47/142
AB Industrietechnik srl – Via Julius Durst, 70 – 39042 BRESSANONE (BZ) Italy – Tel: +39 0472/830626 – info@industrietechnik.it – www.industrietechnik.it
• Analogue
inputs
1. Analogue input 1 (
AI1
):
Parameter
M08
=0
Remote control
sensor for zone 1
Sensor
AI1
is used as a control sensor for zone 1.
M08
=1
Remote control
sensor for zone 2
Sensor
AI1
is used as a control sensor for zone 2.
M08
=2
Remote control
sensor for zone 3
Sensor
AI1
is used as a control sensor for zone 3.
M08
=3
Remote control
sensor for zone 4
Sensor
AI1
is used as a control sensor for zone 4.
M08
=4
External sensor
Sensor
AI1
is used as an external sensor for control with compensation
M08
=5
Floor sensor for
zone 1
The
AI1
VHQVRULVXVHGDVÀRRUWHPSHUDWXUHPHDVXUHPHQWVHQVRUIRU]RQH
M08
=6
Floor sensor for
zone 2
The
AI1
VHQVRULVXVHGDVÀRRUWHPSHUDWXUHPHDVXUHPHQWVHQVRUIRU]RQH
M08
=7
Floor sensor for
zone 3
The
AI1
VHQVRULVXVHGDVÀRRUWHPSHUDWXUHPHDVXUHPHQWVHQVRUIRU]RQH
M08
=8
Floor sensor for
zone 4
The
AI1
VHQVRULVXVHGDVÀRRUWHPSHUDWXUHPHDVXUHPHQWVHQVRUIRU]RQH
M08
=9
Remote season
changeover contact
M09
=
0
1
Summer
Winter
M08
=10
Remote on/off
M09
=
0
1
On
Off
M08
=11
Non-occupied
holiday
M09
=
0
1
“Non-occupied holiday” mode
Occupied mode
M08
=12
Economy mode
M09
=
0
1
No economy mode
Economy mode
M08
=13
The
AI1
sensor is used for the dew point calculation (only for the
MASTER or SLAVE_Y controller)
M08
=14
The
AI1
sensor is used as limit sensor for the MASTER or SLAVE:Y
controller
M08
=15
Sensor not used
)RUFRQ¿JXUDWLRQV
M08
=9, 10, 11, 12, the analogue input 1 is used as a digital input. The contact is considered closed
if there is a short-circuit on the analogue input. The contact is considered open if there is no connection.