1.10 TABLES OF RESISTANCE FACTORS 

AND EQUIVALENT LENGTHS.

TYPE OF DUCT

Resistance

Factor

(R)

Equivalent length 

in m of concentric 

pipe Ø 80/125

Concentric pipe Ø 80/125 m 1

2.1

1

Concentric bend 90° Ø 80/125

3.0

1.4

Concentric bend 45° Ø 80/125

2.1

1

Terminal complete with concentric 

horizontal intake-exhaust Ø 80/125

2.8

1.3

Terminal complete with concentric 

vertical intake-exhaust Ø 80/125

3.6

1.7

Concentric bend 90° Ø 80/125 with 

inspection

3.4

1.6

Stub pipe with inspection Ø 80/125

3.4

1.6

1.9   IMMERGAS FLUE SYSTEMS.

Immergas supplies various solutions separately 

from the boilers regarding the installation of 

air intake terminals and flue exhaust, which are 

fundamental for boiler operation.

Attention: the boiler must be installed ex-

clusively with an original Immergas “Green 

Range” inspectionable air intake device and 

fumes extraction system made of plastic, as 

required by the regulations in force.
The plastic pipes cannot be installed outdoors, 

for tracts longer than 40 cm, without suitable 

protection from UV rays and other atmos-

pheric agents.
This system can be identified by an identifica-

tion mark and special distinctive marking 

bearing the note: “only for condensing boilers”.

•  Resistance factors and equivalent lengths. Each 

flue component has a 

Resistance Factor

 based 

on experimental tests and specified in the table 

below. The Resistance Factor for individual 

components is independent from the type of 

boiler on which it is installed and has a dimen-

sionless size. It is however, conditioned by the 

temperature of the fluids that pass through the 

pipe and therefore, varies according to applica-

tions for air intake or flue exhaust. Each single 

component has a resistance corresponding to 

a certain length in metres of pipe of the same 

diameter; the so-called 

equivalent length

can be obtained from the ratio between the 

relative Resistance Factors. 

All boilers have an 

experimentally obtainable maximum Resistance 

Factor equal to 100.

 The maximum Resistance 

Factor allowed corresponds to the resistance 

encountered with the maximum allowed pipe 

length for each type of Terminal Kit. This 

information allows calculations to be made to 

verify the possibility of setting up various flue 

configurations.

• 

Positioning the gaskets (black) for “green 

range” flue systems.

 Position the gasket cor-

rectly (for bends and extensions) (Fig. 1-8):

  - gasket (A) with notches, to use for bends;
  -  gasket (B) without notches, to use for exten-

sions;

 N.B.:

 if component lubrication (already car-

ried out by the manufacturer) is not sufficient, 

remove the residual lubricant using a dry cloth, 

then to ease fitting coat the parts with talc, sup-

plied in the kit.

• Coupling extension pipes and concentric 

elbows. To install push-fitting extensions with 

other elements of the flue, proceed as follows: 

Install the concentric pipe or elbow with the 

male side (smooth) on the female side (with lip 

seal) to the end stop on the previously installed 

element in order to ensure sealing efficiency of 

the coupling.

 

Attention:

 if the exhaust terminal and/or 

concentric extension pipe needs shortening, 

consider that the internal duct must always 

protrude by 5 mm with respect to the external 

duct.

• 

N.B.:

 for safety purposes, do not obstruct the 

boiler intake/exhaust terminal, even temporar-

ily.

• 

N.B.:

 when installing horizontal pipes, a mini-

mum inclination of 3% must be maintained and 

a section clip with pin must be installed every 

3 metres.

Summary of Contents for VICTRIX ZEUS SUPERIOR

Page 1: ...VICTRIX ZEUS SUPERIOR 26 2 32 2 ERP Instruction and recommendation booklet IE 1 037935ENG...

Page 2: ......

Page 3: ...ofessionals within the dimensional limits established by the Law Installation and maintenance must be performed in compliance with the regulations in force according to the manufacturer s instructions...

Page 4: ...e 20 2 2 General warnings 20 2 3 Control panel 20 2 4 Description of functioning states 21 2 5 Using the boiler 22 2 6 Troubleshooting 23 2 7 Parameters and information menu 25 2 8 Boiler shutdown 26...

Page 5: ...a draining funnel or if there are leaks from the hydraulic connections on the contrary the manufacturer cannot be held responsible for any damage caused to the household appliances For the aforementio...

Page 6: ...uid must be followed scrupulously regarding the percentage neces sary with respect to the minimum temperature at which the system must be kept An aqueous solution must be made with potential pollution...

Page 7: ...et the system requirements es tablished by the technical regulation in force in relation to the pollution of drinking water we recommend installing the IMMERGAS anti backflow kit to be used upstream o...

Page 8: ...t to On Off mode CAR V2 Super CAR or On Off chrono ther mostat electrical connection Optional The operations described below must be performed after having removed the voltage from the appli ance Any...

Page 9: ...efore varies according to applica tions for air intake or flue exhaust Each single component has a resistance corresponding to a certain length in metres of pipe of the same diameter the so called equ...

Page 10: ...Intake and Exhaust 16 3 m 2 5 Intake m 18 7 Exhaust m 4 9 m 7 7 Exhaust m 13 6 Concentric intake exhaust terminal 60 100 vertical Intake and Exhaust 9 m 1 4 Intake m 10 3 Exhaust m 2 7 m 4 3 Exhaust m...

Page 11: ...in the female end with lip seal of the 80 flange unit until it stops Introduce the gasket making it run along the bend Fix it using the sheet steel plate and tighten by means of the straps present in...

Page 12: ...with the boiler flange and tighten using the screws supplied with the kit Fit the 60 100 3 concentric terminal pipe with the male side smooth to the female side of the bend 2 up to the end stop makin...

Page 13: ...cal length of 14 4 m including the terminal This configuration corresponds to a resistance factor of 100 In this case specific extensions must be requested Vertical kit with aluminium tile 80 125 Kit...

Page 14: ...oth in the female side of the bend 5 up to the end stop ensuring that the internal and external wall sealing plates are fitted Fit the exhaust pipe 9 with the male side smooth to the female side of th...

Page 15: ...ical data The dimensions of the shafts must ensure a minimum gap between the outer wall of the smoke duct and the inner wall of the shaft 30 mm for circular section shafts and 20 mm in the event of a...

Page 16: ...he chimney technical slot The maximum possible length of the 80 rigid ducting vertical section is equal to 30 m This length is obtained considering the complete 80 exhaust terminal 1m of 80 pipe in ex...

Page 17: ...gas may come out the condensate drain after a few minutes operation check that this no longer occurs This means that the drain trap is filled with conden sate to the correct level preventing the passa...

Page 18: ...he system flow and return accord ing to set value K Fixed 100 65 in this mode the cir culator works at constant speed the operating range is defined between minimum 65 and maximum 83 for Victrix Zeus...

Page 19: ...e functioning possibilities Cover kit on request If installed outdoors in a partially protected place with direct air intake it is compulsory to mount the appropriate top protection cover for the corr...

Page 20: ...horised local firm 2 2 GENERAL WARNINGS Never expose the wall mounted boiler to direct vapours from cooking hobs Use of the boiler by unskilled persons or children is prohibited For safety purposes ch...

Page 21: ...uest for domestic hot water or central heating in order to evacuate residual flue gas F5 Postcirculation in progress Pump in function after a request for domestic hot water or central heating in order...

Page 22: ...ection it decreases During domestic hot water heating DHW ON appears on the display 24 on the status indicator 6 and at the same time as the burner ignites the flame presence indicator switches on 8 w...

Page 23: ...pressure is between 1 1 2 bar and restore the correct pressure if necessary 12 Storage tank probe anomaly The board detects an anomaly on the storage tank probe The boiler cannot produce domestic hot...

Page 24: ...flame signal This occurs when the boiler is ignited correctly and the burner flame switches off unexpectedly a new ignition attempt is performed and if normal conditions are restored the boiler does...

Page 25: ...els of the menu and the choice of parameters is confirmed Press button C to go back one level M1 information menu This menu contains the various information relative to boiler functioning 1st Level Bu...

Page 26: ...i freezeliquidandinstallation of the Immergas Anti freeze Kit in the boiler In the case of prolonged inactivity second case we also recommend that disconnect the electric power supply fully drain the...

Page 27: ...production of domestic hot water check sealing efficiency of water circuits check ventilation and or aeration of the instal lation room where provided If even only a single safety check offers a negat...

Page 28: ...ed by the drain trap being blocked Check by means of the condensate drain cap that there are no residues of material blocking the flow of condensate Noise due to air in the system Check open ing of th...

Page 29: ...casing mounted while the gas valve calibration operations must be carried out with the casing open and disconnecting the boiler from the power supply Calibration of the minimum CO2 minimum heating pow...

Page 30: ...on the domestic hot water probe on entry to the boiler P54 2 Displays the temperature read on the domestic hot water probe on exit from the boiler P54 3 Displays the temperature read on the return pr...

Page 31: ...in the cylinder falls by 3 C with respect to the temperature set Solar function deactivated P71 1 P71 2 5 C Boiler ignition for heating the domestic hot water occurs when the water contained in the cy...

Page 32: ...rts the pump at least once every 24 hours for the duration of 30 seconds in order to reduce the risk of the pump becoming blocked due to prolonged inactivity 3 11 THREE WAY ANTI BLOCK FUNCTION Both in...

Page 33: ...that it is properly fixed to the combustion chamber lid otherwise it must be replaced Visually check that the water safety drain valve is not clogged Check that after discharging system pressure and b...

Page 34: ...wer grid 1 by taking out the 4 fastening screws 2 Open the control panel door 3 remove the 2 white screw caps 4 and take out the 2 fasten ing screws 5 tilt the panel towards you Unscrew the 2 6 fasten...

Page 35: ...0 92 9 4 0 81 1 28 13 1 9 0 7740 1 00 0 73 7 4 0 75 0 77 7 9 0 73 1 09 11 1 8 0 6880 0 89 0 59 6 0 0 67 0 64 6 5 0 66 0 90 9 2 7 0 6020 0 78 0 46 4 7 0 59 0 52 5 3 0 58 0 73 7 5 6 0 5160 0 67 0 35 3...

Page 36: ...0 7 670 11 270 7 NOX at 0 of O2 at Q Nom Min mg kWh 39 22 108 50 43 30 Flue temperature at nominal output C 78 86 79 Flue temperature at minimum output C 73 82 75 Victrix Zeus Superior 32 2 ErP Gas no...

Page 37: ...h 25 8 22188 32 0 27520 Domestic hot water adjustable temperature C 10 60 10 60 Domestic hot water circuit flow limiter at 2 bar l min 8 7 12 6 Domestic hot water circuit min pressure dynamic bar 0 3...

Page 38: ...Cod Md Model code Sr N Serial Number CHK Check Cod PIN PIN code Type Type of installation ref CEN TR 1749 Qnw min Minimum DHW heat input Qn min CH minimum heat input Qnw max DHW maximum heat input Qn...

Page 39: ...ns 60 C on return and 80 C on flow Low temperature mode for condensation Boilers means 30 C for low temperature boilers 37 C and for other appliances 50 C of return tempera ture Model s Victrix Zeus S...

Page 40: ...mestic hot water function AFC 18 GJ Seasonal room heating yield s 92 Domestic hot water production yield wh 82 Parameter value Yearly energy consumption for the heating function QHE 61 2 GJ Yearly ele...

Page 41: ...ementary heat pump From fiche of heat pump Solar contribution and Supplementary heat pump Select smaller value Boiler and supplementary heat pump installed with low temperature heat emitters at 35 C F...

Page 42: ...35 C From fiche of heat pump The energy efficiency of the package of products provided far in this fiche may not correspond to its actual energy efficiency once installed in a building as the efficien...

Page 43: ...y electricity 3 G F E D C B A A A A 27 27 27 28 27 27 27 28 30 30 30 32 33 34 35 36 36 37 38 40 39 50 55 60 65 75 80 85 100 115 123 131 130 150 160 170 163 188 200 213 M L XL XXL 3 2 3 2 The energy ef...

Page 44: ...Water heating energy efficiency under colder and warmer climate conditions Colder 0 2 x Warmer 0 4 x Declared load profile Solar contribution From fiche of solar device 1 I 2 1 1 x I 10 x II III I Aux...

Page 45: ...45...

Page 46: ...46...

Page 47: ...47...

Page 48: ...mmergas com Immergas S p A 42041 Brescello RE Italy Tel 0522 689011 Fax 0522 680617 Certified company ISO 9001 This instruction booklet is made of ecological paper Cod 1 037935ENG rev ST 001312 001 09...

Reviews: