79/142
AB Industrietechnik srl – Via Julius Durst, 70 – 39042 BRESSANONE (BZ) Italy – Tel: +39 0472/830626 – info@industrietechnik.it – www.industrietechnik.it
&RQ¿JXUDWLRQVWKHUPDODFWXDWRUVLQFRROLQJPRGH
100
0
Control sensor
zone 1
Outputs
I24
DO1
WCS1
I25
DO2
WCS2
WHS1
VHWSRLQWWKHUPDODFWXDWRU
WCS2
VHWSRLQWWKHUPDODFWXDWRU
2, calculated according to paragraph
³6HDVRQRSHUDWLQJVHWSRLQWHFRQRP\
KROLGD\PRGH´SDJH
53
'2WKHUPDODFWXDWRURXWSXW
'2WKHUPDODFWXDWRURXWSXW
I24
: thermal actuator 1 hysteresis
I25
:
thermal actuator 2 hysteresis
If the operating temperature rises above WCS1 + (
I24
:
2) the thermal actuator 1 is enabled. The
icon turns on if
zone 1 is displayed (
I72
=4 or [8 alternately with other zones]).
If the temperature drops below
WCS1
- (
I24
:
2) the thermal actuator 1 is deactivated and the
icon turns off if zone
1 is displayed (
I72
=4 or [8 alternately with other zones]).
If the operating temperature rises above
WCS2
+ (
I25
:
2) the thermal actuator 2 is enabled. The
icon turns on if
zone of the thermal actuator 2 is displayed (
I72
=5 or [8 alternately with other zones]).
If the temperature drops below
WCS2
- (
I25
:
2) the thermal actuator 2 is deactivated and the
icon turns off if the
zone of thermal actuator 2 is displayed (
I72
=5 or [8 alternately with other zones]).
&RQ¿JXUDWLRQVWKHUPDODFWXDWRUVLQKHDWLQJPRGH
100
0
Control sensor
zone 1
Outputs
I26
DO3
WHS3
I25
DO2
WHS2
I24
DO1
WHS1
WHS1
VHWSRLQWWKHUPDODFWXDWRU
1,
WHS2
VHWSRLQWWKHUPDODFWXDWRU
,
WHS3:
VHWSRLQWWKHUPDODFWXDWRU
3, calculated according to paragraph
³6HDVRQRSHUDWLQJVHWSRLQWHFRQRP\
KROLGD\PRGH´SDJH
53
'2WKHUPDODFWXDWRURXWSXW
'2WKHUPDODFWXDWRURXWSXW
'2WKHUPDODFWXDWRURXWSXW
I24
: thermal actuator 1 hysteresis
I25
:
thermal actuator 2 hysteresis
I26
:
thermal actuator 3 hysteresis
If the operating temperature drops below
WHS1
- (I24
:
2) the thermal actuator 1 is enabled. The icon turns on if
zone 1 is displayed (
I72
=4 or [8 alternately with other zones]).
If the temperature rises above
WHS1
+ (
I24
:
2) the thermal actuator 1 is deactivated and the icon turns off if zone 1
is displayed (
I72
=4 or [8 alternately with other zones]).
If the operating temperature drops below
WS2
- (
I25
:
2) the thermal actuator 2 is enabled. The icon turns on if zone
of the
thermal actuator
2 is displayed (
I72
=5 or [8 alternately with other zones]).
If the temperature rises above
WHS2
+ (
I25
:
2) the thermal actuator 2 is deactivated and the icon turns off if the
zone of
thermal actuator
2 is displayed (
I72
=5 or [8 alternately with other zones]).
If the operating temperature drops below
WHS3
- (
I26
:
2) the thermal actuator 3 is enabled. The icon turns on if
zone of the
thermal actuator
3 is displayed (
I72
=6 or [8 alternately with other zones]).
If the temperature rises above
WHS3
+ (
I26
:
2) the thermal actuator 3 is deactivated and the icon turns off if the
zone of
thermal actuator
3 is displayed (
I72
=6 or [8 alternately with other zones]).