UPS SELFTEST
This function is only effective when UPS type s
etting is “HV”. T
herefore, please disconnect all
loads and utility first before executing this function. Then, please change UPS t
ype to “HV”.
For the detailed operation,
please check “System
Paramet
er” menu under Advance
➔
Maintainer directory.
After changing UPS type to
“HV”, you
have to restart the UPS. After the UPS is restarted,
please enter Advance screen and enter Maintainer password. It will
show “UPS SELFTEST”
selection in the screen. In the screen, all tested items ar
e shown “unknown”. Simply cli
ck
“UPS SELFTEST”
button, the UPS will start self-test. If the UPS is normal, it will show
“Normal” in all co
lumns. Oth
erwise, “Unknown” will be di
splayed in the columns.
After the UPS self-test passes, the screen will be black automatically. If the UPS self-test is
abnormal, it will stop on the abnormal screen. At this time, the maintenance personnel should
repair the UPS according to the self-test instructions. Please check local dealer for self-test
instructions.