background image

3.9  Air/gas ratio adjustment Victrix 20 boiler.

CO

2

 setting. Switch the boiler on and bring it to “chimney 

sweep”  phase,  ensuring  that  the  heating  power  trimmer 

(8 page 28) is at min. (turn it anticlockwise). To have an 

exact value of CO

2

 in the fumes the technician must insert the 

sampling probe all the way in the chamber, then check that 

the CO

2

 value is that specified in the table, otherwise adjust 

the CO

2

 by means of screw (3) (Off-Set regulator) bringing 

it to the value given in the table below. After making this 

adjustment bring the heating power trimmer (8 page 28) to 

max. and check maintaining of the CO

2

 parameter.

CO

2

 at rated

output

CO

2

 at min.

output

G 20

9.2% ± 0.2

9% ± 0.2

G 30

12.5% ± 0.2

11.9% ± 0.2

G 31

10.6% ± 0.2

9.7% ± 0.2

3.10  Air-gas ratio adjustment Victrix 27 boiler.

Min. CO

2

 setting.

Switch the boiler on and bring it to “chimney sweep” phase, 

ensuring that the heating power trimmer (8) is at min. (turn 

it fully anticlockwise). To have an exact value of CO

2

 in the 

fumes the technician must insert the sampling probe all the 

way in the chamber, then check that the CO

2

 value is that 

specified in the table, otherwise adjust the screw (3 page 28) 

(Off-Set regulator).
Max. CO

2

 setting.

After min. CO

2

 adjustment, switch the boiler on and bring 

it to “chimney sweep” phase, ensuring that the heating power 

trimmer (8) is at max. (turn it fully clockwise). To have an 

exact value of CO

2

 in the fumes the technician must insert 

the sampling probe all the way in the chamber, then check 

that the CO

2

 value is that specified in the table, otherwise 

adjust the screw (12 page 29) (gas flow regulator).

To increase the CO

2

 value turn the adjustment screw (12) 

anticlockwise or clockwise to decrease the value.

With every adjustment of screw 12 it is necessary to wait for 

the boiler to stabilize at the set value (approx. 30 sec.).

CO

2

 at rated

output

CO

2

 at min.

output

G 20

9.44% ± 0.2

8.90% ± 0.2

G 30

12.2% ± 0.2

11.5% ± 0.2

G 31

10.35% ± 0.2

10.0% ± 0.2

3.11  Combustion parameters check.

For  max.  and  min.  heat  output  adjustment  insert  the 

differential manometer between P1 and P2 (see fig. on 

page  23-24)  for  measuring  the  gas  pressure.  Bring  the 

boiler to “chimney sweep” phase, ensuring that the heating 

power  trimmer  is  at  max.  Adjust  the  max.  fan  speed 

trimmer (9 page 28) in order to obtain (with burner on) 

the value given in the table on page 32. In this way the 

max. heat output adjustment is made. Turn the trimmer 

clockwise  to  increase  pressure  and  anticlockwise  to 

decrease the pressure.

e min. setting occurs automatically.

3.12  Adjustment of boiler rated heating power.

e Victrix boiler is produced with heat output in heating set 

to max. erefore it is advisable not to change that setting. 

If the heating power has to be reduced, the trimmer (8 page 

28) must be adjusted. Turn the trimmer clockwise to increase 

pressure and anticlockwise to decrease the pressure.

3.13  Circulating pump operation.

By operating the jumper (4 page 28) two circulating pump 

operational modes can be selected in heating phase.

With  the  jumper  present,  circulating  pump  operation  is 

activated  by  the  room  thermostat  or  the  Remote  Friend 

Control; with the jumper not present the circulating pump 

always stays on.

3.14  “Chimney Sweep” function.

When activated, this function forces the boiler at max. heat-

ing power for 15 minutes.

In this mode all the adjustments are cut out and only the 

temperature safety thermostat and the limit thermostat re-

main active. To activate the “chimney sweep” function press 

the Reset key (7) (see page 19) for at least 10 seconds with 

the boiler on Stand-by; its activation is signalled by LEDs 

(1) and (4) flashing (see page 19). is function allows the 

technician to check the combustion parameters. After the 

checks deactivate the function, switching the boiler off and 

then on again.

3.15  Pump antiblocking function.

e boiler is equipped with a function that starts the pump 

at least once every 24 hours for the duration of 2.5 minutes 

during the “Summer” phase in order to reduce the risk of the 

pump becoming blocked due to prolonged inactivity.

26

INST

ALLER

USER

TECHNICIAN

27

INST

ALLER

USER

TECHNICIAN

Summary of Contents for VICTRIX ZEUS 20

Page 1: ...GB Instruction booklet and warning Installer User Technician VICTRIX 20 27...

Page 2: ...with the appliance It must be kept in a safe place and read carefully as it contains important information to ensure safe installation use and maintenance Installation and maintenance must be performe...

Page 3: ...ns 18 2 3 Control panel 19 2 4 Restoring heating system pressure 20 2 5 Draining the system 20 2 6 Anti freeze protection 20 2 7 Casing cleaning 20 2 8 Decommissioning 20 3 Boiler start up preliminary...

Page 4: ...quired procedures Before installing the appliance ensure that it is delivered in perfect condition if in doubt contact the supplier immediately Packing materials staples nails plastic bags polystyrene...

Page 5: ...manufacturer declines any responsibility in case of flood ing if the drain valve cuts in Important to preserve the life and efficiency of the domestic circuit exchanger it is advisable to install the...

Page 6: ...on In addition to the functions described in the previous point the Remote Friend Control enables the user to have under control and at hand all the important information regarding appliance and heati...

Page 7: ...set on the Remote Friend Control only if the boiler main switch is turned to Domestic Remote Friend Control Important If the Remote Friend Control is used arrange two separate lines in compliance with...

Page 8: ...tor of the single component does not depend on the type of boiler on which it is installed and is a dimen sional value It is based on the temperature of fluids passing through the ducts and therefore...

Page 9: ...ncentric horizontal intake exhaust 60 100 Intake and exhaust 9 1 4 m Intake and exhaust 5 2 0 8 m Equivalent length in metres of pipe 80 Terminal complete with concentric vertical intake exhaust 60 10...

Page 10: ...t length in metres of pipe 60 Equivalent length in metres of pipe 80 Complete vertical exhaust terminal 60 for ducting Intake 2 2 Exhaust 1 9 Intake 1 9 Exhaust 2 6 Intake 1 2 Exhaust 1 6 Exhaust 3 3...

Page 11: ...boiler inserting the seal 1 not requiring lubrica tion positioning it with the round protrusions downwards in contact with the boiler flange and tighten using the screws supplied with the kit Fit the...

Page 12: ...levant internal and external rings are fitted Fit the male end smooth of the exhaust pipe 9 up to the stop on the female end of the bend 5 making sure that the internal ring is fitted this will ensure...

Page 13: ...system Green Range 60 mm rigid and 80 flexible ducting systems can only be used for domestic use and with Immergas condensing boilers In any case ducting operations must respect the provisions contai...

Page 14: ...s be suitably designed to prevent the possible freezing of condensate inside the fume system and condensate dis charge system trap passivator tank comply with the current relevant national and local r...

Page 15: ...ollowing must be done for boiler start up check gas supply circuit tightness with the 0n Off valve closed and subsequently open with gas valve closed no gas flow must be read on the meter for 10 minut...

Page 16: ...pen adjustment screw fully unscrewed Head kPa A Flowrate l h B C Head m H 2 O Polyphosphate dispenser kit by request e polyphos phate dispenser prevents the formation of scale and preserves the origin...

Page 17: ...with seat for Venturi 13 Electronic control unit 14 Overtemperature safety thermostat 15 Circulating pump 16 Plate type heat exchanger 17 Pump safety pressure switch 18 3 bar safety valve 19 3 way val...

Page 18: ...Electronic control unit 14 Overtemperature safety thermostat 15 Circulating pump 16 Plate type heat exchanger 17 Pump safety pressure switch 18 3 bar safety valve 19 3 way valve monobloc 20 Adjustabl...

Page 19: ...ctrical water and gas supplies In case of work or maintenance to structures located in the vicinity of ducting or fume extraction devices and relevant accessories switch off the appliance and after co...

Page 20: ...iler on Stand by an illuminated horizon tal segment appears on the display In case of malfunction or anomaly the temperature is replaced by the relative error code flashing 1 Ignition block 2 Block du...

Page 21: ...an antifreeze function that starts the pump and the burner when the system water temperature inside the boiler falls below 4 C e anti freeze function is guaranteed if the boiler is fully operative and...

Page 22: ...Control or Room ermostat e boiler is arranged for application of a Room thermostat or the Remote Friend Control C A R Connect the Room ermostat to terminals 40 and 41 and remove jumper X20 e Remote Fr...

Page 23: ...el PTC S1 Main rotary switch S2 Pump flow switch microswitch S3 Domestic circuit priority microswitch T1 Voltage transformer TA Room thermostat On Off optional U1 Rectifier inside gas valve connector...

Page 24: ...stat 18 Automatic air valve 19 Igniters 20 Expansion tank 21 Air intake pipe 22 Circulating pump 23 Circulating pump pressure switch microswitch 24 One way valve 25 Circulating pump pressure switch 26...

Page 25: ...hood 19 Air analyzer chamber 20 p gas pressure point 21 Fume analyzer chamber 22 NTC limit and heating control sensor 23 Overtemperature safety thermostat 24 Automatic air valve 25 Igniters 26 Expansi...

Page 26: ...f CO2 in the fumes with boiler at min output with respect to the following table seal the gas flow regulation devices if the settings are modified after completing conversion apply the sticker include...

Page 27: ...11 Combustion parameters check For max and min heat output adjustment insert the differential manometer between P1 and P2 see fig on page 23 24 for measuring the gas pressure Bring the boiler to chimn...

Page 28: ...the system return water is below 4 C the boiler starts up and functions until reaching 42 C 3 17 System delivery temperature too high By operating the jumper 5 page 28 two delivery temperature ranges...

Page 29: ...mode jumper 5 Heating temperature preselection range 6 RS 232 computer interface VK 4115 V gas valve for Victrix 20 Electronic card 7 Output for fan rpm measurement 8 Max heating power adjustment trim...

Page 30: ...DUNGS gas valve for Victrix 27 Key 1 Gas valve inlet pressure point 2 Gas valve outlet pressure point 3 Off Set adjustment screw 12 Outlet gas flow regulator 29 INSTALLER USER TECHNICIAN...

Page 31: ...he screws 1 on the bottom of the casing front pull the bottom of the casing front outwards while at the same time pushing upwards see fig undo the screws 2 on the top of the casing front support sheet...

Page 32: ...k activation of the device against no gas ionization flame control ensure intervention time is less than ten seconds Visually check for water leaks or oxidation from on con nections and traces of cond...

Page 33: ...14 1 78 18 1 1 12 2 60 26 5 12 0 10320 1 32 1 69 17 3 0 98 1 30 13 3 0 97 1 90 19 4 10 0 8600 1 11 1 23 12 6 0 82 0 91 9 3 0 81 1 40 14 3 8 0 6880 0 89 0 84 8 6 0 67 0 60 6 1 0 66 0 90 9 2 6 0 5160 0...

Page 34: ...low limiter rated delivery min pressure Domestic circuit min pressure dynamic Domestic circuit max working pressure D specific delivery according to EN 625 Drawing capacity in continuous operation T 3...

Page 35: ...x working temperature heating circuit Adjustable heating temperature Pos 1 Adjustable heating temperature Pos 2 Total volume heating expansion tank Heating expansion tank precharge Generator water cap...

Page 36: ...www immergas com ISO 9001 Certified Company is instruction booklet is made of ecological paper Cod 1 021298 Rev 15 017635 000 04 04...

Reviews: