A1 action delayed timer setting 

• Sets action delayed timer for A1. 

  When setting time has passed after the input enters the alarm 

output range, the alarm is activated. 

• Not available if No alarm action is selected in A1 action selection 

• Setting range: 0 to 9999 seconds 

0 seconds 

 

A2 action delayed timer setting 

• Sets action delayed timer for A2. 

When setting time has passed after the input enters the alarm   

output range, the alarm is activated.   

• Not available if alarm A2 is not added or if No alarm action is 

  selected in A2 action selection   

• Setting range: 0 to 9999 seconds 

0 seconds 

 

Direct/ Reverse action selection 

• Selects Reverse (Heating) or Direct (Cooling) action. 

• Reverse (Heating): 

   Direct (Cooling): 

 

Reverse 
(Heating) action 

 

AT bias setting 

• Sets bias value during PID auto-tuning. 

• Not available for DC inputs 

• Setting range: 0 to 50 (0 to 100 ) or 0.0 to 50.0 (0.0 to100.0 ) 

20  

 

SVTC bias setting 

• Control desired value adds SVTC bias value to the value 

received by the SVTC command. 

• Available only when option C5 is added 

• Converted value of 

20% of the rated value or 

20% of the scaling range 

 

SV2 indication selection 

• Selects whether SV2 setting item is indicated or not. 

• Available only when the option SM is added.

 

• 

 (No indication)

 (Indication) 

No indication 

 

Output status selection when input burnout 

• Selects whether OUT1 is turned OFF or not when DC input is 

overscale or underscale.

 

• Available only for DC current output type with DC inputs 

• 

 (Output OFF)

 (Output ON) 

Output OFF 

 

OUT/OFF key function selection 

• Selects whether OUT/OFF key is used for control output 

  OUT/OFF function or for Auto/Manual control function.

 

• 

(OUT/OFF function) 

 (Auto/Manual control function) 

OUT/OFF 
function 

Sensor correction function 

This corrects the input value from the sensor. When a sensor cannot be set at a location where 

control is desired, the sensor measuring temperature may deviate from the temperature in the 

controlled location. When controlling with plural controllers, sometimes the temperatures measured 

(input value) do not concur with the same setting value due to difference in sensor accuracy or  

dispersion of load capacities. In such a case, the control can be set at the desired temperature by 

adjusting the input value of sensors. 

 

Energized/Deenergized 

When [alarm action energized] is selected, the alarm output (between terminals 3-4, or 3-5)  

is conducted (ON) while the alarm output indicator is lit. 

The alarm output is not conducted (OFF) while the alarm output indicator is not lit. 
When [alarm action deenergized] is selected, the alarm output (between terminals 3-4, or 3-5) is not 

conducted (OFF) while the alarm output indicator is lit. 

The alarm output is conducted (ON) while the alarm output indicator is not lit. 

 

               

High limit alarm (when Energized is set)          High limit alarm (when Deenergized is set) 

 

OFF

ON

A1 hysteresis

SV setting

+ A1 set point

OFF

ON

SV setting

+ A1 set point

A1 hysteresis

 

 

 

 
                                            (Fig. 5.5-1)                                                    (Fig. 5.5-2) 
 

11 

Summary of Contents for TP40A

Page 1: ...it might deform or tarnish the unit As the display section is vulnerable do not strike or scratch it with a hard object Any unauthorized transfer or copying of this document in part or in whole is pr...

Page 2: ...key the setting value or selected value can be registered 14 OUT OFF key The control output ON OFF function or Auto Manual control function can be switched To cancel the control output ON OFF function...

Page 3: ...unting Mount the controller vertically to fulfill the Dust proof Drip proof specification IP66 Mountable panel thickness Within 1 to 15mm Insert the controller from the front side of the panel Attach...

Page 4: ...uilt in power switch circuit breaker or fuse Therefore it is necessary to install them in the circuit near the external controller Recommended fuse Time lag fuse rated voltage 250V AC rated current 2A...

Page 5: ...he input range high limit value is indicated on the SV display for approximately 3 seconds Table 5 1 If any other value is set during the scaling high limit setting the set value is indicated on the S...

Page 6: ...OUT1 high limit setting A1 action delayed timer setting OUT1 proportional cycle setting Data transfer rate selection OUT1 low limit setting A2 action delayed timer setting OUT2 proportional cycle sett...

Page 7: ...Not available when OUT1 is ON OFF action Auto reset can be performed when PD action I 0 Setting range 0 to 1000 seconds 200 seconds Derivative time setting Sets derivative time for OUT1 Setting the va...

Page 8: ...ds on the designation When Lock 1 or Lock 2 is designated PID Auto tuning and Auto reset cannot be carried out Unlock Unlock All setting values can be changed Lock 1 None of the setting values can be...

Page 9: ...0 4 to 20mA 1999 to 9999 0 to 20mA 1999 to 9999 0 to 1V 1999 to 9999 0 to 5V 1999 to 9999 1 to 5V 1999 to 9999 0 to 10V 1999 to 9999 K 320 to 2500 199 9 to 750 0 J 320 to 1800 R 0 to 3200 S 0 to 3200...

Page 10: ...to 100 0 or 1 to 1000 0 OUT2 ON OFF action hysteresis setting Sets ON OFF action hysteresis for OUT2 Available only when the option DT is added Setting range 0 1 to 100 0 or 1 to 1000 1 0 A1 action se...

Page 11: ...is overscale or underscale Available only for DC current output type with DC inputs Output OFF Output ON Output OFF OUT OFF key function selection Selects whether OUT OFF key is used for control outp...

Page 12: ...of the unused instrument of the plural units OFF even if the power to the instrument is supplied is indicated on the PV display while the function is working Once the control output OFF function is en...

Page 13: ...dby High Low limit alarm with standby Low limit alarm with standby OFF ON A1 hysteresis OFF ON SV setting OFF ON A1 hysteresis OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON Alarm action Alarm action Alarm...

Page 14: ...or OFF unlit Represents Heating control action Represents Cooling control action 7 6 OUT2 Heating Cooling control action When setting Dead band Changes continuously according to deviation Non contact...

Page 15: ...the temperature rises When AT bias is set to 20 fluctuation is applied at the temperature 20 lower than the setting value 15 1 2 3 4 Temperature Setting value 1 Calculating PID constant 2 PID constant...

Page 16: ...reater Allowable input voltage 15V or less Allowable signal source resistance 100 or less OUT1 output Relay contact 1a Control capacity 3A 250V AC resistive load 1A 250V AC inductive load cos 0 4 Elec...

Page 17: ...370 to 1850 370 to 1850 0 to 1760 50 to 1810 50 to 1810 R S 0 to 3200 50 to 3250 50 to 3250 0 to 1820 50 to 1870 50 to 1870 B 0 to 3300 50 to 3350 50 to 3350 200 to 800 250 to 850 250 to 850 E 320 to...

Page 18: ...breaking status on the loop such as heater burnout sensor burnout or actuator trouble The output terminals will be common if the options W and A2 are applied together Setting range Loop break alarm ac...

Page 19: ...e the function is blinking on the PV display Thermocouple RTD or DC voltage 0 to 1V DC is burnt out Change each sensor How to check sensor burnout Thermocouple If the input terminal of the instrument...

Page 20: ...nterference or noise away from the controller The PV display is indicating Internal memory is defective Contact our agency or us 10 2 Key operation Problem Presumed cause and solution Unable to set th...

Reviews: