Configuration options, Table A:

The criteria below can be set separately with the day/night control activated. Configuration changes are saved on 

X01

to 

X03

Sector

Parameter

Default

Setting

Area

Resolution /

Levels

Saving after

change

Alarm 2

Alarm 2 On / Off

Off

Off / On

X01

X03

Sensitivity (always at least 20% above alarm)

1%/m

– 10%/m

0.0002%/m

X01

X03

Alarm 2 delay

2 s

0 s – 60 s

1 s

X01

X03

Alarm 2 latching

On

On / Off

X01

X03

Hold time for area switchover (Al 2 to Al)

20

10 – 250

1 s

X01

X03

Alarm (EN 54-20)

Alarm threshold

C11

0.02 – 10%/m

0.0002%/m

X01

X03

Smoke level value averaging (number)

4

1 – 10

1

X01

X03

Alarm delay (

UL/ULC max. 30 s

)

2 s

0 s – 60 s

1 s

X01

X03

Alarm cascading

Off

Off / On

X01

X03

Alarm latching

On

On / Off

X01

X03

Pre-signal

Pre-signal 1 On / Off

On

On / Off

X01

X03

Pre-signal 2 On / Off

On

On / Off

X01

X03

Pre-signal 3 On / Off

On

On / Off

X01

X03

Pre-signal 1 (100% = alarm threshold)

30%

10 – 90%

10%

X01

X03

Pre-signal 2 (100% = alarm threshold)

50%

VS

1 + 10 – 90%

10%

X01

X03

Pre-signal 3 (100% = alarm threshold)

70%

VS

2 + 10 – 90%

10%

X01

X03

Pre-signal delay (VS 1 – VS 3)

2 s

0 s – 60 s

1 s

X01

X03

Pre-signal latching

Off

Off / On

X01

X03

Smoke sensor dust/soiling

Smoke sensor dust On / Off

On

On / Off

X01

X03

Smoke sensor soiling On / Off

On

On / Off

X01

X03

Dust threshold (% of Al)

50%

5 – 60%

5%

X01

X03

Soiling threshold (% of Al)

75%

65 – 100%

5%

X01

X03

Dust latching

On

On / Off

X01

X03

Soiling latching

On

On / Off

X01

X03

Smoke sensor fault delay

30 s

0 s – 60 s

1 s

X01

X03

Airflow monitoring

LS-Ü pipe blockage On / Off

On

On / Off

X01

X03

LS-Ü pipe breakage On / Off

On

On / Off

X01

X03

LS-Ü sensitivity (applies to 

A01

to 

C31

)

±20%  

±1 – ±70%

± 1%

X01

X03

LS-Ü value averaging (number)

20

1 – 30

1

X01

X03

LS-Ü delay (applies to 

A01

to 

C31

)

300 s  

10 s – 3600 s

1 s

X01

X03

Stored under switch positions 

W01

to 

W44

are increased values which are 

not

tested for EN compliance (see Technical descrip-

tion, T 140 287, Sec. 4.4.4.4).

Configuration options, Table B:

The following criteria apply to the entire ASD 533. Configuration changes are stored in connection with the adjustments from Table A, likewise 

on one of the user configurable switch positions 

X01

to 

X03

Sector

Parameter

Default

Setting

Area

Resolution /

Levels

Saving after

change

Autolearning

Autolearning On / Off

Off

On

X01

X03

Autolearning duration

3 days

1 min to 14 days

min, h, days

X01

X03

Autolearning factor (of measured Al threshold)

1.5

1.1 – 10 x

X01

X03

Day/night control / weekday control

Day/night control On / Off

Off

Off / clock / FACP /

input “

OEM1

/

St

X01

 – 

X03

Day start time (only with “Clock”)

06:00

00:00 – 24:00

1 min

X01

X03

Night start time (only with “Clock”)

20:00

00:00 – 24:00

1 min

X01

X03

Weekday control (only with “Clock”)

On

Mon to Sun

Days

X01

X03

General faults

Lithium battery / clock fault

On

On / Off

X01

X03

Deactivate / switch off sensor

Smoke sensor I

On

On / deactivated

X01

X03

Summary of Contents for ASD 533

Page 1: ... 35 Memory Card Module The ASD 533 can be connected to a higher level FACP via poten tial free change over contacts Fitting an XLM 35 or SLM 35 means that the ASD 533 can be ide ally connected to the SecuriFire and Integral fire alarm systems via the addressable loop with SLM also to the SecuriPro The RIM 35 is available as a further installation option This mod ule enables the availability of all...

Page 2: ...allation of the ASD release the two lock clamps however it should be left inside its protective packaging until the definitive commissioning The definitive installation is carried out as de scribed below see Fig 3 Always leave the smoke sensor inside its protective packaging until it is ready to be installed definitively in the detector housing Depending on the circumstances e g long period of tim...

Page 3: ...manently assigned parameters Normative system limits according to EN 54 20 Class A to C positions A11 to C31 Non normative system limits positions W01 to W44 Configurable positions for settings after using ASD PipeFlow and or ASD Config or SecuriPro SecuriFire or Integral FACP SLM 35 XLM 35 X01 to X03 The parameters are saved at the factory with values for compliance with EN 54 20 Changing the par...

Page 4: ...ior consultation with the manufacturer The airflow monitoring values stored under those switch positions are not tested in accordance with EN For more information on using the table of system limits please refer to the Technical description T 140 287 Sec 4 4 4 3 and 4 4 4 4 Table of system limits for planning without ASD PipeFlow calculation Compliant with EN 54 20 Class A highly sensitive Shape S...

Page 5: ... 5 3 0 7 0 11 2 0 2 0 2 0 2 0 2 5 2 5 2 5 2 5 2 5 4 0 7 0 12 2 0 2 0 2 0 2 0 2 0 2 0 2 5 2 5 2 5 2 5 4 0 7 0 U T shaped sampling pipes Number of sam pling holes per sampling branch Hole diameter in mm for the sampling hole number as of ASD 1 2 3 4 5 6 7 8 1 5 0 2 4 0 5 0 3 4 0 4 0 5 0 4 4 0 4 0 4 0 5 0 5 4 0 4 0 4 5 5 0 6 5 6 3 0 3 0 3 5 3 5 4 0 6 5 7 2 5 3 0 3 0 3 5 3 5 4 0 6 5 8 2 5 2 5 3 0 3 0 ...

Page 6: ... 5 60 5 X01 X03 Soiling threshold of Al 75 65 100 5 X01 X03 Dust latching On On Off X01 X03 Soiling latching On On Off X01 X03 Smoke sensor fault delay 30 s 0 s 60 s 1 s X01 X03 Airflow monitoring LS Ü pipe blockage On Off On On Off X01 X03 LS Ü pipe breakage On Off On On Off X01 X03 LS Ü sensitivity applies to A01 to C31 20 1 70 1 X01 X03 LS Ü value averaging number 20 1 30 1 X01 X03 LS Ü delay a...

Page 7: ...al 1 s 1 120 s MCM smoke peak value memory Off Off On Carry out new initial reset On Off Smoke sensor mode of operation smoke sensor I SSD DMB SSD DMB or OEM inputs individual or in combination Switched off Isolate smoke sensor smoke sensor I Normal operation Isolate normal operation Filter monitoring smoke sensor I Off Off On Filter service life 6 months 1 24 months Read out operation time months...

Page 8: ... b21 Displays the new set ting Initial reset Measure Display Procedure remarks Before carrying out an initial reset i e after switching on the ASD 533 make sure you observe a waiting time of at least 5 min 1 Press the UP key flashing C31 or others Displays the default setting or the installa tion specific switch position 2 Press the UP key several times until dis play shows U in succession A to U ...

Page 9: ...200006 01 XX SecuriLine eXtended line module XLM 35 11 2200003 01 XX SecuriLine module SLM 35 4000286 0101 Relay interface module RIM 35 4000287 0101 Memory card module MCM 35 4000285 0101 SD memory card industrial version 11 4000007 01 XX USB cable 4 5 m 4301248 Main board AMB 33 1 11 2200004 01 XX BCB 35 without smoke level indicator 4301220 0101 Aspirating fan unit AFU 35 complete 4000299 Airfl...

Page 10: ... C Sampling pipe temperature range 20 60 C Max permissible temperature fluctuation in detector housing and sampling pipe operation 20 C Max permissible storage temperature for detector housing without condensation 20 70 C Ambient pressure difference between detector housing and sampling pipe sampling holes must be identical Humidity ambient condition for detector housing transient without condensa...

Reviews: