PART #22018-DH - High-Resolution Positioner
Page 10
COMMAND TYPE:
The COMMAND TYPE function is used to configure the command signal input for either 4-20mA,
1-5V, 0-5V, 0-10V, 2-10V, or digital so as to match the type of command signal being used. Upon
selecting the COMMAND TYPE function, the Command Input indicator will turn on steady, while the
indicator for the selected type
will flash. Use the adjust buttons (▲ or ▼) to select the desired input
type. The selection will be saved when the MODE button is pressed, which will also advance the
unit to the LOSS OF COMMAND function.
LOSS OF COMMAND:
When using 1-5V, 2-10V, 4-20mA, or a Digital input type for the command signal, the DHC-400 will
detect when the command signal is lost or out of range. A loss of command condition is detected
whenever the input is disconnected, the input becomes less than 0.75V (for 1-5V input), 1.5V (for
2-10V input) or 3mA, or the input is connected backwards. An out of range condition is detected
whenever the input becomes greater than 5.25V (for 1-5V input), 10.5V (for 2-10V input), or 21mA.
If the DHC-400 detects a loss of command, a fault will be indicated (see FAULT INDICATORS), and
the actuator will be moved to one of three preset positions: the open position, the closed position,
or the position last attained prior to losing the command signal. The LOSS OF COMMAND function
is used to set the desired default position.
When the LOSS OF COMMAND function is selected, the adjust buttons are used to set the default
position. The DHC-400 indicates the selected default setting by flashing the Open function indicator
for the open default position, or it will flash the Close function indicator for the closed default position.
When neither indicator is on, then the "last position" default is selected.
When a 0-5V or 0-10V command signal is used, a loss of command signal cannot be reliably
detected. Therefore, if the unit is configured for a 0-5V or 0-10V command signal (see COMMAND
INPUT), the MODE button will not select the LOSS OF COMMAND function. However, the DHC-
400 can detect when a 0-5V or 0-10V command signal is out of range (i.e., greater than 5.25V or
greater than 10.5V) or connected backwards. When an out of range condition is detected for a 0-
5V or 0-10V input, the motor is turned off (leaving the actuator in its "last position") and a fault will
be indicated (see FAULT INDICATORS).
POSITION OUT CAL:
The POSITION OUT CAL function is used to calibrate an optional feedback transmitter output. An
appropriate transmitter option module is required to use this feature. When the POSITION OUT
CAL function is first selected (by pressing the MODE button while in the LOSS OF COMMAND
function), the CLOSE indicator will flash, and the current associated with the closed position will
appear at the option module output. If desired, the output can be adjusted (using the adjust buttons)
to any value from 4 to 20mA. The new setting is saved when the MODE button is pressed.
Pressing the MODE button will leave the unit in the POSITION OUT CAL function except that the
OPEN indicator will flash, and the output current associated with the open position will appear at
the option module output. Like the closed setting, the output can be adjusted to any current from 4
Summary of Contents for 22018-DH
Page 1: ......
Page 3: ...PART 22018 DH High Resolution Positioner Page 3 BOARD OUTLINE...
Page 17: ...PART 22018 DH High Resolution Positioner Page 17 WIRING DIAGRAMS Output Configurations...
Page 18: ...PART 22018 DH High Resolution Positioner Page 18 WIRING DIAGRAMS Input Configurations...
Page 19: ...PART 22018 DH High Resolution Positioner Page 19 WIRING DIAGRAMS Special Applications...
Page 20: ...PART 22018 DH High Resolution Positioner Page 20 WIRING DIAGRAMS Special Applications...