4-2. X2 - Remote EPO Input Port
The UPS is equipped with Emergency Power off (EPO) Function that can be operated by a remote contact
assigned by the users. Users can set the logic (N.C or N.O) of this EPO Function through LCD panel.
X2 is the remote EPO input port. This port is shown below
Remote EPO Input Port
Description of Remote EPO Port
EPO Logic Setting
Position
Description
N.C
X2.1 & X2.2
EPO activated when Opened X2.1 & X2.2
N.O
X2.1 & X2.2
EPO activated when Shorted X2.1 & X2.2
If EPO Logic setting is Normal Closed (N.C), EPO is triggered when pins 1 and pin 2 of X1 are opened.
Otherwise, EPO Logic setting is Normal Opened (N.O). EPO is triggered when pin 1 and pin 2 of X2 are
closed.
Note:
1. EPO action shuts down the rectifiers, inverters and static transfer switch. But it does not internally
disconnect the input power supply.
2. The default setting of the EPO function logic is Normal Opened (N.O).
4-3. Other Communication Interface
4-3-1. Extra Comm. Slot
There is an optional slot to allow
Extra Comm. Card
. This option can enhance the communication
capability of the UPS. It provides an additional SNMP slot, dry contact I/P & O/P signals and temperature
sensor ports.
4-3-2. Local Communication Ports – RS232 & USB
This UPS is equipped with one RS-232 port and one USB port.
Note
: The RS232 and USB ports
CANNOT
work simultaneously.
4-3-3. SNMP Slot
The SNMP card or AS400 card can be inserted into this slot to work with the UPS.