Explosion proof DC version:  

 

 

The following connections can be made 

 

+ and -   

: DC Power connection 

1 and 2   

: Communication connection 

 

 

 

WARNING 

Swapping over the + and – may damage the light fitting.

 

 

WARNING 

Swapping over the 1 and 2 may damage the light fitting. 

 

 

WARNING 

Installing the 24V on the 1 and 2 will damage the light fitting. 

7.

 

Use  

 

7.1

 

Operation 

The light fitting can be switched on immediately after installation by switching on the supply voltage. . 

 

7.2

 

Insulation test 

Installations  in  which  IMT  ILED  Aquarius  Floodlight  light  fittings  are  installed  can  be  tested  by  means  of  an 

insulation test. For this test, apply a maximum of 500 Vdc between earth and (+ and

 

-). 

 

 
WARNING 

Never apply more than 500 VDC between a phase and a neutral wire.

 

All the light fittings are subjected to a dielectric test during manufacture (DC version: 700 Vdc for 60 seconds, 

AC version: 2100 Vdc for 60 seconds). In addition, the light fittings have also been subjected to an endurance 

test. 

 
 

 

 

Summary of Contents for ILED Aquarius

Page 1: ...ILED Aquarius Floodlight User Manual...

Page 2: ...scription 5 5 Specifications 6 5 1 General 6 5 2 Dimensions 6 6 Installation 7 6 1 Preparation 7 6 2 Assembly 7 6 3 Connections 8 7 Use 9 7 1 Operation 9 7 2 Insulation test 9 8 Maintenance 10 9 Recyc...

Page 3: ...fitting s housing Do not clean the light fitting using pressurized steam or a high pressure water jet to avoid damage not covered by the warranty 2 Warranty 2 1 General The warranty for the ILED Aquar...

Page 4: ...e It contains the following information 1 Type ILED FLOODLIGHT 2 Version HELIDECK TYPE X 3 Ambient Temp 40 C 55 C 4 Serial number 5 Year of manufacture 6 Voltage AC Version 95 250Vac DC Version 24Vdc...

Page 5: ...1 66A 8 Power Max 40W 9 Frequency AC Version 50 60 DC Version None 10 Marking Ex e mb IIC T4 Gb Ex tb IIIC T135 C Db IP66 4 Product Description All ILED Aquarius Floodlight light fittings are designed...

Page 6: ...glass Color White Mechanical protection IP66 Voltage DC version 24Vdc 10 Voltage AC version 95 255Vac 50 60Hz Burning position Universal Re ignition Instant Power factor 0 95 Connection Fitted as stan...

Page 7: ...box Take precautions to prevent corrosion to ensure the functionality of the earth connection Ensure that the cable gland is suitable for the dimensions of the type of cable that will be connected and...

Page 8: ...rsion The following connections can be made L and N Power connection Standard DC version The following connections can be made and DC Power connection WARNING Swapping over the and may damage the ligh...

Page 9: ...se 7 1 Operation The light fitting can be switched on immediately after installation by switching on the supply voltage 7 2 Insulation test Installations in which IMT ILED Aquarius Floodlight light fi...

Page 10: ...t fitting invalidates any warranty claim 9 Recycling For recycling the light fitting agreements have been made with local authorities within the context of the WEEE directive Contact your local partne...

Page 11: ...atmospheres ATEX114 2004 108 EC until April 19th 2016 Electromagnetic Compatibility 2014 30 EU from April 20th 2016 Electromagnetic Compatibility And that provisions have been made for all standards...

Page 12: ...IMT B V Pascalweg 10a 4104 BG Culemborg P O Box 88 4100 AB Culemborg Tel 31 0 88 12 69 100 Fax 31 0 88 12 69 101 www imt eu emea sales nl tidelandsignal com...

Reviews: