122/142
AB Industrietechnik srl – Via Julius Durst, 70 – 39042 BRESSANONE (BZ) Italy – Tel: +39 0472/830626 – info@industrietechnik.it – www.industrietechnik.it
Registers
Description
Default
Min
Max.
R/W
7574
MANUAL_OCCUPANCY_ZONE_2
0=Timer extension off
1=Timer extension on
2=zone 2 off
0
0
2
R/W
7575
MANUAL_OCCUPANCY_ZONE_3
0=Timer extension off
1=Timer extension on
2=zone 3 off
0
0
2
R/W
7576
MANUAL_OCCUPANCY_ZONE_4
0=Timer extension off
1=Timer extension on
2=zone 4 off
0
0
2
R/W
7577
STA_MANUAL
0=Winter
1=Summer
0
0
1
R/W
7578
FAN_SPEED_MODE
0=Manual speed 1
1=Manual speed 2
2=Manual speed 3
3=Automatic speed
0
0
3
R/W
7579
ON_OFF_VIA_MODBUS
0=OFF, 1=ON
1
0
1
R/W
7580
YEAR_SET
o
year to be set
2012
2012
2100
R/W
7581
MONTH_SET
o
month to be set
1
1
12
R/W
7582
DAY_SET
o
day to be set
1
1
31
R/W
7583
HOUR_SET
o
time to be set (hour)
0
0
23
R/W
7584
MIN_SET
o
time to be set (min)
0
0
59
R/W
7585
ABI_CLOCK_SET_FROM_MODBUS
o
to update the clock via Modbus, set the
year, month, day, hour, minutes in order with registries 7580 to 7584. Then set the
variable ABI_CLOCK_SET_FROM_MODBUS to 1. The settings are automatically
loaded to the target appliance and the variable ABI_CLOCK_SET_FROM_MODBUS
is automaticaly reset to 0.
0
0
1
R/W
7586
RESET_PARAM_TO_DEFAULT
o
set parameter to 1 to reload the default settings.
Once this has been completed, the parameter automatically resets to 0
0
0
1
R/W
7587
LOCK_KEYBOARD
0=Keypad unlocked
1-Keypad locked
0
0
1
R/W
from 7588
to 7596
Reserved registers (DEBUG)
R/W
7597
Higher software version (factory setting)
-
-
-
R
7598
Lower software version (factory setting)
R
7599
Software revision number (factory setting)
-
-
-
R
7600
DEHUM_VALVE_SELECT
RQO\IRUFRQ¿JXUDWLRQVDQG
'HKXPLGL¿HUXVHG
1=ON/OFF valve used to supply fan-coil
0
0
1
R/W
7601
ABIL_FAN
0=Fan disabled
1=Fan enabled only during the summer season
2=Fan enabled only during winter season
3=Fan enabled in all seasons
3
0
3
R/W
TO OBTAIN THE REAL ADDRESS, SUBTRACT NUMBER 1 FROM THE REGISTER NUMBER
Example: the address of the SUN_Z1_HOUR_ON register is: 7000 - 1 = 6999.
1RWH6HWDOOWHPSHUDWXUHSDUDPHWHUVXVLQJWKHVDPHXQLWDVGH¿QHGE\WKHSDUDPHWHU81,7B&B)
The values of variables BASIC_HEAT_SETx, BASIC_COOL_SETx, DEV_SET_UPWARD_HEAT, DEV_SET_DOWNWARD_HEAT, DEV_SET_UP-
WARD_COOL, DEV_SET_DOWNWARD_COOL, ECO_SET_ADJUST, HOL_SET_ADJUST, SEL_LIM_LOW, SET_LIM_HIGH, SET_MIN_FLOOR_
HEAT, SET_MAX_FLOOR_HEAT, TEMP_EXT_MIN_HEAT, TEMP_EXT_MAX_HEAT, SET_EXT_MIN_HEAT, SET_EXT_MAX_HEAT, TEMP_EXT_
MIN_COOL, TEMP_EXT_MAX_COOL, SET_EXT_MIN_COOL, SET_EXT_MAX_COOL, OFFSET_RANGE, OFFSET_SETPOINT can be set in °C
if multiple of 5. The SETPOINT_DEHUMIDIFICATION variable cannot be set in %rH if multiple of 5.
The variable values COR_INT_TEMP, COR_REM_AI1, COR_REM_AI2, COR_REM_AI3, PROP_BAND_REG_HEAT, PROP_BAND_REG_COOL,
DO_HYST1, DO_HYST2, DO_HYST3, DO_HYST4, DIFF_ACTUATOR1_FAN1, DIFF_ACTUATOR2_FAN2, PROP_BAND_LIM, HYST_FLOOR,
OFFSET_DEW_POINT_CTRL, HYST_FAN_1, HYST_FAN_2, DIFF_S1_S2, DIFF_S2_S3 in °F can be changed if the value to be set is multiple of 2.
The values are displayed, multiplied by 10, except for the setpoint in °F, parameters
I33
,
I35
,
I47
,
I48
,
I51
,
I52
,
I84
in °F, OFFSET SETPOINT in °F.
Note 2: The value displayed corresponds with the value in Volts, multiplied by 10 (for example: value of 80 = 8.0 V).
Note 3: Parameters
M15
to
M19
DUHDXWRPDWLFDOO\VDYHGEDVHGRQWKHVHOHFWHGFRQ¿JXUDWLRQDQGFDQQRWEHPRGL¿HGH[FHSWIRUWKHRQHVLQGLFDWHGLQSDUD
-
graph
³&RQ¿JXUDEOHGLJLWDORXWSXWVHWXS´SDJH
17
.
1RWH,IYDULDEOHV5$1*(B0$;B92/7B,1387DQGRU5$1*(B0,1B92/7B,1387DUHPRGL¿HGWKH&25B$,B92/7B,1387SDUDPHWHUYDOXHLVUHVHWWR
zero.
Note 5: the correction value COR_AI3_VOLT_INPUT set via Modbus is rounded with step 10, if the difference between RANGE_MAX_VOLT_INPUT -
RANGE_MIN_VOLT_INPUT is higher or equal to 800.