background image

The pressure switch is mounted on the back of the vertical
panel that separates the electrical components from the
pump/heater section of the unit. The pressure switch can be
adjusted by using the screws located on top of the pressure
switch. When looking at the front of the pressure switch, the left-
hand screw adjusts the differential and the 
right-hand screw adjusts the set point. The differential is factory
set for 10 PSI (.7 Bar) and should not need to be changed. The
set point can be adjusted by turning the right-hand screw until
the set point indicator points to the desired pressure. 

Pressure Relief Valve 

The pressure relief valve is a safety device designed to vent the
system if the operating pressure exceeds 150 PSI (10.5 Bar).
The pressure relief valve is located on one of the heater tubes.
The pressure in the process loop is the sum of the cooling water
supply pressure and the pressure added by the temperature
controller pump. It is possible that a high pressure cooling water
source and/or a low flow application will cause periodic 
pressure relief valve venting during normal operation. If you are
experiencing this, please contact our Tech Service Department
for assistance and have the serial number and model number of
the unit as shown on the nameplate located on the back 
of the unit.

Standard Options

The following options are the most common standard options
that we offer. In addition to the options shown we specialize in
offering unique options for our customers as are needed for
their particular application. If you are unable to find information
on an option of your unit please refer to the drawings that where
shipped with the unit or contact our Tech Service Department for
further information.

Stacking Bracket Kit (RA & RB series)

RA Series units can be stacked to minimize floor space require-
ments. A stacking bracket kit can be used to allow one unit to
be placed on top of another.

Mold Water Purge

The mold water purge option allows the mold circuit to be
purged of water by an external compressed air source. For ship-
ping purposes, the kit is shipped separately and will require field
installation. To perform a mold purge, follow the steps below in
sequence. 

1. Press the Stop button. This leaves the unit on but puts the

microprocessor in an inactive mode. The Power button light
should still be illuminated.

2. Close the valve on the Cooling Water In line to shut off the

supply of water. 

3. Connect the compressed air supply to the ¼" ball valve on

the back of the unit.

4. Open the ¼" ball valve to let the compressed air into the

mold circuit.

5. Press the Purge button on the control panel and hold it

down for 30 to 60 seconds or until the connecting water
lines stop shaking. When the water lines stop shaking you
can assume that the water has been purged.

6. Close the ¼" ball valve and disconnect the compressed air

line.

7. Close the valves on the Cooling Water Out, From Process

and To Process lines.

8. Open the pressure bleed line to pressurize the mold circuit.

After the pressure is relieved, disconnect the hoses from the
mold. The purge cycle is now complete. 

Crash Cool 

This option provides an additional solenoid valve piped in 
parallel to the vent/cooling solenoid valve. When activated, more
cooling water is allowed into the system providing quicker
process cooling. Enabling the Crash Cool switch located on the
left side of the control panel activates this function. The Crash
Cool solenoid valve will remain open as long as the Crash Cool
switch is enabled. 

Heat Exchanger (RA & RAD series)

The heat exchanger option uses a 4.0 ft² copper tube heat
exchanger to isolate the cooling water source from the process
water after the process is initially filled with water. The heat
exchanger is designed to fit within a heater tube. Due to space
restrictions in the cabinet, this option is only available on units
with 0 KW through 12 KW heating capacities. The process 
circuit is filled separately by bypassing cooling water into the
process circuit. The cooling supply line will be used for 
expansion during operation. This option also includes a 
separate vent solenoid valve. 

PREVENTIVE MAINTENANCE

Once the unit has been placed into service, the following 
maintenance procedures should be adhered to as closely as
possible. The importance of a properly established preventive
maintenance program cannot be overemphasized. Taking the
time to follow these simple procedures will result in substantially
reduced downtime, reduced repair costs, and an extended 
useful lifetime for the unit.

© Copyright 2010 IMS Company. All rights reserved.

An ISO 9001:2008 Registered Quality Company

14

Summary of Contents for Hydra Pressurized

Page 1: ...Company Hydra Pressurized Open Loop Mold Temperature Controllers INSTRUCTION MANUAL January 2007 IMS Company 10373 Stafford Road Chagrin Falls OH 44023 5296 Telephone 440 543 1615 Fax 440 543 1069 Email sales imscompany com Website www imscompany com Hydra is a trademark of IMS Company ...

Page 2: ... 8 Purge 8 Alarm Silence 8 Lower Set Point Temperature 8 Raise Set Point Temperature 8 Low Pressure 8 High Temp Safety 8 Pump Motor Overload 8 Over Set Point 9 Under Set Point 9 Pump On 9 Heat 9 Cool 9 Vent 9 Probe Fault 9 Changing Temperature Display Scale 9 Seal Saver 10 Auto Tune 10 Diagnostic Error Codes 11 Table 3 Diagnostic Error Codes 11 CONTROL OPTIONS 12 Return Water Temperature Display 1...

Page 3: ...r Modulating Valve 13 Pressure Switch 13 Pressure Relief Valve 14 STANDARD OPTIONS 14 Stacking Bracket Kit RA RB series 14 Mold Water Purge 14 Crash Cool 14 PREVENTIVE MAINTENANCE 14 Once a Week 15 Once a Month 15 TROUBLESHOOTING 16 CHARTS PUMP CURVES 17 Table 5 Single Zone Unit Electrical Specifications 17 Table 6 Dual Zone Unit Electrical Specifications 18 Figure 1 RA RAD RB RBD Series Pump Curv...

Page 4: ...ing Inspection Each unit is skid mounted and boxed or crated to protect it during shipping Before accepting delivery check the box or crate for visible damage If damage is evident it should be properly documented on the delivery receipt and the box or crate should be immediately removed to allow for detailed inspection of the unit Check for broken water lines damaged controls or any other major co...

Page 5: ...s well as quick disconnect fittings that offer high resistance to water flow When manifolds are required for water distribution they should be installed as close to the point of use as possible The return line should be the same size as the supply line In addition to the process water connections the unit requires a cooling water supply and return connection We recommend shut off valves at each ma...

Page 6: ...5 PSI 1 75 Bar and 50 PSI 3 5 Bar If the supply cooling water pressure is higher than 50 PSI 3 5 Bar a pressure regulating valve should be installed on the supply line to the temperature control unit For assistance in installing a pressure regulating valve please contact our Tech Service Department 6 Turn on the control power by pressing the Power button located on the control panel of the unit Th...

Page 7: ...ol Fault Logic Alarm Manual Remote Fault Alarm Pump Shut Heater Shut Unit Shut Reset Reset Alarm Indication Off Off Off Required 1 Required 2 Activated 3 Low Pressure LED Yes Yes Yes No No Yes High Temperature Safety LED Yes Yes Yes Yes No Yes Pump Motor Overload LED Yes Yes Yes Yes Yes Yes Over Set Point LED No No No No No Yes Under Set Point LED No No No No No Yes Probe Fault LED Yes Yes Yes Yes...

Page 8: ...epressing the Alarm Silence button will open the contact that was closed when the alarm occurred The contact will not close again until the alarm has been reset and a subsequent alarm has been triggered Lower Set Point Temperature Depressing and then releasing the Lower Set Point Temperature button will decrease the set point temperature by 1 F or 1 C If the Lower Set Point Temperature button is h...

Page 9: ...ted while the microprocessor is performing an Auto Vent sequence This sequence is performed each time the Start button is pressed to energize the unit unless the temperature is above 150 F The Auto Vent sequence opens the cooling solenoid or modulating valve for 30 seconds to vent air from the mold circuit Then the valve is kept open and the pump is energized for an additional 30 seconds The Vent ...

Page 10: ...re a particular application may require additional fine tuning of the control parameters To make this procedure as simple as possible this controller has been equipped with an Auto Tune function The Auto Tune function is designed to automatically select the best control parameters based upon the particular system that the unit is connected to At the factory certain parameters have been limited so ...

Page 11: ...tact Manufacturer for repair or replacement configuration change or invalid 111 Fixed parameter associated Controller requires servicing Contact Manufacturer for repair or replacement with range invalid 112 Setpoint out of temperature range Controller requires servicing Contact Manufacturer for repair or replacement 113 RAM hardware failure Controller requires servicing Contact Manufacturer for re...

Page 12: ...connect the controller and the unit All control functions are available to the operator at the location of the remote panel and no control functions are available at the location of the unit SPI Communications This option provides an RS 485 communication port located below the control panel on the front of the unit The serial communications will be multi drop half duplex SPI 3 01 compatible and wi...

Page 13: ...st not be defeated A small pump seal flush line is provided to continuously flush the pump seal of dirt and debris Construction Pump Assembly The centrifugal close coupled pump features a specially designed cast volute to eliminate fittings and provide easy connection to the heater and or mixing tubes The pump volute is constructed of cast iron The through 2 HP pumps have stainless steel impellers...

Page 14: ...ss the Stop button This leaves the unit on but puts the microprocessor in an inactive mode The Power button light should still be illuminated 2 Close the valve on the Cooling Water In line to shut off the supply of water 3 Connect the compressed air supply to the ball valve on the back of the unit 4 Open the ball valve to let the compressed air into the mold circuit 5 Press the Purge button on the...

Page 15: ...ay from the normal operating pressure 3 Check the pump for leaks in the seal area Replace pump seal if necessary Repeat items 1 through 3 listed above and continue with the following Once a Month 4 With the main disconnect shut off check the condition of electrical connections at all contactors starters and con trols Check for loose or frayed wires 5 Check the incoming voltage to make sure it is w...

Page 16: ...ctioning correctly and replace any defective components Microprocessor controller failure Replace controller Failure of thermocouple Replace thermocouple Failure of heater Replace heater Failure of heater contactor Replace heater contactor Unable to cool properly Cooling water supply is not Check to make sure the cooling water supply is of sufficient sufficient temperature volume and pressure for ...

Page 17: ...20 2 9 24 9 22 6 11 3 9 0 1 2 6 6 6 0 3 0 2 4 69 4 63 0 31 8 25 4 RA183A 2 9 24 9 22 6 11 3 9 0 1 3 9 9 9 0 4 5 3 6 72 7 66 0 33 3 26 6 RA183B 2 9 24 9 22 6 11 3 9 0 1 3 9 9 9 0 4 5 3 6 72 7 66 0 33 3 26 6 RA1850 2 9 24 9 22 6 11 3 9 0 1 5 16 5 15 0 7 5 6 0 79 3 72 0 36 3 29 0 RA1875 2 9 24 9 22 6 11 3 9 0 1 7 5 24 2 22 0 11 0 8 8 87 0 79 0 39 8 31 8 RA2408 2 9 24 9 22 6 11 3 9 0 1 0 75 3 7 3 4 1 ...

Page 18: ...1810 4 9 24 9 22 6 11 3 9 0 2 1 3 7 3 4 1 7 1 4 132 4 120 3 60 4 48 3 RAD1820 4 9 24 9 22 6 11 3 9 0 2 2 6 6 6 0 3 0 2 4 138 2 125 5 63 0 50 3 RAD183A 4 9 24 9 22 6 11 3 9 0 2 3 9 9 9 0 4 5 3 6 144 8 131 5 66 0 52 7 RAD183B 4 9 24 9 22 6 11 3 9 0 2 3 9 9 9 0 4 5 3 6 144 8 131 5 66 0 52 7 RAD1850 4 9 24 9 22 6 11 3 9 0 2 5 16 5 15 0 7 5 6 0 158 0 143 5 72 0 57 5 RAD1875 4 9 24 9 22 6 11 3 9 0 2 7 5...

Page 19: ...e prepared a custom set of drawings for your unit and placed them inside the control panel prior to shipment Please refer to these drawings when troubleshooting servicing and installing the unit If you cannot find these drawings or wish to have additional copies please contact our Tech Service Department and reference the serial number of your unit ...

Page 20: ... the equipment and or system has been subject to misuse negligence or operation in excess of recommended limits including freezing or which has been altered and or repaired without express factory authorization If equipment is installed in hostile environments unless such conditions were specified at the time of purchase or the serial number has been removed or defaced this warranty shall not appl...

Reviews: