64/142
AB Industrietechnik srl – Via Julius Durst, 70 – 39042 BRESSANONE (BZ) Italy – Tel: +39 0472/830626 – info@industrietechnik.it – www.industrietechnik.it
• Table of alarms (faulty temperature sensors)
AI3
AI2
AI1
Internal sensor
E01
No alarm
No alarm
No alarm
Alarm
E02
No alarm
No alarm
Alarm
No alarm
E03
No alarm
No alarm
Alarm
Alarm
E04
No alarm
Alarm
No alarm
No alarm
E05
No alarm
Alarm
No alarm
Alarm
E06
No alarm
Alarm
Alarm
No alarm
E07
No alarm
Alarm
Alarm
Alarm
E08
Alarm
No alarm
No alarm
No alarm
E09
Alarm
No alarm
No alarm
Alarm
E10
Alarm
No alarm
Alarm
No alarm
E11
Alarm
No alarm
Alarm
Alarm
E12
Alarm
Alarm
No alarm
No alarm
E13
Alarm
Alarm
No alarm
Alarm
E14
Alarm
Alarm
Alarm
No alarm
E15
Alarm
Alarm
Alarm
Alarm
• Dew point alarm:
In cooling mode, if the dew point control function is active (see paragraph
³'HZSRLQWIXQFWLRQLQFRROLQJPRGH´
SDJH
59
) and the control is not performed on the dew point + offset
I45
(
M02
DQG
M02
LIWKHFRQWUROWHPSHUD
-
ture drops below the threshold [dew point + offset
I45
] the dew point alarm is triggered. Icon
ÀDVKHVDVORQJDV
the alarm condition persists.
Alarm type
MASTER controller action
Secondary controller action
SLAVE_Y
SLAVE_X
MASTER controller
alarm
Column pump ON
Circulator (*)
Valve (*)
'HKXPLGL¿HU21
Alarm ignored
Thermal actuator OFF
Fan coil OFF
'HKXPLGL¿HU21
SLAVE_Y controller
alarm
Alarm ignored
Column pump ON
Circulator (*)
Valve (*)
'HKXPLGL¿HU21
-
SLAVE_X controller
alarm
Column pump ON
Circulator (*)
Valve (*)
'HKXPLGL¿HU21
-
Thermal actuator OFF
Fan coil OFF
'HKXPLGL¿HU21
(*) Circulator and valve = ON if
I46
= 1
Circulator and valve = OFF if
I46
= 0
• Condensation alarm:
,QFDVHRIFRQGHQVDWLRQDODUPWKHJHQHUDODODUPLFRQÀDVKHVDORQJZLWKWKHLFRQ
(see
“21. Anti-condensation
IXQFWLRQ´SDJH
59
Alarm type
MASTER controller action
Secondary controller action
SLAVE_Y
SLAVE_X
MASTER controller
alarm
Column pump ON
Circulator (*)
Valve (*)
'HKXPLGL¿HU21
Alarm ignored
Thermal actuator OFF
Fan coil OFF
'HKXPLGL¿HU21