NOTE 5:
The cable for for E4 Evolution II + 60k TT S HV or E4 Evolution II 30k TT (S) LV should be
able to withstand over 120A current. It is recommended to use 25mm²/AWG 4 for safety and
efficiency.
NOTE 6:
The cable for E4 Evolution II + 80k TT S HV or E4 Evolution II 40k TT (S) LV should be able
to withstand over 160A current. It is recommended to use 35mm²/AWG 2 for safety and efficiency.
5) Remove the terminal block cover on the rear panel of UPS. Then connect the wires according to the
following terminal block diagrams: (Connect the earth wire first when making wire connection. Disconnect
the earth wire last when making wire disconnection!)