31
9 Technical Specifications (15kVA Saver Plus DSP UPS)
Physical Specifications
Height
970 cm
Width
43 cm
Depth
82 cm
Weight
164 kg
Environmental Conditions
Operating
0 ... +40 [
°
C]
Operating
%20 ... %80
Temperature
Storage
-15 ... +55 [
°
C]
Relative Humidity
Storage
%20 ... %95
Electrical Specifications
System
Efficiency (with Input voltage: 220 V and full capacity batteries)
%100 linear
Load
%50 linear
Load
%100 non-linear
Load(cos
Φ
=0.7)
%50 nonlinear
Load(cos
Φ
=0.7)
Normal Operating (online mode)
>91,1
>89,0
>90,1
>88,6
Green Mode (by-pass mode)
>95,3
>92,3
>95,2
>92
Cross-Sections of Connection Cables
Ground Connection
16 mm
2
Input phase & neutral
16 mm
2
By-pass connection
25 mm
2
Output phase & neutral
25 mm
2
Battery
16 mm
2
Input
Phase Number
3 Phase + Neutral
Nominal Voltage
220 V Nominal
Frequency
50 Hz
Input voltage range at mains running <%47
Load
80
– 280 V
Full load
155 – 280 V
Input current Limit
52 A
Fuse current and type
40A, C Type
Power factor (at nominal input voltage )
Full load
>0,953
Half load
>0,931
Output (online & battery Operation )
Phase number
1
Voltage wave form
Sinusoidal
Nominal Power (kVA)
15000 VA
Nominal active power
10500 W
Nominal voltage
220 V Nominal
current
68
A
Frequency (mains present) Locked to the input
Frequency ( normal run )
50 Hz
±
% 0,005
Power factor
0,7
Crest Factor at nominal power
3:1
Static voltage regulation ( 0 - %100 load variation )
≤
%1
Voltage Total Harmonic Distortion(THD) [%]
%0 Load
<2,0
%25 linear Load
<4,7
%25 non-linear (cos
Φ
=0,7) load
<4,5
%50 linear Load
<3,2
%50 non-linear (cos
Φ
=0,7) load
<4,2
%75 linear Load
<2,9
%75 non-linear (cos
Φ
=0,7) load
<5,0
%100 linear Load
<3,3
%100 nonlinear (cos
Φ
=0,7) load
<6,4
Overload holding time (0% to %150 load variation)
61,8 s
NOTE
Overload holding time is a software parameter and can be changed upon request
Fault removal current
For B type fuse
<24A
For C type fuse
<12 A
Summary of Contents for SAVER PLUS DSP SERIES