Troubleshooting Guide
4.1 Trouble Shooting
When the UPS malfunctions during operation, you may check the followings:
a.
Are the wirings of input and output correct?
b.
If the input voltage of the Utility is within the input window of the UPS?
In case problems or symptoms still exist, please proceed the followings for proper adjustment.
Should the problem persists, please contact your local distributor for help.
Situation Check
Items
Solution
UPS Red Fault
LED lights up
Check the error code
shown on the LCD screen
Er05,
&
Er06, Er10, Er12 Er28 &
EPO
Er11, Er33
Er14
Er15
Er16, Er27
Er21
Er24
other error code
Check to see if the battery connection is properly done,
then re-charge the batteries for 8 hours to see whether
the UPS may backup normally; otherwise, consult your
local distributor right away.
If the CB3 is tripped, please turn off the UPS completely
and keep the CAM switch at position INV before
pressing CB3. Then remove some uncritical load at the
UPS output end. If any damage of the coating of AC
power cord, please replace a new one.
Remove the short circuit occurred at the EPO terminal.
Remove the objects blocked onto the ventilation holes.
Check the cooling fans on rear panel are working
normally.
Make sure the UPS is operated normally. If it is on CVCF
mode, you have to turn off and turn on the UPS again.
All of parameters except ID Number in the parallel UPS
must be same. Please refer chapter 3.5.5 to set them
again
Reconnect the RJ-45 wire or set a UPS with ID=1.
When the UPS is on CVCF mode, it is prohibited to have
bypass input. You have to turn off the UPS and bypass
input and re-start the UPS.
Consult your local distributor for help.
UPS fails to
offer battery
backup or its
back up time
is shorter
than its
calculation.
If the backup time is still too short after 8 hours of
charge, please contact your local distributor for battery
replacement.
UPS locks
itself and it
can not be
turned off.
Please refer to chapter 3.5.6 to trouble shoot the
problem; otherwise, consult your local distributor for
help.