Battery Study: When battery aging occurs, this function is to calibrate backup time
estimation. It’
s a self-learning function for battery. Currently, this function is not available.
◼
Enable: When enabled, UPS will enter battery test mode one time. It will calibrate
backup time estimation by calibrating battery virtual capacity according to a complete
charging and discharging process.
◼
Disable: When disabled, the backup time will not be updated during the charging and
discharging process.
➢
Battery Initial:
◼
Yes: When selected, the battery virtual capacity will be initialized to 100%. Because
battery study is a self-learning function, after the battery is used for a long time, the
virtual capacity of the battery will be continuously updated based on each full charging
process. After replacing the new battery, the virtual capacity of the battery needs to be
initialized.
◼
No: When selected, the virtual capacity of the battery will not be initialized.
➢
BATT Cali Value: Calibrate backup time.
➢
BATT TEMP Compensation: Compensate charging voltage according to battery
temperature
.
MISCELLANEOUS
Miscellaneous setting page
➢
Auto Restart:
◼
Enable:
After “Enable” is s
et, once UPS shutdown occurs due to low battery and
then utility restores, the UPS will return to line mode.