10. Parameter factory settings (level 1 password)
The parameter factory settings are password protected.
Press the
and
buttons together to access the main menu. The following screen is displayed:
CLK
yMdH
(model
FH-xxCSH1
) or
AL
noAL
(model
FH-xxSSH1
)
Press the
or
button to display the following screen:
PAS
1
Press the
button and then the
button until the value
22
is displayed.
Press the
EXWWRQWRDFFHVVOHYHO7KHVFUHHQFRUUHVSRQGLQJWRWKH¿UVWOHYHOSDUDPHWHULVGLVSOD\HG
M01
0
Use the
or
button to scroll through the parameters.
To modify a parameter press the
button and then the
or
buttons to select its value.
Press the
button to save the value or the
ESC
button to exit the parameter editing mode without saving.
To exit the menu, press the
ESC
button one or more times or wait for about 120 seconds.
Parameter
Description
Default
Min
Max.
M01
Controller type
0=Secondary SLAVE controller
1=MASTER controller
0
0
1
M02
Appliance control type:
0=Fixed point control for 2-pipe operation
1=Control with external temperature compensation for 2-pipe operation
&RQWUROZLWK¿[HGSRLQWLQKHDWLQJPRGHZLWKH[WHUQDOWHPSHUDWXUHFRPSHQVDWLRQLQFRROLQJPRGH
3=Fixed point control in heating mode, on the dew point in cooling mode
&RQWUROZLWKH[WHUQDOWHPSHUDWXUHFRPSHQVDWLRQLQKHDWLQJPRGHZLWK¿[HGSRLQWLQFRROLQJPRGH
5=Control with external temperature compensation in heating mode, on the dew point in cooling mode
0
0
5
M03
Modbus activation for SLAVE controller
0=Without Modbus
1=With Modbus
1
0
1
M04
Digital input 1 function:
0=Remote season change (INPUT ON=Winter, INPUT OFF=Summer)
1=Remote On/Off (INPUT ON=OFF, INPUT OFF=ON)
2=Economy (INPUT ON=Economy on)
3=Non-occupied holiday (INPUT ON=Occupied)
4=Condensation contact (INPUT ON=Condensation present)
5=Control request (INPUT ON=Control requested)
6=General alarm (INPUT ON=Active alarm)
7=High temperature alarm (INPUT ON=High temperature) (shown only for MASTER controller)
8=Not used
8
0
8
M05
Digital input 1 contact logic:
0=Normally open (open=INPUT OFF, closed=INPUT ON)
1-Normally closed (closed=INPUT OFF, open=INPUT ON)
0
0
1
M06
Digital input 2 function:
0=Remote season change (INPUT ON=Winter, INPUT OFF=Summer)
1=Remote On/Off (INPUT ON=OFF, INPUT OFF=ON)
2=Economy (INPUT ON=Economy on)
3=Non-occupied holiday (INPUT ON=Occupied)
4=Condensation contact (INPUT ON=Condensation present)
5=Control request (INPUT ON=Control requested)
6=General alarm (INPUT ON=Active alarm)
7=High temperature alarm (INPUT ON=High temperature) (shown only for MASTER controller)
8=Not used
8
0
8
M07
Digital input 2 contact logic:
0=Normally open (open=INPUT OFF, closed=INPUT ON)
1-Normally closed (closed=INPUT OFF, open=INPUT ON)
0
0
1