INSTALLATION 

ALL THE OPERATIONS DESCRIBED IN THIS SECTION MUST BE CARRIED OUT EXCLUSIVELY BY 
QUALIFIED STAFF. 
The company may no be held liable for any damage caused by incorrect connections or by operations 
that are not described in this manual. 

STORAGE OF THE STS 

The storage area must have the following characteristics 
Temperature :  -10 to +50 C 
Relative humidity : 95% max. 

PREPARATION FOR INSTALLATION 

PRELIMINARY INFORMATION 

Model 

STS450 

STS4100 

STS4150 

STS4200 

STS4300 

STS4400 

Nominal current 

50 

100 

150 

200 

300 

400 

Operating temperature 

0 – 40 C 

Non operating temper. 

-10 to + 50 C 

Max. relative humidity 

90% (non-condensing) during operation 

Max. installation height 

1000 m at nominal current rating 

Dimensions WxDxH 

685x530x1500 mm 

685x580x1770 mm 

Weight 

175 Kg 

205 Kg 

220 Kg 

240 Kg 

Protection level 

IP20 

Cable input 

From base / on front 

Communication 

RS232 standard - TCP/IP option 

Flying transfer 

Available - Standard 

LCD panel and mimic 

Available - Standard 

Backfeed protection 

Available - Standard 

Software management 

Available - Standard 

DRY contact outputs 

Available - Standard 

EPO input 

Available – Standard ( NO) 

<X> letter on table shows 3 pole or 4 pole model options ( 3 = 3 pole , 4 = 4 pole ) 

ELECTROMAGNETIC COMPATIBILITY 

This static transfer switch (STS) conforms to the class C2 specifications (in accordance with the provisions laid 
down by the EN62040-2 standard: STS – EMC requirement). In the home environment ,it may cause radio 
interference. The user may have to take supplementary measures. 
This product is designed for professional use in industrial and commercial environments . Connections to the 
RS232 connectors should be made with the cables provided or ,in any case, with shielded cables less than 3 
meters long. 

INSTALLATION ENVIRONMENT 

When choosing the site in which to install the STS , the following points should be taken into consideration : 

  Avoid dusty environments 

  Check that the floor is level and capable of withstanding the weight of the STS 

  Avoid cramped environments that could impede the normal maintenance activities 

  The relative humidity should not exceed 90%, non-condensing. 

  Check that the ambient temperature, with the STS running, remains between 0 and 40 C 

  Avoid installing the equipment in places exposed to the direct sunlight and hot air. 

REMOVING THE STS FROM PALLET 

The STS is packed and enclosed in a structural cardboard carton to protect it from damage. 

1. 

Inspect  for  damage  that  may  have  occurred  during  the  shipment  If  any  damage  is  noted,  call  the  shipper 
immediately and retain the shipping carton and the STS. 

2. 

Carefully open the carton and take the STS out. 

Retain the carton and packing material for possible future use 

Summary of Contents for InfoSTS

Page 1: ...__________________17 DESCRIPTION 17 PRELIMINARY OPERATIONS 17 POWERING ON FOR THE FIRST TIME 17 Switching On Normal Operation The STS From Off Position 18 Switching To Maintenance Bypass Position From...

Page 2: ...system STS permits switching between two independent AC power supplies SOURCE 1 and SOURCE 2 without shutting down the critical load connected to its output DESCRIPTION OF THE FUNCTIONS OF THE InfoST...

Page 3: ...maintenance bypass High current output tolerant up to 1000 Adjustable long dead time during non synchron transfer up to 3 seconds SCR fault sense circuit Cabinet inside temperature sensor Fast voltage...

Page 4: ...transients All power supply inputs are fuse protected On SCR s heat sink there is a thermal contact to warn the user in case of excessive heat sink temperature Protection shield prevents direct touch...

Page 5: ...tenance the position of this switch must be OFF SS1 Static transfer SCR circuit to source 1 This static switch contains SCRS and snubber components and driven by a driver circuit which is controlled b...

Page 6: ...CH Manual transfer switch is located on back front panel and user transfers the load to input source1 or source2 rapidly During normal operation this switch must be at AUTO position Figure 3 Manuel tr...

Page 7: ...s connected risk of electric shock is valid The unit is powered by more than one power mains When one of the incoming power sources is active the unit contains a dangerous level of voltage even when i...

Page 8: ...7 FRONT VIEWS OF THE STS Interior front view S6 Manual transfer Switch Dry contact outputs EPO Input S3 Output Switch S2 Source 2 I P SW S1 Source 1 I P SW RS232 Port S4 Maintenance Bypass SW figure 4...

Page 9: ...urce 1 input is OK SW1 Source 1 input monitor lamp Off source 1 input failed On source 2 input is OK SW2 Source 2 input monitor lamp Off source 2 input failed On SS1 SCR group fired SS1 Source 1 stati...

Page 10: ...transfer switch STS conforms to the class C2 specifications in accordance with the provisions laid down by the EN62040 2 standard STS EMC requirement In the home environment it may cause radio interfe...

Page 11: ...talling the equipment the following points should be considered The air outlets of the STS is on the top cause of this do not prevent air ventilation from the top side No objects should be left on its...

Page 12: ...d will be overloaded and the voltage of this input source will be go down at this point STS monitors the output current and if current is 200 of nominal output current if the input source phase voltag...

Page 13: ...hs type of protection etc These recommendations are for guideline purposes only and are superceded by local regulations and codes in practice CONNECTIONS InfoSTS Series Static Transfer Switches run on...

Page 14: ...13 3 POLE STS POWER CONNECTIONS Input and output terminals of the 3 pole STS are shown in the following figure figure 7 Connection terminals of 3 pole STS figure 8 3 Pole STS cable connections...

Page 15: ...STS units connects load output neutral to the current used source s neutral the neutral of the other source is isolated from output neutral Figure 9 Connection terminals of 4 pole STS Figure 10 Input...

Page 16: ...ibit relay RL4 Summary alarm relay RL5 Manual or static transfer relay RL6 S1 backfeed trip 1 second active RL7 S2 backfeed trip 1 second active EPO input is NO type interface normally open if EPO inp...

Page 17: ...e corresponding phases of the two separate AC input sources respectively 5 Also proper control and signal wire connections Alarm relays EPO etc should be made through the screw terminal block shown in...

Page 18: ...the following switch positions S1 input 1 MCCB 0 position off S2 input 2 MCCB 0 position off S3 output switch 0 position off S4 maintenance bypass switch 0 position center Manual transfer switch auto...

Page 19: ...ontrol circuits will be energized and will start functioning 3 Select your PREFERRED source Default factory setting is Source 1 You can change your selection using the SETTINGS MENU 4 Check from the m...

Page 20: ...m that the load is switched to the source selected by the manual XFER switch S6 3 Then turn the Maintenance Bypass Switch S4 to the selected source for maintenance See the maintenance bypass message o...

Page 21: ...ce source side and follow that the corresponding static switch either SS1 or SS2 is turned on 3 Turn on the output switch S3 4 Change the position of the maintenance bypass switch S4 to 0 lock it agai...

Page 22: ...ormal Operation 1 Turn off all loads which are connected to STS output 2 Turn off the output switch S3 3 Turn off input switches S1 and S2 4 Check that the Maintenance Bypass Switch S4 is in 0 positio...

Page 23: ...follows First line status menu items and measured parameters Second line time shared for alarms The A2 at the beginning of the alarm message on the second line shows the standard alarm code the remai...

Page 24: ...of this message are preferred source is bad and load transferred to alternate source or transfer test is being performed MANUAL TRANSFER Load is transferred to one of the input sources statically Thi...

Page 25: ...shows the output load percentage of STS for each output phase 100 is maximum capacity of STS If the load is above 100 the STS gives overload message OPI 090 100 120A This menu item shows the output cu...

Page 26: ...arm occurs If manual XFER is active from panel or manual transfer switch If maintenance bypass is applied If test is disabled from any reason XF TEST DISABLED will be showned ENTR INHIBIT RST If the S...

Page 27: ...s are arranged as Bitmap and the meanings are as follows Code Description Code 0 No alarm on Source 1 Source normal Code 1 Source 1 input voltage out of tolerant Code 2 Source 1 phase sequency bad Cod...

Page 28: ...the overload behavior of the STS OPTION DESCRIPTION DISABLE Electronic Overload protection feature is disabled STS continues to supply the load during overcurrents The supply current is limited only b...

Page 29: ...FLYING This option determines non synchronous retransfer from alternate to preferred source OPTION DESCRIPTION WAIT SYNC During retransfer from alternate to preferred source wait until two input sour...

Page 30: ...___ This menu is for service personnel only there is no user defined parameter or option on this menu please refer to service manual of STS unit for detailed information SERVICE PASSWORD _____________...

Page 31: ...A3 SYNCHRON BAD Shows that 2 input sources are not synchronized A4 OVERLOAD Output current of the STS is too high A5 NSYNC INHIBIT Non synchronous transfer is disabled by the user and during non sync...

Page 32: ...m panel or RS232 for adjustment MANUAL TRANSFER Manual transfer is activated by the user MAINT BYPASS S1 Maintenance bypass switch is on S1 position MAINT BYPASS S2 Maintenance bypass switch is on S2...

Page 33: ...15 External power input COMMUNICATION INTERFACE AND REMOTE MANAGEMENT The following information contains standard communication interface for INFOSTS Additional RS485 communication for long distance...

Page 34: ...ve with PC so PC can send any command to STS in this case unauthorized users can change parameters and send unwanted commands to STS To prevent unauthorized access to STS from serial port two level se...

Page 35: ...s Inputs Emergency stop If the user presses the external emergency stop switch for more then 2 seconds STS shutdowns the output OPTIONAL TCP IP ADAPTOR On standard models RS232 serial port is installe...

Page 36: ...e max 10 msec in 0 current mode 0 25 sec adjustable in delay mode and in 0 current mode Flying transfer Available Load PF range 0 6 lag to 0 9 lead PROGRAMMING Synchron Non synchron with delay Transfe...

Page 37: ...s 5 push buttons interactive with LCD panel Manual transfer to S1 From panel or RS232 Manual transfer to S2 From panel or RS232 Cancel manual transfer From panel or RS232 Transfer test From panel os R...

Page 38: ...ARM On Output phase or alternance loss sense enabled Off Output phase or alternance loss sense disabled Manual transfer mode 0 current Flying COMMUNICATION INTERFACE Emergency stop input 2 seconds del...

Page 39: ...30 mm 580 mm Weight 175 Kg 205 Kg 220 Kg 240 Kg Ventilation Forced air cooling by internal fans Cooling outlet From top Cable Entry From base on front Protection IP20 Color RAL9011 Service access From...

Page 40: ...wer the questions before calling the service 1 First off all please note the error code AXX on the second line of the STS LCD panel 2 Did you follow the operation procedure Did it happen on installati...

Page 41: ...ice Installer This utility program finds all network connected TCP IP adaptor devices If it fails please change your network settings IP address and subnet mask as static IP to the following values t...

Page 42: ...P adaptor device on the list double click on it and device details will be shown at the window Select the related TCP IP adaptor and click on Assign IP button for adjusting the adaptor to your network...

Page 43: ...ent from 10 0 0 xxx or subnet mask is different from 255 0 0 0 value the unit connection may be lost in this case please re adjust your PC network settings to these network values Figure 25 After adju...

Page 44: ...guration at the left side menu click on Serial settings serial configuration page comes to screen Parameter value Baud rate 2400 Click on OK button for update settings at the end of page Figure 27 For...

Page 45: ...44 Figure 28...

Page 46: ...ller to Remote STS 1 white window check that TCP IP port factory setting value is 10001 Click on Save button From STS CONTROL main window select Connect to Remote STS on 10 0 0 190 or any IP and click...

Page 47: ...NOTES...

Reviews: