7KH(&IDQFRLODFWLYDWLRQORJLFFRQ¿JXUDWLRQVLQFRROLQJPRGH
I91
=1 or 3 (thermal actuator 1 enabled to function during the summer season):
100%
0%
Control temp.
Actuator
I24
WCS1
DO1
0%
Control temp.
Manual speed ventilator
I58
AO1
I6x
Control temp.
I58
Automatic speed ventilator
I28
AO1
Speed 3
Speed 1
WCS1
:
VHWSRLQWRIWKHWKHUPDODFWXDWRU
1 calculated according to paragraph
³6HDVRQRSHUDWLQJVHWSRLQWHFRQRP\
KROLGD\PRGH´SDJH
53
'2WKHUPDODFWXDWRURXWSXW
$2(&IDQRXWSXW
I24
: thermal actuator 1 hysteresis
I28
:
differential between the thermal thermal actuator 1 and the fan coil
1
I58
PDQXDOVSHHGK\VWHUHVLV
I6x
:
I64
LIPDQXDOVSHHGLVVHOHFWHG
I6x
:
I65
LIPDQXDOVSHHGLVVHOHFWHG
I6x
:
I66
LIPDQXDOVSHHGLVVHOHFWHG
Set the EC motor parameters as follows:
- Set parameter
I28
WRGH¿QHWKHGLIIHUHQWLDOEHWZHHQWKHWKHUPDOWKHUPDODFWXDWRUDFWLYDWLRQDQGWKHIDQFRLOGHDFWLYD
-
tion.
- Set the EC fan band by setting
I58
.
- Set the voltage corresponding to the minimum EC motor speed with parameter
I62
.
- Set the voltage corresponding to the maximum EC motor speed with parameter
I63
.
- Set parameters
I64
,
I65
,
I66
WRGH¿QHWKHYROWDJHVIRUVSHHGLQPDQXDORSHUDWLRQ
Example: if
I62
=1 V,
I63
=8 V,
I64
=10%,
I65
=50%,
I66
=100%,
VSHHGFRUUHVSRQGVWR9ĺ>
I64
x (
I63
-
I62
)) +
I62
],
VSHHGFRUUHVSRQGVWR9ĺ>
I65
x (
I63
-
I62
)) +
I62
],
VSHHGFRUUHVSRQGVWR9ĺ>
I66
x (
I63
-
I62
)) +
I62
].
Automatic speed control is linear over the range of speeds 1 to 3, while manual control simply sets a given speed.
To set speed 1 to the minimum EC motor speed, set
I64
to 0.
To set speed 3 to the maximum EC motor speed, set
I66
to 100.
To set speed 2 to the midpoint between speeds 1 and 3, set
I65
to 50.