When OUT1 is non-contact voltage output or DC current output, between OUT1 and communication
and between OUT1 and SV2 are non-isolated and isolation test
must not
be carried out between them.
Isolation resistance
: 10M or greater at 500V DC
Dielectric strength
: 1.5kV AC for 1minute between input terminal and power terminal
1.5kV AC for 1minute between output terminal and power terminal
Supply voltage
: 100 to 240V AC 50/60Hz, 24V AC/DC 50/60Hz
Allowable voltage fluctuation
100 to 240V AC: 85 to 264V, AC 24V AC/DC: 20 to 28V AC/DC
Power consumption
: Approx. 8VA
Ambient temperature
: 0 to 50
(32 to 122 )
Ambient humidity
: 35 to 85%RH (no condensation)
]
Weight
: Approx. 200
g
External dimension
: 48 x 48 x 95mm (W x H x D)
Material
: Flame resistant resin (Case)
Color
: Light gray (Case)
Attached functions
:
[Setting value lock], [Sensor correction], [Auto/manual control switching],
[Input burnout indication
Thermocouple and RTD inputs
If the input value exceeds the Indication range high limit value, the PV display blinks “
”,
and if the input value exceeds the Indication range low limit value, the PV display blinks “
”.
If the input value exceeds the Control range, OUT1 and OUT2 are turned off (for DC current
.
)
output type, OUT1 low limit value and OUT2 low limit value)
(However, for manual control, it outputs the preset manipulated variable
Input Input
range
Indication range
Control range
–199.9 to 400.0
–199.9 to 450.0
–205.0 to 450.0
K T
–199.9 to 750.0
–199.9 to 850.0
–209.0 to 850.0
–200 to 1370
–250 to 1420
–250 to 1420
K
–320 to 2500
–370 to 2550
–370 to 2550
–200 to 1000
–250 to 1050
–250 to 1050
J
–320 to 1800
–370 to 1850
–370 to 1850
0 to 1760
–50 to 1810
–50 to 1810
R S
0 to 3200
–50 to 3250
–50 to 3250
0 to 1820
–50 to 1870
–50 to 1870
B
0 to 3300
–50 to 3350
–50 to 3350
–200 to 800
–250 to 850
–250 to 850
E
–320 to 1500
–370 to 1550
–370 to 1550
–200 to 1300
–250 to 1350
–250 to 1350
N
–320 to 2300
–370 to 2350
–370 to 2350
0 to 1390
–50 to 1440
–50 to 1440
PL-
0 to 2500
–50 to 2550
–50 to 2550
0 to 2315
–50 to 2365
–50 to 2365
C(W/Re5-26)
0 to 4200
–50 to 4250
–50 to 4250
–199.9 to 850.0
–199.9 to 900.0
–210.0 to 900.0
–200 to 850
–210 to 900
–210 to 900
–199.9 to 999.9
–199.9 to 999.9
–211.0 to 1099.9
Pt100
–300 to 1500
–318 to 1600
–318 to 1600
–199.9 to 500.0
–199.9 to 550.0
–206.0 to 550.0
–200 to 500
–206 to 550
–206 to 550
–199.9 to 900.0
–199.9 to 999.9
–211.0 to 999.9
JPt100
–300 to 900
–312 to 1000
–312 to 1000
DC current and voltage inputs
(4 to 20mA DC, 0 to 20mA DC, 0 to 1V DC, 0 to 5V DC, 1 to 5V DC, 0 to 10V DC)
If input value exceeds Indication range high limit value, PV display blinks “
”
, and if input
value exceeds the Indication low limit range, the PV display blinks “
”.
If input value exceeds the Control range, OUT1 and OUT2 are turned ON or OFF, depending on
which has been selected
in
the [Output status selection when input burnout] (for DC current output
type, OUT1 high or low limit value, OUT2 high or low limit value). However, for manual control, it
outputs the preset manipulated variable.
Indication range
: [Scaling low limit value – Scaling span x 1%] to [Scaling high limit value
+Scaling span x 10%]
(If the input value exceeds the range –1999 to 9999, the PV display blinks
“
” or “
”)
Control range
: [Scaling low limit value – Scaling span x 1%] to [Scaling high limit value
+Scaling span x 10%]
DC input burnout
: When DC input is burnt out, PV display blinks “
” for 4 to 20mA DC
and 1 to 5V DC inputs, and “
” for 0 to 1V DC input.
17