PART #22018-DH - High-Resolution Positioner
Page 7
Controlling the DHC-400 from the Override Input is accomplished by connecting a specific
resistance to select a specific operation. The table below defines the operations and their associated
resistance. See Special Applications for details on using the Override Input for an Auto/Manual
Station.
RESISTANCE
OPERATION
> 4.3K ohms
OFF
3.3K ohms ±5%
LATCH
2K ohms ±5%
OPEN
1.2K ohms ±5%
CLOSE
510 ohms ±5%
STOP
The OPEN function will operate the motor in the open direction as set by the OPEN mode, while
the CLOSE function operates the motor in the closed direction as set by the CLOSE mode. The
LATCH function will maintain the previously selected function; this allows momentary switches to
be used for the OPEN and CLOSE functions. The OFF and STOP functions turn the motor off, which
also unlatches the OPEN or CLOSE functions.
Note that the OPEN and CLOSE functions may work in reverse until the open and closed positions
are set by the OPEN and CLOSE modes. The DHC-400 will automatically turn the motor off when
the open or closed positions are reached. However, if a feedback fault occurs (see FAULT
INDICATOR), the motor will be turned on for a period of 15 minutes in the selected direction. For
this reason, limit switches should be used when using the OVERRIDE mode, and should be set to
a position acceptable for the application. The 15 minute period can also be terminated using the
OFF or STOP function.
The motor is also automatically turned off if the DHC-400 detects a stall (see STALL DETECTION).
An OPEN or CLOSE operation can be attempted again after switching to the OFF, LATCH, or STOP
functions first.
The motor is also turned off if a motor current trip is detected (see TRIP SETTING). If the trip
occurred during an OPEN operation, the OPEN operation is disabled until the trip condition is
corrected. The CLOSE operation may be used to attempt to clear the trip condition (by causing a
certain amount of motion in the closed direction).Likewise, if a trip occurs during a CLOSE operation,
the OPEN operation can be used for clearing the trip. If a trip occurs in both directions (i.e., before
the first trip can be cleared), the trip can only be cleared by a mechanical override mechanism, or
by using the MANUAL mode from the DHC-400 front panel, or by powering the DHC-400 down and
back up.
Summary of Contents for 22018-DH
Page 1: ......
Page 3: ...PART 22018 DH High Resolution Positioner Page 3 BOARD OUTLINE...
Page 17: ...PART 22018 DH High Resolution Positioner Page 17 WIRING DIAGRAMS Output Configurations...
Page 18: ...PART 22018 DH High Resolution Positioner Page 18 WIRING DIAGRAMS Input Configurations...
Page 19: ...PART 22018 DH High Resolution Positioner Page 19 WIRING DIAGRAMS Special Applications...
Page 20: ...PART 22018 DH High Resolution Positioner Page 20 WIRING DIAGRAMS Special Applications...