Technical data
Type
ASD 533-1
Supply voltage range
10.5 to 30 (
UL/FM = 12.4 to 27
)
VDC
Maximum power consumption,
in 12 VDC operation
in 24 VDC operation
Typical
measured at
10.5 VDC
18 VDC
24 VDC
ASD 533-1
Quiescent/fault
approx. 265
approx. 160
approx. 130
mA
Alarm
approx. 340
approx. 210
approx. 160
mA
additionally with 1 RIM 35 unit (all relays triggered)
approx. 15
approx. 10
approx. 7
mA
additionally with 2 RIM 35 units (all relays triggered)
approx. 30
approx. 20
approx. 14
mA
additionally with XLM 35 / SLM 35
approx. 20
approx. 10
approx. 5
mA
additionally with MCM 35
approx. 25
approx. 15
approx. 10
mA
Switch-on current peak
(caused by EMC protection elements on the ASD supply input)
approx. 5
A
for max. 1
ms
Sampling pipe length
see T 140 287, Sec. 4.2.1
Sampling pipe diam., typical (inner/outer)
Ø 20 / 25
mm
Max. number of sampling holes
see T 140 287, Sec. 4.2.1
Sampling hole diameter
Ø 2 / 2.5 / 3 / 3.5 / 4 / 4.5 / 5 / 5.5 / 6 / 6.5 / 7
mm
Response range (Sensitivity: Alarm 0,02 %/m – 10 %/m, pre-signals 0,002 %/m – 9 %/m)
EN 54-20, Class A, B, C
Protection type acc. to IEC 60529 / EN 60529
54
IP
Ambient conditions acc. to IEC 60721-3-3 / EN 60721-3-3
3K5 / 3Z1
class
Extended ambient conditions:
•
Detector housing temperature range
–20 – +60 (
UL max. +40
)
°C
•
Sampling pipe temperature range
–20 – +60
°C
•
Max. permissible temperature fluctuation in detector housing and sampling pipe operation
20
°C
•
Max. permissible storage temperature for detector housing (without condensation)
–20 – +70
°C
•
Ambient pressure difference between detector housing and sampling pipe (sampling holes)
must be identical
•
Humidity ambient condition for detector housing (transient without condensation)
95
% rel. hum.
•
Humidity ambient condition detector housing and sampling pipe (continuous)
70
% rel. hum.
Max. loading capacity, relay contact
50 (
UL max. 30
)
VDC
1
A
30
W
Max. loading capacity per OC output (dielectric strength 30 VDC)
100
mA
Plug-in terminals
2.5
mm²
Cable entry for cable Ø
Ø 5 – 12 (M20) / Ø 9 – 18 (M25)
mm
Sound pressure level
34 dB (A) / 1 m
Housing
material
ABS blend, UL 94-V0
colour
grey 280 70 05 / anthracite violet 300 20 05
RAL
Approvals
EN 54-20 / FM 3230-3250 / UL 268 7
th
Ed / ULC-S529 4
th
Ed
Dimensions (W x H x D)
265 x 397 x 148
mm
Weight
3,255
g
Power consumption at maximum permitted voltage drop in the electrical installation (guideline value for calculating the conductor
cross-section).
May cause the protective circuit to actuate immediately in the case of power supplies with overload protective circuits (primarily
in devices with no emergency power supply and output current of < 1.5 A).
Lower or higher temperature ranges are also possible subject to consultation with the manufacturer. The manufacturer must be
consulted if used in the condensation range.