background image

EK-WL8-HS/AU 

WIRELESS HEAT DETECTOR 

WITH BUILD-IN SOUNDER 

STFV.425238.038-AU-UM rev. 18

 

20.08.2020 

Page 

8

 from 

8

 

Summary of Contents for ekho EK-WL8-HS/AU

Page 1: ...ture exceeds a threshold value or starts rising at a certain speed The signal travels through repeaters to the translator module which then informs the main control about the emergency The thermal sensor is A1R type The device is supplied with a mounting kit The product complies with the requirements of the AS ISO 7240 5 and AS ISO 7240 25 standards FEATURES Bi directional wireless communication I...

Page 2: ...g frequency channels 6 Radiated power Not more than 25 mW Receiver category EN300 220 1 1 5 Sound pressure level at 1 m 96 dB A for all modes Battery life Primary battery type CR123A 2 75 3 2V 8 10 years Secondary battery type CR123A 2 75 3 2V 3 months after primary battery low fault Dimensions with the base 111 mm x 76 mm Weight 200 g IP rating IP21С Max tolerated humidity 95 RH Operating tempera...

Page 3: ...crew the device into it Preferably the device should be installed at a certain distance from metallic objects doors and power lines as they can cause the communication distance to drop It is also important to avoid installing the device near electronics and computer equipment in order to protect it from potential electromagnetic interference INDICATION The device has an LED which indicates its sta...

Page 4: ...ftware By analyzing the voltage levels you can manage your maintenance procedures and predict when you will have to replace the batteries Please refer to the software manual for full instructions on how to use the program for system maintenance SOUNDER The EK WL8 OS sounder may generate two tones Tone Mode Frequency Tone1 3500 Hz Tone2 2150 Hz Device has six sound alert modes You can choose mode b...

Page 5: ... is advisable to replace them to reduce the risk of reduced performance caused by external factors Ensure the devices are only used with compatible control panels Detection systems must be checked serviced and maintained on a regular basis to confirm correct operation Refer to and follow National Codes of Practice and other internationally recognized fire engineering standards Appropriate Risk Ass...

Page 6: ... similar characteristics The batteries must meet the following standards UL 1642 lithium batteries UL certified at www ul com or IEC 60086 4 Primary batteries Part 4 Safety of lithium batteries The remaining shelf time of the new batteries must be not less than 8 years Failure to observe these instructions will void the device warranty and any liabilities CAUTION Replacement of a battery with an i...

Page 7: ...ECTOR WITH BUILD IN SOUNDER STFV 425238 038 AU UM rev 18 20 08 2020 Page 7 from 8 Angle Minimal sound pressure level dB A for all supply voltages at 1 m Horizontal and vertical plane 15 88 4 45 94 2 75 97 6 105 97 9 135 94 3 165 85 ...

Page 8: ...EK WL8 HS AU WIRELESS HEAT DETECTOR WITH BUILD IN SOUNDER STFV 425238 038 AU UM rev 18 20 08 2020 Page 8 from 8 ...