Fitted with supplementary heating system:
NO
Mixed heating appliance:
NO
Element
Symbol
Value
Unit
Element
Symbol
Value
Unit
Nominal heat output
P
n
50
kW
Seasonal energy efficiency of central
heating
η
s
91
%
For central heating only and mixed boilers: useful heat output
For central heating only and mixed boilers: useful efficiency
At nominal heat output in high tempera-
ture mode (*)
P
4
49.9
kW
At nominal heat output in high tempera-
ture mode (*)
η
4
87.7
%
At 30% of nominal heat output in a low
temperature mode (**)
P
1
16.4
kW
At 30% of nominal heat output in a low
temperature mode (**)
η
1
95.8
%
Auxiliary electricity consumption
Other items
At full load
el
max
0.044
kW
Heat loss in standby
P
stby
0.091
kW
At partial load
el
min
0.015
kW
Ignition burner energy consumption
P
ign
0.000
kW
In standby mode
P
SB
0.004
kW
Emissions of nitrogen oxides
NO
X
36
mg /
kWh
For mixed central heating appliances
Stated load profile
Domestic hot water production efficiency
η
WH
%
Daily electrical power consumption
Q
elec
kWh
Daily gas consumption
Q
fuel
kWh
Contact information
IMMERGAS S.p.A. VIA CISA LIGURE, 95 - 42041 BRESCELLO (RE) ITALY
(*) High temperature mode means 60°C on return and 80°C on flow.
(**) Low temperature mode for condensation Boilers means 30°C , for low temperature boilers 37°C and for other appliances 50°C of return temper-
ature.