4
6) START UP
1.
Connect the UPS to the wall receptacle.
2.
Push the “On” Switch on the front panel of the UPS until 4 LEDs
(LCD) are lit then extinguished and release the “On” Switch. If you
release your finger before the LED lights are off then the ups shall
not start up. Therefore please keep your finger on the “ON” button
until the LEDs are off. After then the ups starts to operate.
3.
The Backup mode LED (Amber) lights up and the UPS is under
self-test mode now. If Utility is normal, the UPS will run under
Utility mode (Green LED) after its self-test is completed. On the
contrary, the UPS will run under Backup mode and the buzzer
alarms every 2 seconds in case of blackout or over/under voltage.
Caution:
1.
The UPS “On” will not be executed if the above procedure is not
done completely, which means the button is released before all
4 LEDs (LCD) are extinguished.
2.
The UPS will remain at “NO” output, if the start-up operation is
not proceeded properly even though the Input Power Cord is
connected to the wall receptacle.
IMPORTANT NOTICE:
Plug the UPS into the wall receptacle to charge the UPS for over 8
hours after initial installation
STORAGE:
Store at -15 to +30 °C (+5 to +86 °F), charge the UPS battery every
six months.
Store at +30 to +45 °C (+86 to +113 °F), charge the UPS battery every
three months.
5
7) OPERATION TEST
Turn Off the UPS
Push the “Off” Switch for at least 3 seconds to turn off the UPS. If you
press the “Off” Switch less than 3 seconds, the UPS will not execute
shutdown command due to insufficient pressing time.
In some occasions, the UPS will shut itself down in case of overload,
output short-circuited or battery cutoff point reached in the Backup
mode.
The UPS will automatically shut off the output and beep for 5 seconds
then completely shut itself down.
Plug-in Charge
If the Input Power Cord is connected to the wall receptacle properly
and the utility is normal, the UPS will start to charge automatically
without processing “Turn On” procedure. You have to charge for at
least 8 hours every 3 months to avoid from battery self over-discharge
naturally, if the UPS is in an idle condition.
Auto-Restart
The UPS will automatically restart
to provide energy to the output if
the utility recovers in 24 hours after battery cut. The “Backup LED”
will flash every 5 seconds under the waiting situation. On the contrary,
the UPS will not auto-restart if the Utility doesn’t recover within 24
hours. You are required to start up the UPS manually. If you don’t
need UPS auto-restart, you can turn off the UPS by proceeding the
“Turn Off” procedure.
Alarm Silence
The Alarm might be turned off by pushing the “On” Switch for
approximately 1 second in the “Backup” mode. Unless any other
warning or fault condition occurs, the alarm remains at Silence
condition once the “Alarm Silence” is turned off.
Test
Under Utility Normal condition, push the “On” Switch for 3 seconds
to execute the Battery Self-test function. In case the battery is
normal, it will enter into Battery Backup Mode for 10 seconds then
return back to Utility Mode. If the battery voltage is detected lower
than set limit, the Battery Replacement LED will blink for 5 seconds
then extinguish to stop self-test procedure. And if battery is detected
weak or dead, the Battery Replacement LED will steadily illuminate.