background image

INSTRUCTION

i

Read this instruction before installation 

and wiring of the product

Instruction TPDAxxxxAx

1

TPDAxxxxAx

Pressure transmitter

TPDA...A are single or dual port pressure transmitters with one or two 
universal outputs for 0...10 V or 4...20 mA (selectable).

Technical data

Supply voltage 

 

 

24 V AC/DC ±15 %

Protection class 

 

 

IP54

Calculated power consumption 
     0...10 V mode 

 

 

2 VA (rms) / min. trafo size 7.5 VA 

     4...20 mA mode   

 

2.7 VA (rms) / min. trafo size 9 VA

Overall accuracy, pressure   

≤ 1 % full scale

Annual deviation (typical) 
     P1250 models   

 

±2 Pa 

     P2500 models   

 

±4 Pa 

     P7500 models   

 

±20 Pa

Damping (settable)   

 

1, 2, 4 and 8 s

Operating temperature range  -25…+50°C
Operating humidity    

 

Max. 95 % RH (non-condensing)

Overvoltage on any terminal  

Max. ±18 V (referenced to GND)

Universal outputs PS1, PS2

Configured as 0...10 V 

 

Load impedance ≥ 10 kΩ, 

 

 

 

 

 

Output impedance ≤ 35Ω

Configured as 4...20 mA 

 

Output is actively sourced into a resistive 

 

 

 

 

 

load impedance to signal ground. The  

 

 

 

 

load impedance must be between  

 

 

 

 

40...500Ω

Pressure ranges (full scale)

Model

Pressure 

range (Pa)

mBar

mmH

2

O

inH

2

O

TPDA-12A

PS1

0…1250

0…12.5

0…125

0…5

TPDA-25A

PS1

0…2500

0…25

0…250

0…10

TPDA-75A

PS1

0…7500

0…75

0…750

0…30

TPDA-1225A2

PS1

0…1250

0…12.5

0…125

0…5

PS2

0…2500

0…25

0…250

0…10

TPDA-1275A2

PS1

0…1250

0…12.5

0…125

0…5

PS2

0…7500

0…75

0…750

0…30

Note: 

The suffix in the name denotes the number of sensors in the unit. 

The suffix “-2” indicates two sensors. No suffix means one sensor only.

Installation

The transmitter comes with one cable gland mounted and one loose. If 
two cables are used, one for supply voltage and one for output signals, 
the other cable gland must be assembled to the housing. Screw in the 

cable gland until the plastic knockout in the housing snaps. Make sure to 
remove the plastic knockout completely. Secure the cable gland.

1.  Mount the transmitter horizontally or vertically on a stable, 

vibration-free surface. If the unit is installed in a humid environ-
ment, install it vertically with the cable gland edge of the unit 
pointing down to allow moisture to escape. 

Take extra care when connecting the hoses to the inlet ports, as 

the thin inner connections of the inlets are very sensitive. The lid 

should be kept closed while performing the connections, or the 

thin tubing might detach from the sensor.

2.  Refer to the graphics below for wiring. Use the leftmost cable 

gland for supply voltage and use the rightmost gland for output 

signals in order to minimise crosstalk between supply wires and 

signal wires.

3. 

Set the DIP-switch to the desired operational mode and param-
eters.

4.  Power up the unit.
5. 

Let the unit warm up for 10 minutes, then perform a zero-set 

calibration by pressing the pushbutton.

6.  Connect plastic tubes from the ventilation duct to the pressure 

inlets.  
NOTE: A straight cut off nipple must be used for mounting in the 
ventilation duct.

For optimal measuring results, measuring points with turbulent air 

flow should be avoided. Preferably, measuring should be performed 

at a distance of 2 duct diameters before bends and branching and at 
6 duct diameters after bends and branching. 

Wiring

1. G (+)
2. G0 (-)

3. UO1 +

4. UOI GND
5. UO2 +
6. UO2 GND
 
Terminals 2, 4 and 6 are galvanically the same (GND/G0).
For models with two sensors, the leftmost DIP-switch controls sensor 
1 and the rightmost DIP-switch controls sensor 2 (see diagram 2 
below).

12632 C

 

JUL

 17

EN

Summary of Contents for TPDA-12A

Page 1: ...for output signals the other cable gland must be assembled to the housing Screw in the cable gland until the plastic knockout in the housing snaps Make sure to remove the plastic knockout completely Secure the cable gland 1 Mount the transmitter horizontally or vertically on a stable vibration free surface If the unit is installed in a humid environ ment install it vertically with the cable gland ...

Page 2: ... 300 0 2000 Range 3 0 300 0 500 0 3000 Range 4 0 500 0 1000 0 4000 Range 5 0 700 0 1500 0 5000 Range 6 0 1000 0 2000 0 6000 Range 7 0 1250 0 2500 0 7500 Table 2 Pushbutton Quick press Zero set pressure sensors Disconnect the pressure ports before zeroing Let the unit warm up for 10 minutes before attempting the procedure Zeroing usually takes a few seconds The yellow LED will light up while the ze...

Page 3: ... sfondare la parete di tenuta Assicurarsi di rimuovere completa mente i residui all interno dell apparecchio Serrare la ghiera del pres sacavo 1 Montare il trasmettitore orizzontalmente o verticalmente su una superficie stabile esente da vibrazioni Se l unità è installata in un ambiente umido installarlo in verticale con il bordo pres sacavo dell unità verso il basso per permettere all umidità di ...

Page 4: ...la procedura non riesce ancora è presente un errore del sensore e l unità deve quindi essere sostituita Pressione prolungata 10 s Ripristino impostazioni di fabbrica I LED rosso e giallo lampeggiano alternati per la durata dell operazione L unità quindi si ripristinerà e riavvierà LED di stato Il LED di stato rosso si accende all accensione e si spegne poco dopo quando il sistema è pronto per il f...

Reviews: