43/142
AB Industrietechnik srl – Via Julius Durst, 70 – 39042 BRESSANONE (BZ) Italy – Tel: +39 0472/830626 – info@industrietechnik.it – www.industrietechnik.it
Parameter
Description
Default
Min
Max.
I68
$LUGHVWUDWL¿FDWLRQIXQFWLRQ
Determines whether to start the fan at minimum speed if control is not active to prevent
the air to stratify when the control sensor is mounted on the fan coil return.
0=OFF
1=ON in heating and cooling
2=ON in heating only
3=ON in cooling only
1
0
3
I69
)DQVWDUWWLPHGXULQJGHVWUDWL¿FDWLRQF\FOHPLQXWHV
1
1
5
I70
)DQVWRSWLPHLIFRQWUROLVQRWDFWLYHEHIRUHVWDUWLQJDQHZGHVWUDWL¿FDWLRQF\FOHPLQXWHV
10
1
60
I71
0D[LPXPRSHUDWLQJWLPHRIWKHIDQEHIRUHFRQVLGHULQJWKH¿OWHUWREHGLUW\KRXUV
0=Function not used
X=Maximum number of fan operating hours before a warning appears on the display.
2000
0
9990
I72
Value displayed on display A
0=Internal temperature sensor
1=Remote temperature sensor
AI1
2=Remote temperature sensor
AI2
3=Remote temperature sensor
AI3
4=Zone 1 control temperature
(see page
51
)
5=Actuator 2 zone control temperature
(see page
51
)
6=Actuator 3 zone control temperature
(see page
51
)
7=Actuator 4 zone control temperature
(see page
51
)
8=Control temperature for all zones, alternately
9 =Internal humidity reading (for
FH-xxxSH1
models only)
10=Thermal actuator 1 operating setpoint (see page
53
)
11=Thermal actuator 2 operating setpoint (see page
53
)
12=Thermal actuator 3 operating setpoint(see page
53
)
13=Thermal actuator 4 operating setpoint (see page
53
)
14=Operating setpoint for all zones, alternately
15=Dew point
0$67(5FRQWUROOHUÀRZWHPSHUDWXUH
17=Output value 0..10 V
AO1
(V)
18=Output value 0..10 V
AO2
(V)
19=Output value 0..10 V
AO3
(V)
0
0
19
I73
Value displayed on display B
0=Internal temperature sensor
1=Remote temperature sensor
AI1
2=Remote temperature sensor
AI2
3=Remote temperature sensor
AI3
4=Zone 1 control temperature
(see page
51
)
5=Actuator 2 zone control temperature
(see page
51
)
6=Actuator 3 zone control temperature
(see page
51
)
7=Actuator 4 zone control temperature
(see page
51
)
8=Control temperature for all zones, alternately
9 =Internal humidity reading (for
FH-xxxSH1
models only)
10=Thermal actuator 1 operating setpoint (see page
53
)
11=Thermal actuator 2 operating setpoint (see page
53
)
12=Thermal actuator 3 operating setpoint(see page
53
)
13=Thermal actuator 4 operating setpoint (see page
53
)
14=Operating setpoint for all zones, alternately
15=Dew point
0$67(5FRQWUROOHUÀRZWHPSHUDWXUH
17=Output value 0..10 V
AO1
(V)
18=Output value 0..10 V
AO2
(V)
19=Output value 0..10 V
AO3
(V)
20=Current hours:minutes
21=Total hours of fan 1 operation
22=Total hours of fan 2 operation
23=Value of input
AI3
FRQ¿JXUHGDV9LQSXW
24=Display B off
19
0
24
I74
MODE button function
0=Local change of season if a season change contact is not used
1=Timer extension zone 1
2=Timer extension zone 2
3=Timer extension zone 3
4=Timer extension zone 4
5=Operating mode (normal, using the time slots or “non-occupied holiday”)
1
0
5
I75
Unit of measurement (0 = °C, 1 = °F)
0
0
1