Page | 155
3.
User must confirm Load Clone as shown below:
Figure 17.8
–
Load Clone Confirm Screen
4.
After confirmation, all unit settings and register values will be loaded from the Removable media
to the Battery backed RAM (Regardless of AutoLoad settings) and then the
i
³ resets at which stage
the settings take effect.
NOTE
: For security-enabled files, Load Clone asks for password validation before loading the
application.
Load C
lone can also be triggered by setting %SR164.10 bit to “1” from Ladder program or graphics.
Once the operation is completed, this bit is made zero by the firmware. When the Load Clone
operation is triggered by this SR bit, it does not ask the user for confirmation to load the clone. The
success / failure of the operation is not notified on the screen to the user.
In case of failure of the “Load Clone” operation, %S
R164.12 bit is set to
“1” by the firmware and
never reset.