System with online functionality
66
©
COMSOFT
8.1 Baud rate detection
Figure 60:
Baud rate detection
With the function
Baud rate detection
the current baud rate
on the running PROFIBUS is displayed. During the baud rate
scan additionally the all over signal level on the PROFIBUS is
measured and evaluated.
U < 2.5 V:
Weak level or no longer detectable.
2.5 - 7.2 V:
Level is ok.
U > 7.2 V:
If the indicated level is > 7.2 Volt, this is an
indication for a faulty power supply of the
Slaves or for reflections at the bus.