Incite Hochiki-Securiton Interface Module– Rev 1.0 

Page 13 of 21 

 

5.4.2

 

Syncro Cause and Effect Programming 

 

Note:  In this example an ASD535 with dual sampling tubes are used 

Function 

Type 

Cause 

Operator  Effect 

 

Comment 

Fault 1 and 2 

Action 

CHQ-POM Input 

OR 

SECRDU Channels 

4 and 6 

The ASD 535-2 has 

only one fault 

output for both 

sensors. 

Fire 1 

Action 

CHQ-POM Input 

OR 

SECRDU Channel 3   

Fire 2 

Action 

CHQ-SIM Input 

OR 

SECRDU Channel 5   

ASD535.1 

Reset 

Action 

SECRDU 

Channel 11 

OR 

CHQ-POM Output   

ASD535.2 

Reset 

Action 

SECRDU 

Channel 15 

OR 

CHQ-POM Output  The ASD 535-2 has 

only one reset 

input output for 

both sensors. 

ASD535.1 

Disablement 

Disablement  SECRDU 

Channel 9 

OR 

CHQ-POM Input 1   

ASD535.2 

Disablement 

Disablement  SECRDU 

Channel 13 

OR 

CHQ-SIM Input 

 

ASD535.1 and 

2 Disablement 

Disablement  SECRDU 

Channel 9 and 

13 

AND 

CHQ-POM Input 2  We have a common 

fault, so only 

disable it when 

both are disabled 

ASD535.1 and 

2 Total 

Disablement 

Action 

SECRDU 

Channel 10 and 

14 

AND 

CHQ-POM Output  This used the aux 

disablement 

outputs to turn off 

the ASD. 

 

 

 

Summary of Contents for SEC-HIM-35

Page 1: ...Incite Hochiki Securiton Interface Module Rev 1 0 Page 1 of 21 ...

Page 2: ...SYNCRO SECRDU and TAKTIS SECRDU 6 4 2 1 Unit addresses 6 4 2 2 Config Switch 6 5 FIP Configuration 7 5 1 General 7 5 2 SEC HIM 35 8 5 3 SEC HIM 35B 10 5 4 SYNCRO SECRDU 11 5 4 1 I O Setup and Attributes 11 5 4 2 Syncro Cause and Effect Programming 13 5 5 TAKTIS SECRDU Error Bookmark not defined 5 5 1 I O Setup and Attributes 14 5 5 2 Taktis Cause and Effect Programming 16 6 Installation 17 6 1 SEC...

Page 3: ... These modules are used to display the status of the ASDs and allow individual Disable and Reset switches for each ASD 2 Modules 2 1 SEC HIM 35 The Hochiki Securiton Interface Module consists of two parts connected via a ribbon cable These are available only as a complete set The control PCB consists of a CHQ POM and associated electronics to allow it to interface to the Securiton ASD 531 ASD 532 ...

Page 4: ... individual Securiton ASD units They must be configured through Cause and Effects in the Syncro or Taktis panels They must be used in conjunction with either a Syncro or Taktis panel and are not available in a stand alone configuration These modules come only as pairs Should only one be needed the second unit is left out of the FIP configuration ...

Page 5: ...located on the SEC HIM 35B module 3 2 Fault Mode All the inputs on the SEC HIM 35 and SEC HIM 35B are monitored for open circuit and short circuit faults Should any portion of the unit be unplugged a fault will be generated When the fault contact on the ASD is activated the second input on the CHQ POM is activated This allows the input to signal a fault and also trigger other devices through C E i...

Page 6: ...n the SECRDU are capsense type They are activated by placing a finger onto the faceplate where the finger capacitance is detected by the PCB circuitry The sensitivity can be fine tuned by switches 1 to 4 on the configuration switch SW3 It should not be necessary to move the switches from their default setting Settings are only read on a board reset To perform a reset momentarily press SW1 which is...

Page 7: ...apacitance makes the button MORE sensitive Care must be taken not to make the button too sensitive or false triggering may occur similarly if the sensitivity is reduced too far the button will not work at all 5 FIP Configuration 5 1 General The SEC HIM 35 is presented to the FIP as a CHQ POM device while the SEC HIM 35B is presented to the FIP as a CHQ SIM Both the SYNCRO SECRDU and the TAKTIS SEC...

Page 8: ...Incite Hochiki Securiton Interface Module Rev 1 0 Page 8 of 21 5 2 SEC HIM 35 The SEC HIM 35 should be configured as CHQ POM Output CHQ POM Input 1 ...

Page 9: ...Page 9 of 21 CHQ POM Input 2 Note When Input 1 is set to Latching a 10 second delay must be placed on the input in order for it to reset with a Panel Reset Failure to do so will result in the point re alarming and a second reset needing to be performed ...

Page 10: ...HIM 35B The SEC HIM 35B should be configured as Note When the Input is set to Latching a 10 second delay must be placed on the input in order for it to reset with a Panel Reset Failure to do so will result in the point re alarming and a second reset needing to be performed ...

Page 11: ...ctive Used to disable inputs via C E 10 Disablement 1 2 Input May be used as required Is activated whenever the Disablement function on ASD1 is active 11 Reset 1 1 Input Activated for 5 seconds whenever the Reset function on ASD1 is activated Used to reset the ASD via C E 12 Reset 1 2 Input May be used as required Is Activated for 5 seconds whenever the Reset function on ASD1 is activated 13 Disab...

Page 12: ...ce Module Rev 1 0 Page 12 of 21 I O points and channel attributes should be set as shown All outputs should have attributes CLEARED Input 9 and 13 should be set to DISABLEMENT all other inputs should be set to TRANSPARENT NON LATCHING ...

Page 13: ...CRDU Channel 5 ASD535 1 Reset Action SECRDU Channel 11 OR CHQ POM Output ASD535 2 Reset Action SECRDU Channel 15 OR CHQ POM Output The ASD 535 2 has only one reset input output for both sensors ASD535 1 Disablement Disablement SECRDU Channel 9 OR CHQ POM Input 1 ASD535 2 Disablement Disablement SECRDU Channel 13 OR CHQ SIM Input ASD535 1 and 2 Disablement Disablement SECRDU Channel 9 and 13 AND CH...

Page 14: ...he Disablement function on ASD1 is active Used to disable inputs via C E 10 Disablement 1 2 Input May be used as required Is activated whenever the Disablement function on ASD1 is active 11 Reset 1 1 Input Activated for 5 seconds whenever the Reset function on ASD1 is activated Used to reset the ASD via C E 12 Reset 1 2 Input May be used as required Is Activated for 5 seconds whenever the Reset fu...

Page 15: ...ev 1 0 Page 15 of 21 I O points should be set as follows Channel attributes should be set as shown All outputs should have attributes CLEARED Input 9 and 13 should be set to DISABLEMENT all other inputs should be set to TRANSPARENT NON LATCHING ...

Page 16: ...CRDU Channel 5 ASD535 1 Reset Action SECRDU Channel 11 OR CHQ POM Output ASD535 2 Reset Action SECRDU Channel 15 OR CHQ POM Output The ASD 535 2 has only one reset input output for both sensors ASD535 1 Disablement Disablement SECRDU Channel 9 OR CHQ POM Input 1 ASD535 2 Disablement Disablement SECRDU Channel 13 OR CHQ SIM Input ASD535 1 and 2 Disablement Disablement SECRDU Channel 9 and 13 AND CH...

Page 17: ...all the mounting bracket in the first slot and fasten with the Torx screw provided with the bracket Locate the relevant plug for the type of ASD and connect the SEC HIM 35 On the ASD531 and ASD532 install the board in terminals 8 to 16 Note the 2 fingers not connected On the ASD535 install the board in terminals 10 to 20 ...

Page 18: ...To install the SEC HIM 35B first install mounting bracket in the second slot and fasten with the Torx screw provided with the bracket Install the loop wiring into the CHQ SIM on the SEC HIM 35 then slide the unit into the carrier making sure that no cables are pinched Route the interconnection cable in a position where it can t get damaged and plug it into the receptacle provided on the SEC HIM 35...

Page 19: ...off cut out the label and slide it into the label pocked on the side of the SECRDU module Place the SYNCRO SECRDU behind the carrier plate opening Using the M3 screws provided attach the SECRDU to the carrier plate 6 2 2 Taktis Installation Using the template provided modify print off cut out the label and slide it into the label pocked on the side of the SECRDU module Place the TAKTIS SECRDU squa...

Page 20: ...ent damage may result and warranty will be void Insert the cabled into the top of its respective terminal while pushing GENTLY vertically downwards on the white terminal release button Incoming and outgoing terminals are provided The termination switch on the last unit must be switched on otherwise it must be switched off To remove the cables GENTLY push in the white terminal release button for th...

Page 21: ...Incite Hochiki Securiton Interface Module Rev 1 0 Page 21 of 21 ...

Reviews: