18: Output A voltage calibration
Interface Setting
Parameter 2:
it always shows
OP.V
as output voltage.
Parameter 3:
it shows the internal measurement value of the output A
voltage, and you can calibrate it by pressing
Up
or
Down
according to
the measurement from an external voltage meter. The calibration result
will be effective by pressing
Enter
. The calibration range is limited within
+/-9V. This function is normally used for parallel operation.
19: Output B voltage calibration
Interface Setting
Parameter 2:
it always shows
OP.V
as output voltage*.
Parameter 3:
it shows the internal measurement value of the output B
voltage, and you can calibrate it by pressing
Up
or
Down
according to
the measurement from an external voltage meter. The calibration result
will be effective by pressing
Enter
. The calibration range is limited within
+/-9V. This function is normally used for parallel operation.
*It will display number 1 under
to represent the output B
voltage.
20: Output C voltage calibration
Interface Setting
Parameter 2:
it always shows
OP.V
as output voltage.
Parameter 3:
it shows the internal measurement value of the output C
voltage, and you can calibrate it by pressing
Up
or
Down
according to
the measurement from an external voltage meter. The calibration result
will be effective by pressing
Enter
. The calibration range is limited within
+/-9V. This function is normally used for parallel operation.
*It will display number 2 under
to represent the output C
voltage.