Page | 132
Figure 15.9
–
LAN1 Configuration Dialog
If
Get settings from
is set to
Configuration
for any parameter, the addresses in the
Default Settings
column will take place when this program is loaded and every time this controller enters RUN mode.
Registers may optionally be defined that will reflect the settings. These settings may temporarily be
changed via the SYSTEM menu but will revert to the I³ Config-configured settings at any transition into
RUN mode, i.e. a program download or at power-up.
If
Get settings from
is set to
Register
for any parameter, the addresses in the
Default Settings
column
are ignored entirely. The addresses instead must come from the configured registers. It is not possible
to change these settings via the SYSTEM menu in this case.