95/142
AB Industrietechnik srl – Via Julius Durst, 70 – 39042 BRESSANONE (BZ) Italy – Tel: +39 0472/830626 – info@industrietechnik.it – www.industrietechnik.it
•
7KH(&IDQFRLODFWLYDWLRQORJLFFRQ¿JXUDWLRQVLQKHDWLQJPRGH
I91
=2 or 3 (thermal actuator 1 enabled to function during the winter season):
100%
0%
Control temp.
Actuator
0%
Control temp.
Manual speed ventilator
I6x
I24
WHS1
DO1
I58
AO1
Speed 3
Speed 1
Control temp.
Automatic speed ventilator
AO1
I58
I28
WHS1
:
VHWSRLQWRIWKHWKHUPDODFWXDWRU
1 calculated according to paragraph
³6HDVRQRSHUDWLQJVHWSRLQWHFRQRP\
KROLGD\PRGH´SDJH
53
'2WKHUPDODFWXDWRURXWSXW
$2(&IDQRXWSXW
I24
: thermal actuator 1 hysteresis
I28
:
differential between the thermal thermal actuator 1 and the fan coil
1
I58
VSHHGSURSRUWLRQDOEDQG
I6x
:
I64
LIPDQXDOVSHHGLVVHOHFWHG
I6x
:
I65
LIPDQXDOVSHHGLVVHOHFWHG
I6x
:
I66
LIPDQXDOVSHHGLVVHOHFWHG
Set the EC motor parameters as follows:
- Set parameter
I28
WRGH¿QHWKHGLIIHUHQWLDOEHWZHHQWKHWKHUPDOWKHUPDODFWXDWRUDFWLYDWLRQDQGWKHIDQFRLOGHDFWLYD
-
tion.
- Set the EC fan band by setting
I58
.
- Set the voltage corresponding to the minimum EC motor speed with parameter
I62
.
- Set the voltage corresponding to the maximum EC motor speed with parameter
I63
.
- Set parameters
I64
,
I65
,
I66
WRGH¿QHWKHYROWDJHVIRUVSHHGLQPDQXDORSHUDWLRQ
Example: if
I62
=1 V,
I63
=8 V,
I64
=10%,
I65
=50%,
I66
=100%:
VSHHGFRUUHVSRQGVWR9ĺ>
I64
x (
I63
-
I62
)) +
I62
],
VSHHGFRUUHVSRQGVWR9ĺ>
I65
x (
I63
-
I62
)) +
I62
],
VSHHGFRUUHVSRQGVWR9ĺ>
I66
x (
I63
-
I62
)) +
I62
].
Automatic speed control is linear over the range of speeds 1 to 3, while manual control simply sets a given speed.
To set speed 1 to the minimum EC motor speed, set
I64
to 0.
To set speed 3 to the maximum EC motor speed, set
I66
to 100.
To set speed 2 to the midpoint between speeds 1 and 3, set
I65
to 50.