Page | 19
3.6
Factors Affecting Panel Layout Design and Clearances
The designer of a panel layout needs to assess the requirements of a particular system and to consider
the following design factors
.
3.7
Clearance / Adequate Space
Install devices to allow sufficient clearance to open and close the panel door.
Table 3.1
–
Minimum Clearance Requirements for Panel Box and Door
Minimum Distance
–
between base of device and
sides of cabinet.
2
”
(50.80mm)
Minimum Distance
–
between base of device and
wiring ducts.
1.5
”
(38.10mm)
Minimum Distance - between bases of each
device
if more than one device is installed in
panel box or on door.
4
”
between bases of each device
(101.60mm)
Minimum Distance
–
between device and closed
door
when door is closed
.
(Be sure to allow enough depth for the I³.)
2
”
(50.80mm)
3.8
Grounding
Panel Box: The panel box needs to be properly connected to earth ground to provide a good
common ground reference.
Panel Door: Tie a low impedance ground strap between the panel box and the panel door to
ensure that they have the same ground reference.
WARNING: It is important to follow the requirements of the panel manufacturer and to follow
all applicable electrical codes and standards.
WARNING: Be sure to meet the ground requirements of the panel manufacturer and meet
applicable electrical codes and standards.
Summary of Contents for i3C Lite
Page 1: ......
Page 8: ...Page 8 ...
Page 65: ...Page 65 Figure 9 3 Screen Calibration ...
Page 78: ...Page 78 Figure 11 2 Relay and Digital Output ...
Page 82: ...Page 82 Figure 11 5 Digital Input ...
Page 86: ...Page 86 11 9 RTD Wiring on J3 Connector ...
Page 110: ...Page 110 Figure 13 8 Alarm Configuration in i Config ...
Page 167: ...Page 167 ...