 PART #22018-DH - High-Resolution Positioner 
 

 

 

Page 7

 

 

 

 

Controlling  the  DHC-400  from  the  Override  Input  is  accomplished  by  connecting  a  specific 
resistance to select a specific operation. The table below defines the operations and their associated 
resistance.  See  Special  Applications  for  details  on  using  the  Override  Input  for  an  Auto/Manual 
Station. 

RESISTANCE  

 

OPERATION 

> 4.3K ohms   

 

OFF 

3.3K ohms ±5%  

 

LATCH 

2K ohms ±5%  

 

OPEN 

1.2K ohms ±5%  

 

CLOSE 

510 ohms ±5%  

 

STOP 

The OPEN function will operate the motor in the open direction as set by the OPEN mode, while 
the CLOSE function operates the motor  in the closed direction as set by the CLOSE mode. The 
LATCH function will maintain the previously selected function; this allows momentary switches to 
be used for the OPEN and CLOSE functions. The OFF and STOP functions turn the motor off, which 
also unlatches the OPEN or CLOSE functions. 

Note that the OPEN and CLOSE functions may work in reverse until the open and closed positions 
are set by the OPEN and CLOSE modes. The DHC-400 will automatically turn the motor off when 
the  open  or  closed  positions  are  reached.  However,  if  a  feedback  fault  occurs  (see  FAULT 
INDICATOR), the motor will be turned on for a period of 15 minutes in the selected direction. For 
this reason, limit switches should be used when using the OVERRIDE mode, and should be set to 
a position acceptable for the application. The 15 minute period can also be terminated using the 
OFF or STOP function. 

The motor is also automatically turned off if the DHC-400 detects a stall (see STALL DETECTION). 
An OPEN or CLOSE operation can be attempted again after switching to the OFF, LATCH, or STOP 
functions first. 

The  motor  is  also  turned  off  if  a  motor  current  trip  is  detected  (see  TRIP  SETTING).  If  the  trip 
occurred  during  an  OPEN  operation,  the  OPEN  operation  is  disabled  until  the  trip  condition  is 
corrected. The CLOSE operation may be used to attempt to clear the trip condition (by causing a 
certain amount of motion in the closed direction).Likewise, if a trip occurs during a CLOSE operation, 
the OPEN operation can be used for clearing the trip. If a trip occurs in both directions (i.e., before 
the first trip can be cleared), the trip can only be cleared by a mechanical override mechanism, or 
by using the MANUAL mode from the DHC-400 front panel, or by powering the DHC-400 down and 
back up. 

 

 

Summary of Contents for 22018-DH

Page 1: ......

Page 2: ...ry switches fault relay contact or digital communications A wide range of data is accessible through a digital communications module providing additional control or information ADDITIONAL FEATURES 10...

Page 3: ...PART 22018 DH High Resolution Positioner Page 3 BOARD OUTLINE...

Page 4: ...it s size and mounting allows the DHC 400 to replace the DMC 100 series controllers in most applications with minimal rewiring The simple three button control MODE and allows the user to perform a com...

Page 5: ...otentiometer are connected to J1 as shown in the Block Diagram The feedback potentiometer wiper must be connected to pin 5 while one end is connected to pin 4 and the other end to pin 6 The Polarity D...

Page 6: ...ators will flash to indicate specific settings associated with the mode Each of the modes are described in more detail in the following sections If a 0 5V or 0 10V command signal is used the LOSS OF C...

Page 7: ...r closed positions are reached However if a feedback fault occurs see FAULT INDICATOR the motor will be turned on for a period of 15 minutes in the selected direction For this reason limit switches sh...

Page 8: ...manual operation of the actuator by using the adjust buttons and without affecting any other settings within the DHC 400 When the button is pressed the MOTOR 1 J1 4 output is connected to BAT POS J2 1...

Page 9: ...The adjust buttons are used to set the actuator to a desired position Whenever the actuator position falls between the defined closed position and the Aux Close position the Aux Close Output indicator...

Page 10: ...s the selected default setting by flashing the Open function indicator for the open default position or it will flash the Close function indicator for the closed default position When neither indicato...

Page 11: ...sed when operating the motor under a fault condition The OVERRIDE mode can also operate the motor when a fault condition exists see OVERRIDE MODE for details Note that the indicators may not indicate...

Page 12: ...disabled The command signal cannot clear this condition only manual operation or a mechanical override can clear the fault Alternatively the DHC 400 can be powered off and then on to temporarily clea...

Page 13: ...d The fault can be cleared in the same manner as previously described for a Double Stall Feedback Alarm A fault condition is detected whenever the feedback signal is out of range that is less than 5 o...

Page 14: ...lows the use of a more moderate battery power supply and smaller gauge wires for a given length see WIRE TABLE The trip setting essentially performs the same function as commonly used torque switches...

Page 15: ...turn actuator the return spring can generate high electrical energies while back driving the motor that can damage the DHC 400 motor outputs In this application the motor must be disconnected usually...

Page 16: ...VDC input 10 5V 0 10 VDC 2 10 VDC input 21mA 4 20mA input A FEEDBACK SIGNAL INPUT Input Voltage 0 to 2 5 VDC External Feedback Potentiometer 1K ohm COMMAND POTENTIOMETER POWER OUTPUT J2 6 5V OUT 5mA...

Page 17: ...PART 22018 DH High Resolution Positioner Page 17 WIRING DIAGRAMS Output Configurations...

Page 18: ...PART 22018 DH High Resolution Positioner Page 18 WIRING DIAGRAMS Input Configurations...

Page 19: ...PART 22018 DH High Resolution Positioner Page 19 WIRING DIAGRAMS Special Applications...

Page 20: ...PART 22018 DH High Resolution Positioner Page 20 WIRING DIAGRAMS Special Applications...

Page 21: ...voltage drop of 1VDC with 20 of the locked rotor current and assumes that the full load running current is less than that All signal wires on the DHC 400 should be connected with wire sizes ranging f...

Page 22: ...____________________________ _________________________________________________________________ _________________________________________________________________ _______________________________________...

Page 23: ...____________________________ _________________________________________________________________ _________________________________________________________________ _______________________________________...

Page 24: ...24 Contact Information Debbie Voges dvoges indelac com 859 727 7890 ext 100 Matt Robinson mrobinson indelac com 859 727 7890 ext 109 Talbot Caywood tcaywood indelac com 859 727 7890 ext 110 For News U...

Reviews: