background image

7 - ENG

200-2824

Main Power Disconnect

 

Install a main power disconnect switch in the power line to 

the compressor, near the compressor’s location. It is operated 

manually, but when it is in the ON position, the compressor 

will start up or shut down automatically based on air demand. 

ALWAYS operate this switch to OFF when the compressor is not 

being used.

Pressure switch 

(see 

A

)

 

This switch turns on the compressor. It is operated manually, 

but when in the ON position, it allows the compressor to start up 

or shut down automatically, without warning, upon air demand. 

ALWAYS set this switch to OFF when the compressor is not 

being used.

 

WARNING:

For your safety, tank pressure is preset    

 

within the switch and must never be tampered with.

 

This switch must not be adjusted by the operator; doing so 

will void the warranty. The pressure switch controls the level of 

air pressure in the tank by automatically starting and stopping the 

motor, as required to maintain the factory preset pressure level.
 

The pressure switch also automatically bleeds pressure from 

the pump head when the pump stops. This feature eliminates 

back pressure in the pump, ensuring easier starting.

Tank Safety Valve

 (see 

B

)

 

Used to allow tank pressure to escape into the atmosphere. 

If the pressure switch does not shut off the compressor at it’s “cut-

out” pressure setting, the safety valve will protect against high 

pressure by releasing tank pressure at it’s factory set pressure 

(slightly higher than the pressure switch “cut-out” setting). To 

operate manually, pull the ring on the valve to relieve air pressure 

in the tank.

Pressure Release Valve

 (see 

C

 

The pressure release valve (located on the bottom of the 

pressure switch), is designed to release compressed air from the 

compressor head and outlet tube when the compressor reaches 

“cut-out” or is shut off. The pressure valve allows the motor to 

restart freely. When the motor stops running, air will be heard 

escaping from this valve for a few seconds. No air should be 

heard leaking when the motor is running or after brief release 

after reaching “cut-out” pressure. 

Tank Pressure Gauge

 (see 

D

)

 

This gauge measures the pressure level of the air stored 

in the tank. It is not adjustable by the operator, and does 

not

 

indicate line pressure.

COMPRESSOR CONTROLS

ELECTRICAL POWER REQUIREMENTS

Fig. 3

A

B

D

(Measures pressure in 

tank, not line pressure)

C

WARNING:

Ensure that all guards and shrouds are in  

 

 

place before pressing the reset switch to restart the  

  motor.

 

TOPS senses both temperature and current, providing 

more complete motor overload 

protection than a magnetic starter, 

which senses only current. If TOPS 

senses an overload condition, it 

will automatically shut down the 

compressor. Allow 10-15 minutes 

for the unit to cool down, than press 

the reset button on the motor to restart the compressor.

 

If the motor shuts down because of overload, wait 10–15 

minutes so the motor can cool down, then press (

NEVER force

the reset switch (see 

E

) to restart the motor (see 

Fig. 4

).

 

Refer to the air compressor’s serial label for the unit’s voltage 

and amperage requirements. Ensure that all wiring is done by 

a licensed electrician, in accordance with the National Electrical 

Code. Use electrical conduit to protect the wiring.

 

For best performance and reliable starting, the air 

compressor must be installed on a dedicated circuit, as 

close as possible to the electrical power panel.

 Provide 

circuit breaker or fuse protection at your main power panel. Use 

time delay fuses on the circuit, because the compressor will 

momentarily draw several times its specified amperage when first 

started.

 

Install a main power disconnect switch in the line from the 

panel to the compressor. The main power disconnect switch 

must be located near the compressor, for ease of use and safety. 

When turned OFF, the main power disconnect switch shuts off all 

power to the compressor. When it is turned ON, the compressor 

will start and stop automatically, controlled by the pressure 

switch.

 

Low voltage will cause difficult starting or an overload. Low 

voltage can be caused by a low supply voltage from the local 

power company, other equipment running on the same line, or 

inadequate wiring. If any other electrical devices are drawing from 

the compressor’s circuit, it may fail to start.
 

Low voltage to the compressor can be caused by a 

supply wire of insufficient gauge for the distance between the 

compressor and the power source. The longer the distance, the 

larger the wire gauge (lower the number) must be, to overcome 

the inherent voltage loss caused by the wire resistance. Refer to 

the National Electrical Code to determine proper wire size for your 

circuit.
 

If the wiring is not adequate, the input voltage will drop by 20 

to 40 volts at startup. Low voltage or an overloaded circuit can 

result in sluggish starting that causes the circuit breaker to trip, 

especially in cold conditions.

 

This product must be connected to a grounded, metallic, 

permanent wiring system, or an equipment - grounding terminal 

or lead on the product.

MOTOR RESET SWITCH

Fig. 4

E

ELECTRICAL WIRING

MAIN POWER PANEL

MAIN POWER DISCONNECT SWITCH

LOW VOLTAGE PROBLEMS

GROUNDING INSTRUCTIONS

Summary of Contents for ILA5148080

Page 1: ...s contenues dans ce manuel peut entra ner l annulation de la garantie causer des blessures et ou des dommages mat riels Le fabricant NE SAURA tre tenu responsable de dommages r sultant de l inobservat...

Page 2: ...ny manner will void the warranty If tank develops a leak replace it immediately with a new tank or replace the entire compressor RISK OF ELECTRICAL SHOCK Never use an electric air compressor outdoors...

Page 3: ...compressed air distribution lines RISK OF FIRE Unattended operation of this compressor could result in personal injury or property damage To reduce the risk of fire do not allow the compressor to oper...

Page 4: ...oil lubed compressors oil can leak or spill and could result in fire or breathing hazard Oil leaks will damage paint carpet or other surfaces in vehicles or trailers Always place the compressor on a p...

Page 5: ...the power panel and use a longer air hose or distribution line to reach the usage area b The flywheel side of the compressor must be at least 12 inches 31 cm from any wall or obstruction in a clean w...

Page 6: ...k not pressure in the air line Install an air regulator in the drop line for each tool to regulate air pressure to that tool Never exceed the maximum pressure rating of the tool Air lubrication Instal...

Page 7: ...OPS senses both temperature and current providing more complete motor overload protection than a magnetic starter which senses only current If TOPS senses an overload condition it will automatically s...

Page 8: ...the tank petcock see D 4 Turn ON the main power disconnect switch Turn the pressure switch to the AUTO position see B The pump will start filling the tank with air When the air pressure in the tank re...

Page 9: ...starts automatically ALWAYS shut off the main power disconnect and bleed all pressure from the system before servicing the compressor and when the compressor is not in use Do not use the unit with the...

Page 10: ...where the belts can be easily removed and installed 4 Remove and replace belts NOTE The belts must be centered over the grooves on the flywheel and motor pulley 5 Shift the motor back to the point whe...

Page 11: ...ll substantially reduce the performance of your air compressor If you suspect a leak spray a small amount of soapy water around the area of the suspected leak with a spray bottle If bubbles appear rep...

Page 12: ...and flywheel Check alignment Low oil level in pump crankcase Keep oil at proper level at all times Excess carbon on valves or top of piston Contact a qualified service center Oil in discharge air Worn...

Page 13: ...nnulera la garantie Si une fuite est observ e sur le r servoir le remplacer imm diatement par un nouveau r servoir ou remplacer le compresseur au complet RISQUE DE CHOC LECTRIQUE Ne jamais utiliser un...

Page 14: ...ier galvanis pour propulser l air comprim RISQUE D INCENDIE Le fonctionnement sans surveillance du compresseur pourrait entra ner des blessures corporelles ou des dommages la propri t Ne pas laisser l...

Page 15: ...istribuer correctement l huile Tous les pieds doivent tre soutenus et des cales doivent tre plac es aux endroits n cessaires avant la fixation au sol Fixez tous les pieds au sol Il est galement recomm...

Page 16: ...d une ligne de distribution pour atteindre la zone d utilisation b Le compresseur doit tre situ au moins 30 cm de tout mur ou obstacle dans un endroit propre et bien ventil afin d assurer une circula...

Page 17: ...te d air Installer un r gulateur d air dans la conduite de drainage de chaque outil pour r guler la pression d air de cet outil Ne d passez jamais la limite de pression de l outil Lubrification de l a...

Page 18: ...OMMANDES DU COMPRESSEUR AVERTISSEMENT Veillez ce que toutes les s curit s et protections soient install es avant d appuyer sur l interrupteur de remise en marche Le TOPS d tecte la temp rature et l in...

Page 19: ...rsque l air comprim est utilis le manocontacteur red marrera le moteur automatiquement afin d envoyer davantage d air comprim dans le r servoir AVERTISSEMENT El moteur lectrico y la bomba del compreso...

Page 20: ...add B Replacer le bouchon de remplissage de l huile Ne remplissez jamais au dessus du niveau ou underfill la pompe REMARQUE Utilisez une huile compl tement synth tique et sans d tergent pour compresse...

Page 21: ...ent TOUJOURS arr ter le pouvoir disjoncteur principal et purger toute la pression du syst me avant l entretien du compresseur et lorsque le compresseur n est pas utilis Ne pas utiliser l appareil sans...

Page 22: ...ment expos des salet s et de la peinture Tirer sur la bague de la soupape de s ret du r servoir quotidiennement afin d assurer que la soupape fonctionne correctement et pour nettoyer la soupape de tou...

Page 23: ...Cognement de la pompe Poulie du moteur ou volant motoeur desserr Resserrez la poulie et le volant moteur V rifiez l alignement Niveau d huile trop bas dans le carter de la pompe Maintenez le niveau d...

Page 24: ...re invalidar la garant a Si detecta un escape en el dep sito reempl celo inmediatamente con un nuevo dep sito o reemplace todo el compresor RIESGO DE DESCARGA EL CTRICA Nunca utilice un compresor el c...

Page 25: ...nes personales o da os materiales No utilice mangueras de pl stico o pvc para aire comprimido Use solo mangueras y conectores de acero galvanizado para l neas de distribuci n de aire comprimido RIESGO...

Page 26: ...gotear o derramarse y ocasionar un peligro de incendio o causar problemas de respiraci n El goteo de aceite podr a da ar la pintura las alfombrillas u otras superficies de veh culos o remolques Deposi...

Page 27: ...el compresor cerca del panel de alimentaci n y el uso de una manguera de aire m s largo o l nea de distribuci n para alcanzar el rea de uso b El lado del volante del compresor se debe encontrar como...

Page 28: ...de aire en la l nea de ca da para cada herramienta a fin de regular la presi n de aire hacia dicha herramienta Nunca debe sobrepasar la presi n nominal m xima de la herramienta Lubricaci n de aire Ins...

Page 29: ...agado Man metro del tanque vea D Este man metro mide la presi n del aire almacenado en el tanque No es ajustable por el operador y no indica la presi n de la l nea CONTROLES DEL COMPRESOR REQUISITOS D...

Page 30: ...aire y disminuir el nivel de presi n en el dep sito el interruptor de presi n volver a arrancar el motor y el bomba comenzar a llenar neuvamente el dep sito ADVERTENCIA La bomba genera altas temperatu...

Page 31: ...exceso NOTA Utilice un aceite completamente sint tico y sin detergente para compresor de aire NOTA El ajuste de la tensi n de la correa de transmisi n y la alineaci n de la polea se realizan al mismo...

Page 32: ...correa Todas las piezas m viles deben quedar protegidas Esta unidad arranca autom ticamente SIEMPRE apague el compresor quite el enchufe de la toma de corriente y purgue toda la presi n del sistema an...

Page 33: ...as que est n pintando anular n su garant a Tire de la v lvula de seguridad del dep sito todos los d as para asegurarse de que la v lvula funciona adecuadamente y para limpiar la v lvula de cualquier o...

Page 34: ...ificado Golpeteo de la bomba del compresor Polea del motor o volante del compresor suelto Vuelva a ajustar la polea y el volante Verifique la alineaci n Bajo nivel de aceite en el c rter de la bomba M...

Page 35: ...200 2824 35 200 2824 NOTES...

Page 36: ...ervez votre re u et ce manuel pour r f rence ult rieure Quand vous avez besoin des services de l usine s il vous pla t contactez au centre d entretien autoris le plus proche ou composez simplement le...

Reviews: