Settings
the following properties regarding the
online functions may be selected:
•
Livelist hold (Yes / No, Default: No)
-
If the livelist hold is activated, also sporadically
detected DP Slaves at the PROFIBUS are stored in
the livelist.
•
Level timeout (2s, 5s, 10s, 60s, ~, Default: 2s)
-
If the adjusted level time expires, the level
measurement is proceeded with the next DP Slave.
With “~” adjusted,
NetTEST II
waits endless for a
valid level measurement with the actual DP Slave.
This can be useful in connection with low baud
rates or very slow DP Slaves.
•
Level scrolling (Yes, No, Default: No)
-
With Level scrolling activated, the bar graph
display is automatically shifted to display always
the actual measured DP Slave which guarantees a
complete level measurement with all selected
DP Slaves.
•
Event update (2 s, 5 s, 10 s, 60 s, ~, Default: 2 s)
-
The event update is responsible for the event
protocol, for the event count and for the diagnostic
event. If the set update time is reached, then the
display window is updated. During updating events
occurring at the PROFIBUS cannot be registered.
Thus, it is recommended to set to ‚~’, especially for
higher baud rates (
≥
1,5 Mbit) and to update the
display window manually by means of the key
.