background image

2

Summary of Contents for LEA INTERNATIONAL LS Plus 200

Page 1: ...DD2922 NOTED 2 21 11 DAW 1 8 12 1 A B39 38 0002 LS PLUS 200 AC PROTECTOR INSTALLATION MANUAL NOTICE THE INFORMATION AND DESIGN IN THIS DOCUMENT IS THE PROPERTY OF LEA INTERNATIONAL ALL RIGHTS RESERVED REV DATE DRAWN CHECKED ALL DIMENSIONS IN INCHES UNLESS OTHERWISE SPECIFIED CAGE TITLE A ENG APPD PROJ APPD PROJECT NO MATERIAL FRACTIONS ANGLES TOLERANCES SIZE SCALE PAGE OF THIRD ANGLE PROJECTION PR...

Page 2: ...2 ...

Page 3: ...y questions concerning the voltage configuration prior to installation and application of power Perform such work only after reading and understanding all of the instructions contained in this manual Beware of potential hazards wear personal protective equipment and take adequate safety precautions Before performing visual inspections tests or maintenance on the equipment disconnect all sources of...

Page 4: ... conductors are sized appropriately for this SPD Mounting The SPD should be mounted as close as possible to the connection of service point The SPD is mounted using the four mounting holes located near the enclosure corners Electrical conductors should enter the top of the SPD enclosure or on either side near the top of SPD enclosure Electrical conduit should be of sufficient size per NFPA 70 and ...

Page 5: ...ire building ground system to the Safety Ground lug Tighten all connections to the recommended torque value Remote Alarm Connection The SPD offers one set of dry contacts for remote alarm monitoring These screw terminal connections are located on the PC board as shown on Pages 8 or 10 The three connections are labeled NC Normally Closed NO Normally Open and C Common Remote Alarm Contact Maximum Ra...

Page 6: ... circuit is enabled A red LED indicates the Audible Alarm has been silenced and serves as a reminder that the SPD needs to be serviced Audible Alarm Disable button Press to turn off the audible alarm The Alarm Disabled LED will turn red and serves as a reminder that the SPD needs to be serviced If the SPD has been severely damaged disconnect power to the SPD using the circuit breaker or disconnect...

Page 7: ... OFF the Alarm Disabled Light Audible Alarm Disable Button Turns OFF the Alarm and Illuminates the Alarm Disable Light TVSS Status Indicator Light Illuminated Green Indicates Normal Operation with All Protection Modes Functioning Light Illuminated Red Indicates SPD Needs Replacement 7 1 Please Note LS Plus 200 shown without the Disconnect Switch The Operation of the Surge Counter and Audible Alarm...

Page 8: ...8 mm 21 9 16 548 mm Use 3 8 10 mm Mounting Hardware Mechanical Specifications for LS Plus 200 Dimensions are for Reference Only 8 Mounting External mounting brackets with 0 41 10 3 mm mounting holes Dimensions 20 X 16 X 6 508 mm X 406 mm X 152 mm Weight 32 lbs 14 5 kg ...

Page 9: ...e Alarm Contacts Normally Open Common 3X Torque Specification 4 5 in lbs 0 5Nm Normally Closed Contact is Closed when SPD is Powered and Functional Normal State Wire Range 24 to 14 AWG 9 Remote Alarm Contacts NC Contact Closed with SPD powered and Functional Normal State Remote Alarm Contacts NO Contact Open with Power OFF or SPD Requires Replacement NC C NO NC C NO Note Remote Alarm Contacts Chan...

Page 10: ... 21 9 16 548 mm Use 3 8 10 mm Mounting Hardware Mounting External mounting brackets with 0 41 10 3 mm mounting holes Dimensions 20 X 16 X 6 508 mm X 406 mm X 152 mm Weight 33 lbs 15 kg Mechanical Specifications for LS Plus 200 with Disconnect Switch Dimensions are for Reference Only 10 ...

Page 11: ... mm Wire Range 8 to 1 0 AWG Remote Alarm Contacts 3X Torque Specification 4 5 in lbs 0 5 Nm Common Normally Open Note Remote Alarm Contacts Change State with Loss of Power Normally Closed Contact is Closed when SPD is Powered and Functional Wire Range Wire Strip Length Neutral Block Wire Range 11 Remote Alarm Contacts NC Remote Alarm Contacts NO Replacement NC C NO NC C NO Torque 50 in lbs 5 6 Nm ...

Page 12: ...n or Close the Enclosure Door 2 Step 2 Disconnect Handle from the Disconnect or Close the Lock Out of Enclosure in the OFF Position if Required 1 2 Pull Out Locking Tab to Install Install Lock Handle Locking Tab only accepts a Shackle Diameter as shown Lock not supplied by LEA O F F ON 1 12 Disconnect Handle Operation ...

Reviews: